23 24
Technician Setup Menu Technician Setup Menu
Tech Setup Steps Adjustment Options Default
LCD Will Show Tech Setup Steps Adjustment Options Default
LCD Will Show
This feature will congure the
fan to run a selected number of
cycles per hour. Note:This mode
can be enabled or disabled at
anytime during normal operation
by selecting IAQ mode with the
fan key. Turning this feature on
shows IAQ option in fan key.
Notes:
This programmable/selectable mode
will operate the fan 1-4 cycles per
hour, 1-45 minutes per cycle. Once
programmed in tech setup, to enable
this mode select“IAQ”with the fan
key. Disable this mode by selecting
“ON”or“AUTO”with the fan key.
IAQ Mode
Cycle
Select OFF, 1, 2, 3 or 4 with the
or buttons. This sets
the number of cycles per hour
that the IAQ fan mode will
operate.
OFF
IAQ MODE CYCL
OF
This allows you to select the
minimum number of minutes
that the fan will run per IAQ
mode cycle. The thermostat will
keep track of fan runtime from
normal heat and cool operation. If
additional fan runtime is needed,
the thermostat will run the fan to
satisfy the IAQ mode minutes.
Notes: This programmable/selectable
mode will operate the fan 1-4 cycles
per hour, 1-45 minutes per cycle. Once
programmed in tech setup, to enable
this mode select“IAQ”with the fan
key. Disable this mode by selecting
“ON”or“AUTO”with the fan key.
IAQ Minutes
Per Cycle
Select 1, 5, 10, 15, 20, 30 or
45 minutes.
When IAQ fan mode is
enabled, it will ensure the
fan runs at least the selected
number of minutes per IAQ
Mode Cycle.
This step will not appear if
previous step is set to“OFF”.
IAQ MODE MIN
11
27 28
Technician Setup Menu Technician Setup Menu
Tech Setup Steps Adjustment Options Default
LCD Will Show Tech Setup Steps Adjustment Options Default
LCD Will Show
Balance point run time will allow
the W2 auxiliary terminal to ener-
gize even if outdoor temperature
is above selected balance point
temperature. If enabled, auxiliary
will energize for the current cycle
after the balance point run time
has expired.
Note: Only shows if Balance Point is
set to an outdoor temperature.
Balance
Point Run
Time
(Only displayed
if remote sensor
setting is set
to 2)
This feature will bring in outside
air for rst stage cooling opera-
tions, if the outdoor temperature
is 5 (or more) degrees lower than
the setpoint temperature. This
setting can only be enabled if the
thermostat is in cooling mode.
Free Cooling
(Only displayed
if remote sensor
setting is
set to 2)
O, 15, 30, 45, 60, 75, 90
BP RUN TIME
Use the and buttons
to select ON/OFF.
OFF
This setting provides the option to
select a terminal for Free Cooling
functions. The selected terminal
cannot be used for reversing valve
operations when the heat pump
setting is turned on.
Free Cooling
Terminal
(Fresh air mode and
free cooling can
be used together.
Free cooling cannot
be used with PTAC
mode, three stages
of heat, or
economizer mode)
Use the and buttons
to select O/B.
O
FREE COOLTRM
OF
O
This setting allows you to set
a maximum oor temperature
limit for heat. Heat will be locked
out when the oor temperature
is above this value. Note: Only
shows when REOP is set to 3.
Floor High
Limit
(Only displayed
if remote sensor
setting is set
to 3)
This setting allows you to set
a minimum oor temperature
limit for heat. Heat will turn on
automatically when the oor
temperature is below this value.
Note: Only shows when REOP is
set to 3.
Floor Low
Limit
(Only displayed
if remote sensor
setting is set to 3)
Use the or buttons to
select the High Limit for the
oor sensor.35 - 120
HIGH LIMIT
Use the or keys to
select the Low Limit for the
oor sensor.
35 - 120 50
86 86
50
LOW LIMIT
OF OFF
FREE COOLING
The temperature of the oor
sensor will be displayed.
Note: Only shows when REOP is
set to 3.
Use and buttons to adjust.
Floor
Temperature
(Only displayed
if remote sensor
setting is set to 3)
N/A
N/A
76
FLOOR TEMP
This feature allows you to put
your phone number in the
display. You can choose ON or
OFF.
Notes: If contractor call number is
selected ON, the phone number en-
tered will show in the display if there
has been a continuous call for heating
or cooling for 24 hours or if the light
button is held down for 3 seconds. To
remove the phone number from the
display, hold the light button down
for 3 seconds.
Contractor
Call Number
If selected ON, you will see
the input screen after
pressing NEXT STEP. Use the
or button to select
the desired number and
the FAN or SYSTEM key to
move from one character to
another. See note below for
operation. OFF
OF
PHONE NUMBER
A Note about IAQ Mode
This programmable/selectable mode will operate the fan 1-4 cycles
per hour, 1-45 minutes per cycle. Once programmed in tech setup, to
enable this mode select “IAQ” with the fan key. Disable this mode by
selecting “ON” or “AUTO” with the fan key.
Contractor Call Number Note
If contractor call number is selected ON, the phone number en-
tered will show in the display if there has been a continuous call for
heating or cooling for 24 hours or if the light button is held down for
3 seconds. To remove the phone number from the display, hold the
light button down for 3 seconds.
Balance point with electric
auxiliary will optimize heat
pump usage. When the outdoor
temperature is above the AUX CUT
OUT selection, the thermostat
to only allow theY terminal(s)
to energize and lockout theW2
terminal. When the outdoor
temperature falls below the
AUX CUT OUT selection and sits
above the AUX CUT IN selection,
the thermostat to allow theY
terminal(s) and theW2 terminal
to energize. When the outdoor
temperature below the AUX CUT
IN selection, the thermostat will
only energize theW2 terminal
and lockout theY terminal(s).
Balance Point
Electric AUX
Cut In
(Only displayed if
remote
sensor setting is
set to 2 and Duel
Fuel Aux if O)
Use the and buttons
to select 10, 15, 20, 25, 30,
35, 40, 45, 50 degrees.
40
40
AUX CUT IN
When this feature is enabled, the
economizer terminal is energized
in the WAKE, RETURN, SLEEP or
OCCUPIED time periods. This
feature will remain disabled if
programming is OFF (0D). This
feature will use one of the
congurable terminals (O/B) to
connect to the economizer.
Economizer
Mode
(This feature
cannot be used
with non-
programmable
PTAC mode, three
stages of cool,
fresh air, of free
cooling mode)
OFF
ECONOMIZER
OF
This setting provides the option to
select a terminal for Economizer
functions. The selected terminal
cannot be used for reversing valve
operations when the heat pump
setting is turned on.
Economizer
Terminal
Designation
(Only displayed
if economizer is
turned on)
O
ECON TERMINAL
O
B
Use the and buttons
to select ON or OF.
Use the and buttons
to select O/B.
This feature allows fresh air into
a unit for a selectable amount
of time.When Fresh Air Mode is
enabled, the fan and the fresh air
damper terminal will energize
simultaneously.
Fresh Air
Mode
(This setting cannot
be used with PTAC,
three stages of
cool, or economizer
turned on)
Use the and buttons to
select OFF, OC ON or ON.
OFF:Thermostat does not
enable Fresh Air Mode.
OC ON: Fresh Air Mode is
enabled during the OCCUPIED,
WAKE, RETURN, and SLEEP
time periods (It will not bring
in fresh air during UNOCCUPIED
and LEAVE time periods).
ON:Thermostat will enable
Fresh Air Mode for every time
periods.
OFF
FRESH AIR
OF