Powtran PI9000-S Series User manual

Foreword
Thank you for choosing POWTRAN PI9000-S Series Frequency Inverter. This product
made by POWTRAN is based on years of experience in professional production and
sale, and designed for solarpump inverter
This manual provides user the relevant precautions on installation, operational
parameter setting, abnormal diagnosis, routine maintenance and safe use. In order to
ensure correct installation and operation of the frequency converter, please carefully
read this manual before installing it.
For any problem when using this product, please contact your local dealer authorized by
Powtran or directly contact us, our professionals are happy to serve you.
The end-users should hold this manual, and keep it well for future maintenance & care,
and other application occasions. For any problem within the warranty period, please fill
out the warranty card and fax it to theour authorized dealer.
The contents of this manual are subject to change without prior notice. To obtain the
latest information, please visit our website.
For more product information, please visit: http:// www.powtran.com
POWTRAN
April, 2014

Table of contents
Foreword ............................................................................................................... 1
Table of contents....................................................................................................2
Chapter 1.Inspection and safety precautions............................................................ 1
1-1. Inspection after unpacking............................................................................... 1
1-1-1.Instructions on nameplate.............................................................................. 1
1-1-2.Safety precautions......................................................................................... 1
1-2. Safety precautions........................................................................................... 2
1-3. Precautions...................................................................................................... 4
1-4. Scope of applications.......................................................................................6
Chapter 2 Standard specifications ........................................................................... 8
2-1. Technical specifications................................................................................... 8
2-2. Standard specifications.................................................................................... 9
2-3. Dimensions...................................................................................................13
2-3-1. Appearance and installation holes size......................................................... 13
2-3-2. PI9100 series.............................................................................................. 13
2-3-3. PI9200 series.............................................................................................. 15
2-3-4. Keyboard size diagram............................................................................... 16
Chapter 3 Keyboard.............................................................................................. 17
3-1. Keyboard description..................................................................................... 17
3-2. Keyboard Indicators......................................................................................17
3-3. Description of operation panel keys................................................................ 18
3-4. Examples of parameter settings......................................................................18
3-4-1. Instructions on viewing and modifying function code.................................. 18
3-4-2. Theway to read parameters in various status...............................................20
3-4-3. Password settings....................................................................................... 20
3-4-4. Motor parameter auto tunning..................................................................... 20
Chapter 4 Commissioning.....................................................................................22
Chapter 5 Function parameter............................................................................... 23
5-1. Menu grouping..............................................................................................23

5-1-1. d0Group - Monitoring function group .........................................................24
5-1-2. F0 Group -Basic function group..................................................................26
5-1-3. F1 Input terminals group.............................................................................28
5-1-4. F2 Group - Output terminals group .............................................................33
5-1-5. F3 Group - Start and stop control group.......................................................37
5-1-6. F4 V/Fcontrol group...................................................................................38
5-1-7. F6 Keybaord and Display ...........................................................................39
5-1-8. F7 Group - Auxiliary function group...........................................................40
5-1-9. F8 Group - Fault and protection..................................................................41
5-1-10. F9 Group - Communication parameter.......................................................43
5-1-11. FB Group - Control optimization parameters .............................................45
5-1-12. E0 Solar water pump special group ...........................................................45
5-1-13. E2 PID Function Group............................................................................47
5-1-14. E3 Virtual terminal group..........................................................................49
5-1-15. b0 Motor parameters group.......................................................................52
5-1-16. y0 Function code management group ........................................................54
5-1-17. y1 Fault query group.................................................................................57
Chapter 6 EMC (Electromagnetic Compatibility)...................................................61
6-1. Definition......................................................................................................61
6-2. EMC standard ...............................................................................................61
6-3. EMC directive...............................................................................................61
6-3-1. Harmonic effect..........................................................................................61
6-3-2. Electromagnetic interference and installation precautions ............................61
6-3-3. Remedies for the interferences from the surrounding electromagnetic
equipments to the inverter.....................................................................................62
6-3-4. Remedies for the interferences from the inverter to the surrounding
electromagnetic equipments..................................................................................62
6-3-5. Remedies for leakage current......................................................................62
6-3-6. Precautions on installing EMC input filter at the input end of power supply..63
Chapter 7 Troubleshooting....................................................................................64
7-1.Fault alarm and countermeasures ....................................................................64
Chapter 8 Installation and Commissioning guidance..............................................71

8-1. Operating environment.................................................................................. 71
8-2. Installation direction and space......................................................................71
8-3. Wiring diagram ............................................................................................. 71
Chapter 9 Maintenance and Repair........................................................................81
9-1. Inspection and Maintenance........................................................................... 81
9-2. Parts for regular replacement .........................................................................82
9-3. Storage..........................................................................................................82
9-4. Capacitor ...................................................................................................... 82
9-4-1. Capacitor rebuilt.........................................................................................82
9-5. Measuring and readings.................................................................................83
Chapter 10 Warranty............................................................................................. 84
Appendix I Recommended solar array configuration.............................................. 85
Appendix II RS485 Communication protocol........................................................ 86
II-1 Communication protocol.............................................................................86
II-2 Check mode................................................................................................ 90
II-3 Definition of communication parameter address........................................... 92
Warranty Card......................................................................................................98

1
第
十
章
Chapter 1.Inspection and safety precautions
POWTRAN frequency inverters have been tested and inspected before leaving
factory. After purchasing, please check if its package is damaged due to careless
transportation, and if the specifications and model of the product are consistent with
your order requirements. For any problem, please contact your local authorized
POWTRAN dealer or directly contact this company.
1-1.Inspection after unpacking
※Check if that packing container contains this unit, one manual and one warranty
card.
※Check the nameplate on the side of the frequency inverter to ensure that the
product you have received is right the one you ordered.
1-1-1.Instructions on nameplate
Input Source Spec.
Output Power Spec.
Production Sequence Number
Inverter model
POWER
INPUT
OUTPUT
DALIAN POWTRAN TECHNOLOGY CO.,LTD.
MODEL
7.5kW
DC 1PH 350 750V
AC 0 17A 0 400Hz3PH 380V
PI9130-S 7R5G3
ZPB1A0100001
Output Spec.
Bar code
Production Address
AC 3PH 380V
1-1-2Safety precautions
Special model code:
S:Solar pump
Powtran Inverter
Rated Output Power
Example:7R5:7.5KW,004:4KW
Product function code:
G: General Load
Serial Code:
91:PI9130 series
92:PI9230 series
Input Voltage Level:
1:DC200-380v , Single phase AC 220V
2:DC200-380v , three phase AC 220V
3:DC350-750v , three phase AC 380V
Class code:
0:standard configuration
1: special 1configuration
2: special 2 configuration
3:With MCU keyboard.
Type Code:
A:Single IGBT
B: Integrated intelligent power
module (omitted)

Chapter1.Inspection and Safety Precautions
2
1-2.Safety precautions
Safetyprecautions in this manual are divided into the following two categories:
Danger: the dangers caused by failure to perform required operation, may result in
serious injury or even death;
Caution:the dangers caused by failure to perform required operation, may result in
moderate injury or minor injury, and equipment damage;
Process
Type
Explanation
Before
installation
Danger
● When unpacking, if control system with water,
parts missed or component damaged are found,
do not install!
● If packing list does not match the real name, do
not install!
● Gently carry with care, otherwise there is the risk
of damage to equipment!
● Please do not use the damaged driver or the
frequency inverter with missed pieces, otherwise
there is the risk of injury!
● Do not use your hand to touch the control system
components, otherwise there is the risk of
electrostatic damage!
When
installing
Danger
● Please install the unit on the metal or flame
retardant objects; away from combustible material.
Failure to do so may cause a fire!
● Never twist the mounting bolts of the equipment
components, especially the bolt with the red mark!
Note
● Do not let the lead wires or screws fall into the
driver. Otherwise which may cause damage to the
driver!
● Keep the driver installed in the place where less
vibration, avoid direct sunlight.
● When two or more converters are installed in a
cabinet, please pay attention to the installation
location, ensure the good heat dissipation effect.
When wiring
Danger
● Must comply with this manual's guidance, any
construction shall be performed by a professional
electrician, otherwise there would be the
unexpected risk !
● A circuit breaker must be set between the inverter
and the power supply to separate them, otherwise it
may cause a fire!
● Verify if power is a zero-energy status before
wiring, otherwise there is a risk of electric shock!
● The inverter shall be grounded correctly
according to standard specifications, otherwise
there is a danger of electrical shock!
● Ensure that the distribution line meets the
regional safety standards of EMC requirements.

Chapter1.Inspection and Safety Precautions
3
The diameter of used wire shall refer to the
recommendations of this manual. Otherwise it may
cause an accident!
● Never directly connect braking resistor to the DC
bus P(+) and P(-) terminals. Otherwise it may cause
a fire!
● Encoder must use the shielded wire, and the
shielding layer must ensure the single-ended
grounded!
Before
energizing
Note
● Please confirm whether the input power voltage
is same as the inverter rated voltage; wiring
positions of power input terminals(R, S, T) and
output terminals(U, V, W) are correct or not; and
note that if there is a short circuit in the peripheral
circuit connected to driver, if the connected lines
are tight, otherwise it may cause damage to the
driver!
● Do not need to perform withstand voltage test for
any part of the inverter, this product has been tested
before leaving factory. Otherwise it may cause an
accident!
Danger
● The inverter's cover plate must be closed before
power on. Otherwise it may cause an electric shock!
● Wiring of all external accessories must comply
with the guidance of this manual, please correctly
wiring in accordance with the circuit connection
methods described in this manual. Otherwise it may
cause an accident!
After
energizing
Danger
● Do not open cover plate after energizing.
Otherwise there is a risk of electric shock!
● Do not touch the driver and peripheral circuits
with wet hands. Otherwise there is a risk of electric
shock!
● Do not touch any input and output terminals of
the inverter. Otherwise there is a risk of electric
shock!
● The inverter automatically perform the safety
testing for the external strong electrical circuit in
the early stages of energizing, therefore never touch
the driver terminals(U, V, W) or motor terminals,
otherwise there is a risk of electric shock!
● If you need to identify the parameters, please pay
attention to the danger of injury during motor
rotation.Otherwise it may cause an accident!
● Please do not change the inverter manufacturer
parameters. Otherwise it may cause damage to this
unit!
During
Danger
● Do not touch the cooling fan and the discharge

Chapter1.Inspection and Safety Precautions
4
operation
resistor to feel the temperature. Otherwise it may
cause burns!
● Non-professional personnel is not allowed to
detect signal when operating. Doing so may cause
personal injury or damage to this unit!
Note
● When the inverter is operating, you should avoid
that objects fall into this unit.Otherwise cause
damage to this unit!
● Do not start/stop the driver by switching on/off
contactor. Otherwise cause damage to thisunit!
When
maintaining
Danger
● Do not perform repairs and maintenance for the
live electrical equipment. Otherwise there is a risk
of electric shock!
● The repairs and maintenance task can be
performed only when the inverter bus voltage is
lower than 36V,Otherwise, the residual charge from
capacitor would cause personal injury!
● Non-well-trained professional personnel is not
allowed to perform repairs and maintenance of
inverter. Doing this may cause personal injury or
damage to this unit!
● After replacing the inverter, parameter settings
must be redone, all pluggable plugs can be operated
only in the caseof powering off!
1-3.Precautions
N
o.
Type
Explanation
1
Motor insulation
inspection
Please perform motor insulation inspection for the first time
use, re-use after leaving unused for a long time as well as
regular check, in order to prevent damage to the inverter
because of the motor's winding insulation failure. Wiring
between motor and inverter shall be disconnected, it is
recommended that the 500V voltage type megger should be
adopted and insulation resistance shall be not less than 5MΩ.
2
Motor thermal
protection
If the rated capacity of the selected motor does not match the
inverter, especially when the inverter rated power is greater
than the motor rated power, be sure to adjust the motor
protection parameter values inside inverter or install thermal
relay in the front of motor for motor protection.
3
Run over
power
frequency
The inverter output frequency rang is 0Hz to
3200Hz(Maz.vector control only supports 300Hz). If the user
is required to run at 50Hz or more, please consider the
endurance of your mechanical devices.
4
Vibrations of
mechanical
device
Inverter output frequency may be encountered mechanical
resonance point of the load device, you can set jump
frequency parameter inside inverter to avoid the case.
5
Motor heat
The inverter output voltage is PWM wave that contains a

Chapter1.Inspection and Safety Precautions
5
and noise
certain amount of harmonics, so the temperature rise, noise
and vibration of motor show a slight higher than frequency
power frequency operation.
6
Output side
with piezo-
resistor or
capacitor for
improving
power factor
The inverter output is PWM wave, if the piezo-resistor for
lightning protection or the capacitor for improving power
factor is installed in the output side, which easily cause the
inverter instantaneous over-current or even cause damage to
the inverter. Please do not use.
7
Contactor or
switch used in
the inverter
input/output
terminals
If contactor is installed between power supply and inverter,
the contactor is not allowed to start/stop the inverter.
Necessarily need to use the contactor to control the inverter
start/stop, the interval should not be less than one hour.
Frequent charging and discharging may reduce the service
life of the inverter capacitor. If the contactor or switch is
equipped between output terminals and motor, the inverter
should be turned on/off without output status, otherwise
which easily lead to damage to the inverter module.
8
Use other
than the rated
voltage
PI series inverter is not suitable for use beyond the allowable
operating voltage described in this manual, which easily
cause damage to the parts inside inverter. If necessary, please
use the corresponding transformer to change voltage.
9
Never change
3-phase input
to 2-phase
input
Never change PI series 3-phase inverter to 2-phase one for
application. Otherwise it will lead to malfunction or damage
to the inverter.
10
Lightning
surge
protection
The series inverter is equipped with lightning over-current
protection device, so it has the ability of self-protection to
lightning induction. For the area where lightning is frequent,
user should also install the extra protection in the front of the
inverter.
11
High altitude
and derating
application
When the inverter is used in areas over 1000m altitude, it is
required to reduce frequency because the thin air will
decrease the cooling effect of inverter. Please consult our
technician for details on the application.
12
Special use
If the user need to use methods other than the suggested
wiring diagram provided in this manual, such as common DC
bus, please consult our technician.
13
Precautions
for scrap
disposal of
the inverter
When electrolytic capacitors on the main circuit and printed
circuit board as well as plastic parts are burned, it may produce
toxic gases.Please disposing as industrial waste.
14
Adaptive
motor
1) Standard adaptive motor shall be four-pole asynchronous
squirrel-cage induction motor or permanent magnet
synchronous motor. Apart from the said motors, please select
the inverter according to the motor rated current.
2) The cooling fan and the rotor shaft for non-inverter motor
are coaxially connected, the fan cooling effect is reduced

Chapter1.Inspection and Safety Precautions
6
when the rotational speed is reduced, therefore, when the
motor works in overheating occasions, a strong exhaust fan
should be retrofitted or replace non-inverter motor with the
inverter motor.
3) The inverter has built-in the adaptive motor standard
parameters, according to the actual situation, please identify
motor parameters or accordingly modify the default values to
try to meet the actual value, otherwise it will operation affect
and protection performance;
4) When short-circuit of cable or motor internal will activate
the inverter alarm, even bombing. Therefore, firstly perform
insulation short-circuit test for the initial installation of the
motor and cable, routine maintenance often also need to
perform such test. Note that the parts to be tested and the
inverter shall be disconnected completely when testing.
15
Others
1) Never connect the AC power to the inverter output
terminals(U, V, W).
2) Properly fix and lock the panel before powering on, so as
to avoid hurting the personal safety due to internal poor
capacitors.
3) Never perform wiring, checking and other operations after
power is turned on.
4) Do not touch the internal circuit board and its components
in order to avoid the risk of electric shock after this unit is
powered,
5) Do not touch internal circuit board and any parts after
powering off and within five minutes after keyboard indicator
lamp goes out, you must use the instrument to confirm that
internal capacitor has been discharged fully, otherwise there
is a danger of electric shock.
6) Body static electricity will seriously damage the internal
MOS field-effect transistors, etc., if there are not anti-static
measures, do not touch the printed circuit board and IGBT
internal device with hand, otherwise it may cause a
malfunction.
7)The ground terminal of the inverter(E or ) shall be
earthed firmly according to the provisions of the National
Electrical Safety and other relevant standards. Do not shut
down(power off) by pulling switch, and only cut off the
power until the motor stopping operation.
8) It is required to add the optional input filter attachment so
as to meet CE standards
1-4.Scope of applications
※This inverter is suitable for three-phase AC asynchronous motor and permanent
magnet synchronous motor.
※This inverter can only be used in those occasions recognized by this company, an
unapproved use may result in fire, electric shock, explosion and other accidents.

Chapter1.Inspection and Safety Precautions
7
※If the inverter is used in such equipments(e.g: equipments for lifting persons,
aviation systems, safety equipment, etc.) and its malfunction may result in
personal injury or even death. In this case, please consult the manufacturer for
your application.
Only the well-trained personnel can be allowed to operate this unit, please
carefully read the instre1tions on safety, installation, operation and
maintenance before use. The safe operation of this unit depends on proper
transport, installation, operation and maintenance!

8
第
十
章
Chapter 2 Standard specifications
2-1.Technical specifications
Inverter
model
Input voltage
Rated
output
power(kW
)
Rated
output
current
(A)
Adaptive
motor
Base
No.
PI9130-S 0R4G1
1-phase
AC 220V
±10%;
recommend
DC 200V~380V
0.4
2.5
0.4
9S2
PI9130-S 0R7G1
0.75
4
0.75
9S2
PI9130-S 1R5G1
1.5
7
1.5
9S2
PI9130-S 2R2G1
2.2
10
2.2
9S3
PI9130-S 004G1
4.0
16
4.0
9S4
PI9230-S 5R5G1
5.5
25
5.5
9L1
PI9130-S 0R4G2
3-phase
AC 220V
±10%;
recommend
DC 200V~380V
0.4
2.5
0.4
9S2
PI9130-S 0R7G2
0.75
4
0.75
9S2
PI9130-S 1R5G2
1.5
7
1.5
9S2
PI9130-S 2R2G2
2.2
10
2.2
9S3
PI9130-S 004G2
4.0
16
4
9S4
PI9230-S 5R5G2
5.5
25
5.5
9L1
PI9230-S 7R5G2
7.5
32
7.5
9L1
PI9230-S 011G2
11
45
11
9L2
PI9230-S 015G2
15.0
60
15.0
9L3
PI9130-S 0R7G3
3-phase
AC380V
±10%;
recommend
DC 350V~750V
0.75
2.5
0.75
9S2
PI9130-S 1R5G3
1.5
3.8
1.5
9S2
PI9130-S 2R2G3
2.2
5.1
2.2
9S2
PI9130-S 004G3
4.0
9
4.0
9S3
PI9130-S 5R5G3
5.5
13
5.5
9S3
PI9130-S 7R5G3
7.5
17
7.5
9S4
PI9230-S 011G3
11
25
11
9L1
PI9230-S 015G3
15
32
15
9L1
※Remarks:The power of solar modules should be up to 1.2 times higher than inverter
power
※Remarks:PI9130 distinguish between A and B two series,A is single IGBT,B is
integrated intelligent power modules,the specification of both parameters are the same.

Chapter2.Standard Specifications
9
2-2.Standard specifications
Items
Specifications
Power
Voltage and
frequency levels
Single-phase 220V±10%,50/60Hz±5%
Three-phase 220V±10%,50/60Hz±5%
Three-phase 380V±10%,50/60Hz±5%
Recommend pv
input DC
voltage range
G1/G2:DC 200~380V;
G3:DC 350~750V
Control system
Control system
High performance vector control inverter based on DSP
Control method
V/F control, vector control W/O PG
Automatic torque
boost function
Realize low frequency (1Hz) and large output torque
control under the V/F control mode.
Acceleration/de
celeration
control
Straight or S-curve mode. Four times available and time
range is 0.0 to 6500.0s.
V/F curve mode
Linear, square root/m-th power, custom V/F curve
Over load
capability
G type:rated current 150% - 1 minute, rated current 180% -
2 seconds
Maximum
frequency
Vector control:0 to 300Hz
V/F control:0 to 3200Hz
Carrier
Frequency
0.5 to 16kHz; automatically adjust carrier frequency
according to the load characteristics.
Input frequency
resolution
Digital setting: 0.01HzAnalog setting: maximum
frequency×0.1%
Start torque
G type: 0.5Hz/150% (vector control W/O PG)
Speed range
1:100 (vector control W/O PG)
Steady-speed
precision
Vector control W/O PG: ≤ ± 0.5% (rated synchronous
speed)
Torque response
≤ 40ms (vector control W/O PG)
Torque boost
Automatic torque boost; manual torque boost(0.1% to
30.0%)
DC braking
DC braking frequency: 0.0Hz to max. frequency, braking
time:
0.0 to 100.0 seconds, braking current value: 0.0% to
100.0%
Jogging control
Jog Frequency Range: 0.00Hz to max. frequency;
Jog Ac/deceleration time: 0.0s to 6500.0s
Multi-speed
operation
Achieve up to 16-speed operation through the control
terminal
Built-in PID
Easy to realize closed-loop control system for the process
control.

Chapter2.Standard Specifications
10
Items
Specifications
Automatic
voltage
regulation(AVR)
Automatically maintain a constant output voltage when the
voltage of electricity grid changes
The specific
function of solar
pump inveter
the biggest Optical power tracking,Light weak auto
sleep,Light intensity automatically wake up,High water
level automatic stop,Low water level automatic run,under
load protection.
Peronalization function
Self-inspection
of peripherals
after power-on
After powering on, peripheral equipment will perform
safety testing, such as ground, short circuit, etc.
Common DC bus
function
Multiple inverters can use a common DC bus.
Quick current
limiting
The current limiting algorithm is used to reduce the inverter
overcurrent probability, and improve whole unit anti-
interference capability.
Timing control
Timing control function: time setting range(0m to 6500m)
Running
Input signal
Running
method
Keyboard/terminal/communication
Frequency
setting
10 frequency settings available, including adjustable DC(0
to 10V), adjustable DC(0 to 20mA), panel potentiometer,
etc.
Start
signal
Rotate forward/reverse
Multi-
speed
At most 16-speed can be set(run by using the multi-function
terminals or program)
Emergenc
y stop
Interrupt controller output
Fault reset
When the protection function is active, you can automatically
or manually reset the fault condition.
PID feedback
signal
Including DC(0 to 10V), DC(0 to 20mA)
Output signal
Running
status
Motor status display, stop, ac/deceleration, constant speed,
program running status.
Fault
output
Contact capacity :normally closed contact 5A/AC 250V,
normally open contact 3A/AC 250V,1A/DC 30V.
Analog
output
Two-way analog output, 16 signals can be selected such as
frequency, current, voltage and other, output signal range (0
to 10V / 0 to 20mA).
Output
signal
At most 3-way output, there are 40 signals each way

Chapter2.Standard Specifications
11
Items
Specifications
Run function
Limit frequency, jump frequency, frequency compensation,
auto-tuning, PID control
DC current
braking
Built-in PID regulates braking current to ensure sufficient
braking torque under no overcurrent condition.
Running
command
channel
Three channels: operation panel, control terminals and
serial communication port. They can be switched through a
variety of ways.
Frequency
source
Total 5 frequency sources: digital, analog voltage, analog
current, multi-speed and serial port. They can be switched
through a variety of ways.
Input terminals
6 digital input terminals, compatible with active PNPor
NPN input mode, one of them can be for high-speed pulse
input(0 to 100 kHz square wave); 2 analog input terminals
for voltage or current input.
Output terminals
2 digital output terminals, oneof them can be for high-speed
pulse output(0 to 100kHz square wave); one relayoutput
terminal; 2 analog output terminals respectively for optional
range (0 to 20mAor 0 to 10V), they can be used to set
frequency, output frequency, speed and other physical
parameters.
Protection function
Inverter
protection
Overvoltage protection, undervoltage protection,
overcurrent protection, overload protection, overheat
protection, overcurrent stall protection, overvoltage stall
protection, losting-phase protection (optional),
communication error, PID feedback signal abnormalities,
and short circuit to ground protection.
IGBT
temperature
display
Displays current temperature IGBT
Inverter fan
control
Can be set
Instantaneous
power-down
restart
Less than 15 milliseconds: continuous operation.
More than 15 milliseconds: automatic detection of motor
speed, instantaneous power-down restart.
Speed start tracking
method
The inverter automatically tracks motor speed after it starts
Parameter
protection
function
Protect inverter parameters by setting administrator
Password and decoding

Chapter2.Standard Specifications
12
Items
Specifications
Display
LED/OL
ED
display
keyboard
Runni
ng
infor
matio
n
Monitoring objects including: running frequency, set
frequency, bus voltage, output voltage, output current,
output power, output torque, input terminal status, output
terminal status, analog AI1 value, analog AI2 value, motor
Actual running speed,PID set value percentage, PID
feedback value percentage.
Error
messa
ge
At most save three error message, and the time, type,
voltage, current, frequency and work status can be queried
when the failure is occurred.
LED display
Display parameters
OLED display
Optional, prompts operation content in Chinese/English
text.
Copy parameter
Can upload and download function code information of
frequency converter, rapid replication parameters.
Key lock and
function
selection
Lock part or allof keys, define the function scopeof some
keys to prevent misuse.
Commu
nication
RS485
The optional completely isolated RS485 communication
module can communicate with the host computer.
Environment
Environment
temperature
-10 ℃to 40 ℃(temperature at 40 ℃to 50 ℃, please
derating for use)
Storage
temperature
-20 ℃to 65 ℃
Environment
humidity
Less than 90% R.H, no condensation.
Vibration
Below 5.9m/s²(= 0.6g)
Application sites
Indoor whereno sunlight or corrosive, explosive gas and
water vapor,dust, flammable gas, oil mist, water vapor,
drip or salt, etc.
Altitude
Below 1000m
Pollution degree
2
Product standard
Product adopts
safety standards.
IEC61800-5-1:2007
Product adopts
EMC standards.
IEC61800-3:2005
Cooling method
Forced air cooling and natural air cooling

Chapter2.Standard Specifications
13
2-3.Dimensions
2-3-1.Appearance and installation holes size
2-3-2.PI9100 series
1. 9S2 to 9S4
b
W
a
L
H
d
d
WARNING
Refer to the operation manual when adjust or inspect.
High voltage inside.Maintenance by the well-trained
personnel.
Confirm the output or control Confirm the output or
control wires are not grounded.
Perform parts replacement after discharge.
1) 9S2
操作面板
上盖板
活动盖板
控制电缆入口
整机固定孔
防护密封片
安装位(可选)
普传变频器铭牌
风道进风口
Top cover plate
Operation panel
Sealing guard
mounting position
(optional)
Fixing holes
Nameplate
Movable cover plate
Control cable inlet
Air duct inlet

Chapter2.Standard Specifications
14
Power
supply
level
Type
Power
(kW)
Dimensions
Installation size
L
W
H
a
b
d
1-phase
220V
G
0.4 to 1.5
185
120
165
174
108
Ø5.3
3-phase
220V
G
0.4 to 1.5
3-phase
380V
G
0.75 to 2.2
2) 9S3
Power supply
level
Type
Power
(kW)
Dimensions
Installation size
L
W
H
a
b
d
1-phase 220V
G
2.2
220
150
182
209
138
Ø5.3
3-phase 220V
G
2.2
3-phase 380V
G
4.0 to 5.5
3) 9S4
Power
supply
level
Type
Power
(kW)
Dimensions
Installation size
L
W
H
a
b
d
1-phase
220V
G
4.0
285
180
200
272
167
Ø5.5
3-phase
220V
G
4.0
3-phase
380V
G
7.5

Chapter2.Standard Specifications
15
2-3-3.PI9200 series
2. 9L1 to 9L3
bH
W
a
L
d
WARNING
Read instruction manual carefully before installation
and operation
High voltage inslde. Maintenance shorld be performed
by well-trained personel
Make sure to connect the ground terminal before
connecting orther terminals
Perform maintenance or inspection after the charge
LED turns off(fully discharged)
Power
supply
level
Type
Power
(kW)
Base
No.
Dimensions
Installation size
L
W
H
a
b
d
1-
phase
220V
G
5.5
9L1
360
220
225
340
150
Ø10
3-
phase
220V
G
5.5~7.5
3-
phase
380V
G
11~15
3-
phase
220V
G
11
9L2
435
275
258
415
165
Ø10
3-
phase
220V
G
15
9L3
480
296
262
460
200
Ø10

Chapter2.Standard Specifications
16
2-3-4.Keyboard size diagram
JP6E9100 size diagram:
JP6D9200 keyboard case size diagram:
Install keyboard case on the panel, opening square hole is
required:(76±0.1)*(123±0.1)
Table of contents
Other Powtran Inverter manuals

Powtran
Powtran PI500-E Series User manual

Powtran
Powtran PI8600 F Series User manual

Powtran
Powtran PI9000 series User manual

Powtran
Powtran PI160 Series User manual

Powtran
Powtran PI9100 Series User manual

Powtran
Powtran PI500A Series User manual

Powtran
Powtran PI500-S Series User manual

Powtran
Powtran PI7500 Series User manual

Powtran
Powtran PI500A-S Series User manual

Powtran
Powtran PS9500 Series User manual