SectionII.Installation&StandbyCircuit
2-5-2DescriptiontoControlCircuitTerminals.
Class
Terminal
Description Function
COM Common point forcontrol
commands
F05=1, Edgetriggers(F62=0),and runsforwardinfalling
edge, stopsinrising edge
FWD Forwardrotationcommand F05=3, Leveltriggers(F62=0/1/2)
F05=1, Edgetriggers(F62=0), andrunsreverseinfalling
edge, stopsinrising edge.
REV Reverserotation command F05=3, Leveltriggers(F62=0/1/2)
JOG Jog command
Leveltriggers, and executesJOG command inalowerlevel,
stopsinahigh level
Multi-step speed/acceleration
F63=1/2,Short-circuited toCOMtocompose7-stepspeed
and acceleration, leveltriggers, effectiveinalowerlevel
Rising/Falling control F04=4,forrising control
SS1
Frequency mode switch Switchthe frequency settingmodewithSS2, SS3
Multi-step speed/acceleration
F63=1/2,Short-circuited toCOMtocompose7-stepspeed
and acceleration, leveltriggers, effectiveinalowerlevel
Rising/Falling control F04=4,forfalling control
SS2
Frequency mode switch Switchthe frequency settingmodewithSS1,SS3
Multi-step speed/acceleration
Short-circuited toCOMtocompose7-stepspeedand
acceleration, leveltriggers, effectiveinalowerlevel
JOG control F63=3COMis short-circuited toSS3toexecuteJOG
reversecommand, toJOG toexecuteJOG forward
command, andthe previousJOG direction is invalid.
Three-line running control F63=1/2,F62=2Three-line terminalrunning fordetails
Program running restart Forselecting theprogram runningrestartmode
Rising/Falling control F04=4,forfalling control
SS3
Frequency mode switch Switchthe frequency settingmodewithSS1,SS2
FRE Free Run
Leveltriggers, and executesfree stop command inalower
level
Control signal
RST Restore Leveltriggers, executesrestorecommand infalling edge.
TA1/
TB1/TC1
Output signal5 TA1-TC1is open and
TB1-TC1is closed (programmable)
Output
signal
SPA/COM
Output signal1 Output open set signalwhen action (24VDC/50Ma)
SectionII.Installation&StandbyCircuit
V1,V3 PowerSupply +10V, GND
V2 Voltage Input signal Rangeis adjustablein0~10V
I2 CurrentInput signal Rangeis adjustablein0~20mA
V1 PowerSupply of DA1 Used forPowerSupply whenDA1selectscurrent output
Analog Input and output
signal
DA1 Multi-functionanalogsignal
output1 0~10/1~5VDC
0~20/4~20mA
24V PowerPositiveterminal
Auxiliary
Power
COM Common point
Maximaloutput 24V/200mA. COMandV3couldnotnever
be short-circuited.
2-6.ConnectionPrecautions
Dontinstallpowerfactorcapacitanceorresistance-capacitance
absorbingdevicebetweentheoutputterminalsU,V,Wofthe
frequency inverter.
Todisassembleorreplacethemotor,theinputpowersupplymustbe
turnedoff forthefrequency inverter.
Themotororpowersupplycanbeswitchedon/offonlyafterthe
inverterstopsitsoutput.
Inordertominimizetheeffect ofelectromagneticinterference, asurge
absorbingdeviceshouldbeinstalledif usedelectromagneticcontactor
and relay,etc. isneartothefrequency inverter.
Forexternalcontroloffrequency inverter,aisolationdeviceshouldbe
usedforthecontrollinesorscreenedcableshouldbeused.
Ascreenedcableshouldbeusedasthesignalconnectionlinefor
inputcommand and mustberoutedseparatelyaswell,and ithad
betterbeinstalledfarfromthemaincircuit.
Whenthecarrierfrequency isless than3kHz,thedistancebetween
thefrequency inverterand motormustnotbegreaterthan50meters
(maximum).Whenitisabove4kHz,thisdistanceshouldbereduced.
Thecableforthisconnectionhad betterbelaidinmetalconduit.
If thefrequency inverterisequippedwithperipheraldevices(suchas
filter,reactor),firstmeasureitsinsulationresistancetotheearthwith
1000Vmegohmmeter,andensuretheresistancevalueisnotbelow
4MΩ.
If thefrequency invertermust bestartedfrequently,dontswitchoff its