PR electronics 4511 User manual

PERFORMANCE
MADE
SMARTER
Product Manual
4511
Communication enabler
TEMPERATURE | I.S. INTERFACES | COMMUNICATION INTERFACES | MULTIFUNCTIONAL | ISOLATION | DISPLAY
No. 4511V101-UK
From serial no.: 141590001

6 Product Pillars
to meet your every need
With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six
product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial
and factory automation. All our products comply with or surpass the highest industry standards, ensuring reliability in even
the harshest of environments and have a 5-year warranty for greater peace of mind.
Individually outstanding, unrivalled in combination
Our range of temperature transmitters and sensors provides the highest level of signal integrity from the
measurement point to your control system. You can convert industrial process temperature signals to analog, bus or
digital communications using a highly reliable point-to-point solution with a fast response time, automatic self-
calibration, sensor error detection, low drift, and top EMC performance in any environment.
Our unique range of single devices covering multiple applications is easily deployable as your site standard. Having
one variant that applies to a broad range of applications can reduce your installation time and training, and greatly
simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low
power consumption, immunity to electrical noise and simple programming.
We provide inexpensive, easy-to-use, future-ready communication interfaces that can access your PR installed base
of products. All the interfaces are detachable, have a built-in display for readout of process values and diagnostics,
and can be configured via push-buttons. Product specific functionality includes communication via Modbus and
Bluetooth and remote access using our PR Process Supervisor (PPS) application, available for iOS and Android.
Our display range is characterized by its flexibility and stability. The devices meet nearly every demand for display
readout of process signals, and have universal input and power supply capabilities. They provide a real-time
measurement of your process value no matter the industry, and are engineered to provide a user-friendly and
reliable relay of information, even in demanding environments.
We deliver the safest signals by validating our products against the toughest safety standards. Through our
commitment to innovation, we have made pioneering achievements in developing I.S. interfaces with SIL 2 Full
Assessment that are both efficient and cost-effective. Our comprehensive range of analog and digital intrinsically
safe isolation barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard.
Our backplanes further simplify large installations and provide seamless integration to standard DCS systems.
Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology to provide exceptional
performance and EMC-immunity for dedicated applications at a very low total cost of ownership. They can be
stacked both vertically and horizontally with no air gap separation between units required.

4511V101-UK 1
Communication enabler
4511
Contents
Warning ................................................................................................ 2
Symbol identification .................................................................................... 2
Safety instructions ...................................................................................... 3
Applications ............................................................................................ 4
Technical characteristics ................................................................................. 4
Mounting / installation / programming .................................................................... 4
Mounting on a 4000 / 9000 device ....................................................................... 5
Order ................................................................................................... 6
Electrical specifications .................................................................................. 6
4511 installation examples .............................................................................. 7
Modbus basics .......................................................................................... 8
4511 Modbus parameter settings ........................................................................ 9
4511 Modbus settings - routing diagram.................................................................. 10

2 4511V101-UK
Warning
This device is designed for connection to hazardous electric voltages. Ignoring this warning can result in
severe personal injury or mechanical damage.
To avoid the risk of electric shock and fire, the safety instructions of this guide must be observed and
the guidelines followed. The specifications must not be exceeded, and the device must only be applied
as described in the following.
Prior to the commissioning of the device, this installation guide must be examined carefully.
Only qualified personnel (technicians) should install this device.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment may be impaired.
Warning
Until the device is fixed, do not connect hazardous voltages to the device. The following operations
should only be carried out on a disconnected device and under ESD safe conditions:
General mounting, connection and disconnection of Modbus cable.
Troubleshooting the device.
Warning
Repair of the device must be done by PR electronics A/S only.
Symbol identification
Triangle with an exclamation mark: Read the manual before installation and commissioning of the
device in order to avoid incidents that could lead to personal injury or mechanical damage.
The CE mark proves the compliance of the device with the essential requirements of the directives.
The double insulation symbol shows that the device is protected by double or reinforced insulation.
Ex devices have been approved according to the ATEX directive for use in connection with installations
in explosive areas.
GENERAL
CAUTION
HAZARD-
OUS
VOLTAGE

4511V101-UK 3
Safety instructions
Receipt and unpacking
Unpack the device without damaging it and check whether the device type corresponds to the one ordered. The packing
should always follow the device until this has been permanently mounted.
Environment
The device is manufactured for indoor use. Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as
well as rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be
avoided by way of ventilation.
The device may be used in Overvoltage Category II, Pollution Degree 2 at an altitude up to 2000 m.
Mounting
Only qualified technicians who are familiar with the technical terms, warnings, and instructions in this installation guide and
who are able to follow these should connect the device. Only devices which are undamaged and free of moist and dust may be
installed. The device may be installed and supplied by PR electronics 4000 and 9000 series only.
Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com
Calibration and Adjustment
During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the
specifications of this manual. The technician must use tools and instruments that are safe to use.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
IECEx, ATEX installation in Zone 2
IECEx DEK 13.0026 X ..................................................Ex nA IIC T5 Gc
DEKRA 13ATEX0098 X.................................................II 3 G Ex nA IIC T5 Gc
For safe installation the following must be observed
The device must be installed by qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
The devices must be installed in a suitable enclosure providing a degree of protection of at least IP54 according to EN60529,
taking into account the environmental conditions under which the equipment will be used.
To prevent ignition of the explosive atmospheres do not separate connectors when energized and an explosive gas mixture is
present.
To avoid the risk of explosion due to electrostatic charging of the enclosure, do not handle the units unless the area is known
to be safe, or appropriate safety measures are taken to avoid electrostatic discharge.
Liability
To the extent the instructions in this manual are not strictly observed, the customer cannot advance a demand against PR
electronics A/S that would otherwise exist according to the concluded sales agreement.

4 4511V101-UK
Communication enabler
4511
• Programming display for system 4000 and 9000 devices
• Modbus RTU protocol interface over RS-485
• Monitor process value from the built-in display
• High 2.5 kV isolation to host unit
• Shielded RJ45 Modbus connector on top
Applications
• The 4511 detachable display adds Modbus RTU RS-485 serial communications to all current and future 4000/9000 units.
• The unit converts a wide array of sensors and analog device signals measured by the system 4000, like uni- and bipolar
mA and voltage signals, potentiometer, Lin. R, RTD and TC, to a Modbus communication line signal.
• When mounted on a system 9000 device any signal coming from or going to I.S. classified area, like AI, AO, DI and DO
signals, can be converted to a Modbus network.
• All individual unit operating parameters can easily and quickly be configured by using the Modbus communication or by
using the front display menu.
• The easily readable 4511 display can be used to read the process signal, simulate the output signal, indicate sensor errors
and internal module errors.
Technical characteristics
• 4511 has full 4501 functionality for unit programming, process signal monitoring and diagnostics handling.
• Modbus RTU protocol is supported using a serial RS-485 communication wiring.
• Multidrop half-duplex connection via shielded RJ45 connector.
• High safe galvanic isolation of 2.5 kVAC between the serial wiring and the connected system 4000/9000 units.
• Modbus parameters such as address, baud rate, stop bit(s), and parity bit are configured from the 4511 display, which also
stores parameters.
Mounting / installation / programming
• Mounting in Zone 2 / Div 2.
• The 4511 can be moved from one device to another. The individual system 4000/9000 unit configuration of the first
transmitter can be saved and downloaded to subsequent transmitters.
• Programmed parameters can be protected by a user-defined password.
• When mounted on devices that are installed upside down, a menu item allows the display on the 4511 to be rotated 180
and the up/down buttons to switch function.

4511V101-UK 5
Mounting on a 4000 / 9000 device
4511 is a detachable display that can be mounted on all system 4000/9000 fronts for programming and signal monitoring.
4511 contains a four line LCD dot display
Line 1 can e.g. show the scaled process value.
Line 2 can e.g. show the selected engineering unit.
Line 3 can e.g. show the analog output or TAG no.
Line 4 shows status for communication and e.g. signal trending.
RJ45 Modbus Connector
Pin 5: RS485 A line
Pin 4: RS485 B line
Pin 8: RS485 GND and shield

6 4511V101-UK
Order
Electrical specifications
Environmental conditions:
Specifications range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -20°C to +60°C
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -20°C to +85°C
Humidity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond.)
Protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP20
Installation in pollution degree 2 / overvoltage category II.
Mechanical specifications:
Dimensions (HxWxD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.2 x 23.3 x 26.5 mm
Dimensions (HxWxD) w/ 4000/9000 unit . . . . . . . . . . . . . . . . . . . . . 109 x 23.5 x 131 mm
Weight approx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 g
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RJ45 - shielded
Common specifications:
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 0.15 W
Isolation voltage - test / working . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 kVAC / 250 VAC reinforced isolation
Extended EMC immunity:
NAMUR NE 21, A criterion, burst . . . . . . . . . . . . . . . . . . . . . . . . . No loss of communication
Signal / noise ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 60 dB
Update rate / response time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 50 Hz / < 20 ms
Signal type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RS-485 half duplex
Serial protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modbus RTU
Modbus mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RTU - slave
Devices on an RS485 line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Up to 32 (without a repeater)
Data rates, baud . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2400, 4800, 9600, 19200,
38400, 57600, 115200
Automatic baudrate detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes - can be configured ON or OFF
Parity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Even, Odd, None
Stop bit(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 or 2
Digital adressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1...247
Response delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...1000 ms
Observed authority requirements:
EMC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/30/EU
LVD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/35/EU
ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/34/EU
RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011/65/EU
Approvals:
DNV-GL, Marine. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TAA00000JD
c UL us, UL 61010-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E314307
EAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR-CU 020/2011
Ex:
ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEKRA 13ATEX0098 X
II 3 G Ex nA IIC T5 Gc
IECEx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEK 13.0026 X
Ex nA IIC T5 Gc
FM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0003049132-C
CL I DIV2 GP A- D T5
CL I Zn2 Groups IIC T5
CL I Zn2 AEx/Ex nA IIC T5
Type Description
4511
4590
4801
Communication enabler
Configmate interface
Modbus gateway

4000
/
9000
4000
/
9000
4000
/
9000
4511
4000
/
9000
4000
/
9000
4000
/
9000
45114511
IP54
4000
/
9000
4000
/
9000
4000
/
9000
4511 45114511
4801
4511 45114511
T
T
T
4511V101-UK 7
4511 installation examples
Modbus RTU
Zone 2 / Cl. 1, Div. 2, gr. A-DSafe Area
Modbus RTU
Gateway
Gateway
Modbus RTU
Ethernet
Modbus TCP/IP
PLC/DCS
HMI/PC
PLC/DCS
HMI/PC
Modbus RTU
PLC/DCS
HMI/PC
Access
Point

8 4511V101-UK
Modbus basics
Modbus is a “master-slave” system..., where the “master” communicates with one or multiple “slaves”.
The master typically is a PLC (Programmable Logic Controller), DCS (Distributed Control System), HMI (Human Machine
Interface), RTU (Remote Terminal Unit) or PC.
The three most common Modbus versions used are: MODBUS ASCII, MODBUS RTU and MODBUS/TCP.
In Modbus RTU, data is coded in binary, and requires only one communication byte per data byte. This is ideal for use over
multi-drop RS485 networks, at speeds up to 115,200 bps.
The most common speeds are 9,600 bps and 19,200 bps.
Modbus RTU is the most widely used industrial protocol and is supported by the 4511.
Modbus RTU:
To communicate with a slave device, the master sends a message containing:
Device Address - Function Code - Data - Error Check
The Device Address is a number from 0 to 247.
Messages sent to address 0 (broadcast messages) will be accepted by all slaves, but numbers 1-247 are addresses of specific
devices.
With the exception of broadcast messages, a slave device always responds to a Modbus message so the master knows the
message was received.
4511 Supported Modbus Function Codes:
The Function Code defines the command that the slave device is to execute, such as read data, accept data, report status.
Some function codes have subfunction codes.
The Data defines addresses in the device’s memory map for read functions, contains data values to be written into the
device’s memory, or contains other information needed to carry out the function requested.
The Error Check is a 16-bit numeric value representing the Cyclic Redundancy Check (CRC).
Maximum number of registers which can be read or written at once:
For a read command, the limit is 8 registers at a baud rate up to 38,400 bps, 16 registers @ 57,800 bps and 32 registers @
115,200 bps.
For a write command, the limit is 123 registers at baud rates up to 115,200 bps.
Command Function code
Read Holding Registers 03
Read Input Registers 04
Write Single Register 06
Diagnostics 08
Write Multiple Registers 16

4511V101-UK 9
4511 Modbus parameter settings
Automatic Baudrate Detection:
Can be configured YES or NO
Supported baudrates:
2400, 4800, 9600, 19.2k, 38.4k, 57.6k, 115.2k bps
Parity Mode:
Even, Odd or None parity
Stop Bits:
1or 2 stop bits
Response delay:
0...1000 ms (0 ms = default)
Modbus slave addressing range:
1 - 247 (247 = default address)
Modbus Parameter Storage:
Saved in non-volatile memory in the 4511 device
(Factory Default Values are marked in bold)
Modbus RTU segment line termination:
A 120 Ohm resistor should be installed on both ends of a RS485 Modbus RTU segment loop to prevent signal echoes from
corrupting data on the line.

10 4511V101-UK
4511 Modbus settings - routing diagram
4511 local submenu:
V0R9
"Monitor"
SCROLLING HELPTEXTS:
40.0
0000
(correct)
No
(No)
xxxx
[1]
Set correct password
%
---OK-->
--------->
PASSW.
---OK-->
ADV.SET
---OK-->
XXXX
[2]
Enter advanced setup menu?
10.4mA
[1]
[2]
(Yes)
[x]
[3]
Enter Language setup
^ o
V
Enter Password setup
v ^
v ^
|
v ^
Enter Simulation mode
|
9999
YES
|
Perform Process calibration
|
0000
NO
|
Enter Display setup
|
|
Perform Memory operations
|
|
MEM
(MEM)
Enter Modbus setup
|
|---->
SETUP
-OK-|-->
Enter Rotation setup
|
[3]
|
[4]
Enable modbus communication
|
(DISP)
Disable Modbus communication
|
v ^
|-->
See automatic baudrate detection status
|
MEM
|
[5]
Reset Modbus to default?
|
DISP
(CAL)
[6]
Select Modbus slave address
|
CAL
|-->
[7]
Select parity for Modbus
|
SIM
|
[8]
Select number of stop bits
|
PASS
(SIM)
[9]
Select response delay in ms
|
LANG
|-->
[10]
Enable automatic baudrate detection
|
MODB
|
[11]
Modbus baudrate not detected
|
ORIEN
(PASS)
Searching for Modbus baudrate
|
|-->
Modbus baudrate detected
|
|
[12]
Select baudrate in bps
|
(LANG)
[13]
Rotate device upside down?
| |-->
|
|
| (MODB) YES (OFF)
|--> ------- ------- ------- ------- ------- ------- -------
|--> MOD.EN ---OK--> ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ---------> "Monitor"
|
[4]
(ON) |
^
^
|
|
NO
(Yes)
|
|
| v ^ |----> MOD.RST ---OK--> ----| |
! ! ! Returns to "Monitor" from any menu, after 1 min with no keypress.
|
ON
|
[5]
(No) |
|
! ! ! Returns to "Monitor" upon succesful Modbus write command.
|
OFF
|
|
247
EVEN
1
20
NO
(Yes)
|
|STATUS
*1) | v ^ |----> ADR PARITY STP.BIT RSP.DLY AUTO.B ---OK--> ------- -------> ----|
||YES [6] [7] [8] [9] [10] (No) | ^
|
|
NO
|
|
| | v ^ v ^ v ^ v ^ v ^ | 19.2k |
|| 247 EVEN 1 1000 YES
|---->
BAUD OK -|
|| | ODD 2 | NO [12]
|
|
1
NONE
0
| (STATUS) v ^
|
|
*1)
2400
|| SEAR 4800
*1)
| |----> ------- ------- ------- ---------> STATUS ---OK--> "Monitor" 9600
Only if automatic baudrate detection is enabled
|
[11]
19.2k
(ORIEN)
NO
38.4k
|--> ROT.DEV ---OK--> "Monitor" ERR 57.6k
[13]
SEAR 115.2k
2400
v ^
4800
YES
9600
NO
19.2k
38.4k
57.6k
115.2k
The gray shaded menus/texts are only shown for guidance, and are not part of
the 4511 specific submenu.
The Modbus submenu is located somewhere in the menu structure of any host
device supporting 4511. The actual place is defined for each particular device.
PR electronics A/S 4511 Local Menu.xlsx FSS 13-10-2014

4511V101-UK 11
4511 local submenu:
V0R9
"Monitor"
SCROLLING HELPTEXTS:
40.0
0000
(correct)
No
(No)
xxxx
[1]
Set correct password
%
---OK-->
--------->
PASSW.
---OK-->
ADV.SET
---OK-->
XXXX
[2]
Enter advanced setup menu?
10.4mA
[1]
[2]
(Yes)
[x]
[3]
Enter Language setup
^ o
V
Enter Password setup
v ^
v ^
|
v ^
Enter Simulation mode
|
9999
YES
|
Perform Process calibration
|
0000
NO
|
Enter Display setup
|
|
Perform Memory operations
|
|
MEM
(MEM)
Enter Modbus setup
|
|---->
SETUP
-OK-|-->
Enter Rotation setup
|
[3]
|
[4]
Enable modbus communication
|
(DISP)
Disable Modbus communication
|
v ^
|-->
See automatic baudrate detection status
|
MEM
|
[5]
Reset Modbus to default?
|
DISP
(CAL)
[6]
Select Modbus slave address
|
CAL
|-->
[7]
Select parity for Modbus
|
SIM
|
[8]
Select number of stop bits
|
PASS
(SIM)
[9]
Select response delay in ms
|
LANG
|-->
[10]
Enable automatic baudrate detection
|
MODB
|
[11]
Modbus baudrate not detected
|
ORIEN
(PASS)
Searching for Modbus baudrate
|
|-->
Modbus baudrate detected
|
|
[12]
Select baudrate in bps
|
(LANG)
[13]
Rotate device upside down?
| |-->
|
|
| (MODB) YES (OFF)
|--> ------- ------- ------- ------- ------- ------- ------- |--> MOD.EN ---OK--> ------- ------- ------- --
----- ------- ------- ------- ------- ------- ------- --------->
"Monitor"
|
[4]
(ON) |
^
^
|
|
NO
(Yes)
|
|
| v ^ |----> MOD.RST ---OK--> ----|
|
! ! ! Returns to "Monitor" from any menu, after 1 min with no keypress.
|
ON
|
[5]
(No) |
|
! ! ! Returns to "Monitor" upon succesful Modbus write command.
|
OFF
|
|
247
EVEN
1
20
NO
(Yes)
|
|STATUS *1) | v ^ |----> ADR PARITY STP.BIT RSP.DLY
AUTO.B ---OK--> ------- -------> ----|
||
YES [6] [7] [8] [9] [10] (No) | ^
|
|
NO
|
|
| | v ^ v ^ v ^ v ^ v ^ |
19.2k |
||
247 EVEN 1 1000 YES
|---->
BAUD OK -|
||
| ODD 2 | NO [12]
|
|
1
NONE
0
| (STATUS)
v ^
|
|
*1)
2400
||
SEAR 4800
*1) | |----> ------- ------- ------- --------->
STATUS ---OK--> "Monitor" 9600
Only if automatic baudrate detection is enabled
|
[11]
19.2k
(ORIEN)
NO
38.4k
|--> ROT.DEV ---OK-->
"Monitor" ERR 57.6k
[13]
SEAR 115.2k
2400
v ^
4800
YES
9600
NO
19.2k
38.4k
57.6k
115.2k
The gray shaded menus/texts are only shown for guidance, and are not part of
the 4511 specific submenu.
The Modbus submenu is located somewhere in the menu structure of any host
device supporting 4511. The actual place is defined for each particular device.
PR electronics A/S 4511 Local Menu.xlsx FSS 13-10-2014
Default settings:
Baud rate: 19.2 kbps
Parity mode: Even
Stop bit: 1
Address: 247
Reponse delay: 0 ms

We are near you,
all over the world
All our devices are backed by expert service and a 5-year
warranty. With each product you purchase, you receive
personal technical support and guidance, day-to-day delivery,
repair without charge within the warranty period and easily
accessible documentation.
We are headquartered in Denmark, and have offices and
authorized partners the world over. We are a local business
with a global reach. This means that we are always nearby
and know your local markets well.
We are committed to your satisfaction and provide
PERFORMANCE MADE SMARTER all around the world.
For more information on our warranty program, or to meet
with a sales representative in your region, visit
prelectronics.com.
Our trusted red boxes are supported wherever you are

PR electronics is the leading technology company specialized in making industrial process
control safer, more reliable and more efficient. Since 1974, we have been dedicated to
perfecting our core competence of innovating high precision technology with low power
consumption. This dedication continues to set new standards for products communicating,
monitoring and connecting our customers’ process measurement points to their process
control systems.
Our innovative, patented technologies are derived from our extensive R&D facilities and
from having a great understanding of our customers’ needs and processes. We are guided
by principles of simplicity, focus, courage and excellence, enabling some of the world’s
greatest companies to achieve PERFORMANCE MADE SMARTER.
Benefit today from
PERFORMANCE MADE SMARTER
www.prelectronics.com
Other manuals for 4511
2
Table of contents
Popular Conference System manuals by other brands

Clear One
Clear One XAP 800 datasheet

Smart Technologies
Smart Technologies SMART Room System manual

Clear One
Clear One UNITE 60 quick start guide

Paradox
Paradox GPRS14 installation instructions

Telegärtner
Telegärtner FSP 100 user manual

Lucent Technologies
Lucent Technologies MERLIN LEGEND Release 6.1 Maintenance and troubleshooting