Procentec ProfiHub F1 User manual

ProfiHub F1
User Manual

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 2/26
Important information
Purpose of the Manual
This user manual provides information how to work with ProfiHub F1.
Recycling and Disposal
The parts of the ProfiHub F1 can be recycled. For further information about environment-friendly recycling and
the procedure for disposing of your old equipment, please contact:
Document Updates
You can obtain constantly updated information on PROCENTEC products on the Internet at
www.procentec.com
You can also contact PROCENTEC Customer Support:
•by phone at +31-(0)174-671800
•by fax at +31-(0)174-671801
•by email at support@procentec.com
PROCENTEC
Klopperman 16
2292 JD WATERINGEN
The Netherlands
T: +31-(0)174-671800
F: +31-(0)174-671801
E: info@procentec.com

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 3/26
Safety Guidelines
This manual contains notices which you should observe to ensure your own personal safety, as well as to
protect the product and connected equipment. These notices are highlighted in the manual by a warning sign
and are marked as followed according to the level of danger:
Draws your attention to important information on handling the product, a particular part of the
documentation or the correct functioning of the product.
Warning
This device and its components may only be used for the applications described in this manual and only in
connection with devices or components that comply with PROFIBUS and RS 485 interface.
This product can only function correctly and safely if it is transported, stored, set up, installed, operated and
maintained as recommended. ProfiHub F1 is a CE class A product. In a domestic environment it may cause
radio interference in which case the user may be required to take adequate measures.
Warranty
Warranty is void if you open ProfiHub F1.
Qualified Technicians
Only qualified technicians should be allowed to install and work with this equipment. Qualified technicians are
defined as persons who are authorized to commission, to ground, to tag circuits and systems in accordance
with established safety practices and standards. It is recommended that the technicians carry a Certified
PROFIBUS Installer or Certified PROFIBUS Engineer certificate.
Disclaimer of Liability
We have checked the contents of this manual as much as possible. Since deviations cannot be precluded
entirely, we cannot guarantee full agreement. However, the content in this manual is reviewed regularly and
necessary corrections will be included in subsequent editions. Suggestions for improvements are welcome.
Copyright © 2011-2018 PROCENTEC
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior
written permission of the publisher.
ProfiHub F1 is a registered trademark of PROCENTEC. Other products or company names are or may be
registered trademarks and are the property of their respective companies.

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 4/26
Content
Important information........................................................................................... 2
1. System description ........................................................................................ 5
2. Hardware installation .................................................................................... 6
3. Project: planning a ring structure.................................................................. 8
4. Dimensions .................................................................................................... 9
5. Connectors and operation modes............................................................... 10
6. System Description ...................................................................................... 11
7. Mounting ..................................................................................................... 12
8. Type selection and technical data ............................................................... 13
9. Other PROCENTEC products........................................................................ 15
10. Sales offices and distributors....................................................................... 17
11. About PROCENTEC....................................................................................... 22
12. Notes ........................................................................................................... 23

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 5/26
1. System description
The interface modules ProfiHub F1 couple PROFIBUS-DP or PROFIBUS-FMS two-wire-segments (RS-485) via op-
tical fibres. The module can work as a ring module or work in a Line- or Point-to-point-structure. This can be set
by a DIP-switch.
They are equipped with two supply voltage inputs to provide redundant power supply. The integrated error
relay can be used to indicate malfunctions.
The PROFIBUS-data rates 9,6KBit/s, 19,2KBit/s, 45,45KBit/s, 93,75KBit/s, 187,5KBit/s, 500KBit/s, 1,5MBit/s,
3MBit/s, 6MBit/s and 12MBit/s are automatically detected by the module.

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 6/26
2. Hardware installation
Power off the devices, which will be connected by using the fiber optic system.
Snap the system onto the DIN EN rail and check the correct holding!
Use only the correct optical connectors for the fiber optic system. Using incorrect connectors can
cause damage to the fiber optic system. Take care that connectors with a latch can only be mounted
in a defined position.
Don't stare into the optical cable or the transmitter of the fiber optic system. Visible and non-visible
light (depending on its wavelength) of the optical transmitter can cause eye-damages!
Connect the fiber optic system by using the correct fiber optic cable. Take care that you always have to connect
an optical transmitter and an optical receiver.
Use the plugs to save the unused optical receiver and transmitter against impurity.
Don't bend the fiber optic cable! Please refer to the specifications of the cable manufacturer.
Otherwise the fiber optic cable can be damaged or the communication will be disturbed.
Power on the devices. Please use a power supply of 12-30VDC, connected to the terminals marked with VDC1,
VDC 2 and GND. Note, that VDC 1 and VDC 2 are redundant power inputs with reverse voltage protection.
Function of the DIP-Switch :
SW1 to SW3 : PROFIBUS termination between “A” and “B” line
SW4 : Choose Ring or Line / Point-to-Point structure
SW5 : Disables Fiber Port CH2
SW6 : Disables Fiber Port CH1
Function of the Status-LEDs:
VDC : Power Supply at VDC1 or VDC2
FAIL : Failure group signal and failure relay opened
Status : No data rate detected yet or bus-error (to long data-
frame or to long duration of a zero). Changed PROFIBUS-wires can be detected by the status-led when the
termination of the ProfiHub F1 is turned off (DIP-switches 1 to 3).
Rx : Data being received. A received frame is only shown at the Rx-led of the channel where it arrives first. Thus
it can happen that although working in a ring, only one of the Rx-leds lights or both Rx-leds of the ProfiHub F1
are blinking.
Function of the Status-LEDs Fiberview:
Fail : Received optical signal failed
Limit : System reserve reached
Link / Act : Transmitting or receiving data
Failure Relay: Terminals K1 to K3 are connected to a potential free relay. If the optical connection works
without failures the relay gets active and closes K1 to K2 and opens K2 to K3. If the optical connection is
disconnected or power supply at VDC1 or VDC2 fails, the relay will get inactive and K1 to K2 opens and K2 to K3
closes
Function of K1 – K2: Potential free failure relay contact NC.

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 7/26
Function of K2 –K3: Potential free failure relay contact NO.
Systems with 2 FX-Ports always have transceiver CH1 as the upper one.
Start-up: After having applied the supply voltage the module start the data rate detection. When the data rate
is detected, the transmission of the received data is started.
Thus, at slow data rates and in ring structures with many converters closing the ring at start-up can take some
seconds. As well, after having changed the data rate of the system, the ring may take some seconds before
adjusting the new data rate.
The fail-led of the PROFIBUS-connector lights until the first data rate is detected. After the data rate detection
it only lights to show bus-errors.
To meet the required values a PROFIBUS-cable has to be used and modules and cable-shield have to
be grounded properly.
POF-connection:
To connect the POF cable into the Optolock, the end of the cable is cut cleanly. Use a POF-Cutter to make a
straight cut in an angle of 90° at the chose position of the cable. After that the end of the two strands are
separated. Then the strands are inserted into the two holes in the termination housing, which is then pressed
close to hold the POF in place.
Pay attention on the bending radius of the optical cables while installing them and check the temperature
range of the used plugs.

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 8/26
3. Project: planning a ring structure
When planning a ring structure the following things have to be considered:
•Set DIP-switch 4 ON, 5 and 6 to position OFF
•The minimum response time of the slaves (min TSDR) must be set to 11 bit times or higher.
•The slot time or the PROFIBUS (TSL) must be adjusted to a value high enough to guarantee that the answers
of all slaves are at the master within the slot time, even when an optical connection is broken. The
minimum slot time depends on the data rate, the length of the optical fibre and on the number of ProfiHub
F1 in the ring. It can be calculated using the formula below
TSL≥max_TSDR + LLWL .tLWL + nDL .tDL.
max_TSDR: maximum response time of the slaves.
LLWL: Length of the whole optical fibre in the ring. The two longest branch lines – if there are any –
should be added to the length of the fibre optical in the ring.
LWL: Constant considering the bit times per km fibre optical cable (see table)
nDL: Number of ProfiHub F1 in the ring.
tDL: Constant considering the delay time (in bit times) of one ProfiHub F1 (see table below).
Data rate [KBit/s] tLWL [Bit times/km] tDL [Bit times]
12.000
240
80
6.000
120
40
3.000
60
20
1.500
30
10
500
10
4
187,5
3,33
3
93,75
1,66
3
45,45
1,66
3
19,2
0,33
2
9,6
0,17
2

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 9/26
4. Dimensions
CH1
CH2

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 10/26
5. Connectors and operation modes
6: Channel 1 ON: Fiber port CH1 disabled
5: Channel 2 ON: Fiber port CH2 disabled
4: Mode ON: Ring OFF: Line
1-3: termination ON or OFF

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 11/26
6. System Description
A ring topology must be connected from CH1 to CH1 and CH2 to CH2. Only with an uneven number
of FO modules, the cables may be connected from CH1 to CH2 and CH2 to CH1 (only once per ring).

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 12/26
7. Mounting
As standard, the system has a clip for 35mm DIN rails according to DIN EN 60175.
For mounting the system please engage it onto the rail at the bottom side (see left picture), press it against the
spring force to the top (1) and then towards the mounting plate (2). The system latches as shown in the picture
at the right. Please refer to the above mentioned steps in reverse order to demount the switch.
As an option, a wall mount kit is also available. If the system should be fixed onto the wall, the clip for DIN rail
mount has to be unscrewed first.

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 13/26
8. Type selection and technical data
Type
13-MM-ST
Order no.
123-022MM01-ST
Fiber connector
ST
Fiber Multi mode
62,5 (50) /125µm
Optical budget
13dB
Transmission path 5 km
(2 dB/km)
Wavelength
1310 nm
Transmission rate max.
12MBit/s
Transmission
Half duplex
Operation Mode
RS485
↔
Fiber Optic LWL : < 3 TBit / Tx
↔
Rx : 11 TBit
Load
switchable termination: open or characteristic impedance (Rw + Rpd + Rpu)
Cable Length 1.200m (9,6 – 187,5KBit/s), 400m (500KBit/s), 200m (1.5MBit/s) 100m (3MBit/s –
12MBit/s)
Cable Length according to PROFIBUS User Organization
Connector
9-pin female Sub-D and 6-pin connection terminal
Control - LED’s Power supply (green) / Failure (red) / Data receive (green) / Status (red) / Fiber view (red,
yellow, green)
Operating voltage
12-30 VDC, other voltages on request
Current consumption 200 mA
Potential separation 500 VDC (24 VDC →RS-485)

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 14/26
Failure
relay contact
25VDC (1A) / 60VDC (0,3A)
Operating temperature -40°C … +70°C (Multi mode and Single mode with ST or SC)
-20°C … +55°C (all others)
Storage temperature -40 … +85° C
EMC
EN61000-6-2 (2001) / EN55022 Kl. B (1998) +A1 + A2
Weight 500 g
Dimensions
H x D x W
H: 115mm W: 61mm D: 113mm
Case
Stainless steel, powder-coated

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 15/26
9. Other PROCENTEC products
PROFINET Cable Tester
•Suitable for 4- and 8-wire PROFINET and regular Ethernet cables
•Suitable for straight and 90°, metal or plastic PROFINET plugs
•Tests cable shielding
•Detects short circuits, wire breaks, swaps, miswiring and split pairs
•Large LCD clearly indicates the test results
•150 hours on one 9 V battery
•Operating temperature: 0 to 50 °C
•Just 1-key-press to start continuous testing
•It can also test telephone and coax cable
www.PROFINETcabletester.com
ProfiHub B5+R
•6 galvanicly isolated channels
•Configurable grounding system
•Redundant power supply
•Bus redundancy option
•Star, tree and bus structured networks
•Alarm contact
•Monitoring port per channel
•IP20
•Certifications: UL Listed, DNV, FCC, CE
www.procentec.com/profihub

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 16/26
ProfiHub A5
•5 Isolated channels
•Transparent
•Increased signal strength
•31 devices per channel
•12 Mbps
•1200 m spur line length
•No address required
•Integrated switchable termination
•IP 65 classification
www.procentec.com/profihub
Compact PROFIBUS Repeater B1
•Single channel PROFIBUS repeater
•Transparent
•Increased signal strength
•12 Mbps
•Auto baudrate detection
•Redundant power supply
•Digital glitch filtering
•No limit in cascading
•Integrated switchable termination
•Diagnostic LEDs
•DB9 connector for measurements
•IP 20 with DIN-rail mounting
www.procentec.com/profihub

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 17/26
10. Sales offices and distributors
HEADQUARTERS
PROCENTEC T: +31 (0)174 671 800
Klopperman 16 F: +31 (0)174 671 801
Netherlands W: www.procentec.com
ARGENTINA
eFALCOM T: +54 237 46 31 151
Alcorta 2411 F: +54 237 46 31 150
Buenos Aires W: www.efalcom.com
Argentina
AUSTRIA
RELISTE T: +43 2236 315 25-25
Enzersdorfer Straße 8-10 F: +43 2236 315 25-60
A-2345 Brunn am Gebirge E: office@reliste.at
Austria W: www.relise.at
AUSTRALIA
IS Systems Pty Limited T: +61 2 4964 8548
14 Laverick Ave., F: +61 2 4964 8877
Tomago E: fritz.woller@issystems.com.au
NSW, Australia, 2322 W: www.issystems.com.au
Pentair Flow Control Pacific T: +61 2 4448 0466
1 Percival Road F: +61 2 4423 3232
Smithfield E: sharee.hazell@pentair.com.au
NSW, Australia, 2164 W: www.PROFIBUScentre.com.au
BELGIUM and LUXEMBOURG
Bintz Technics N.V. T: +32 2 720 49 16
Brixtonlaan 23 F: +32 2 720 37 50
B-1930 Zaventem E: [email protected]
Belgium W: www.bintz.be
BRAZIL
Westcon Instrument. Indl Ltda T: +55 11 5561-7488
Rual Alvaro Rodrigues, 257 F: +55 11 5093-2592
Brazil - CEP 04582-000 W: www.wii.com.br
CANADA
Streamline Process Management Inc. T: +1 403 225 1986
#3, 4351 – 104 Ave SE F: +1 587 585 2828
Calgary, Alberta T2C 5C6 E: admin@streamlinepm.com
Canada W: www.streamlinepm.com
CHILE
RP Ingenieria Limitada T: +56 41 246 93 50
Tucapel 92 oficina 52 F: +56 41 252 25 92
Concepción E: rodrigopinto@rpingenieria.cl
Chile W: www.rpingenieria.cl
CHINA
PROCENTEC Beijing T: +86 (10)847 669 11 / +86 (10) 847 873 11
Room E-1115 WangJingYuan YouLeHui F: +86 (10)847 667 22
ChaoYang E: info@procentec.net
Beijing W: www.procentec.net
China
CZECH REPUBLIC
FOXON s.r.o. T: +420 484 845 555
Polní 367 F: +420 484 845 556
Czech Republic W: www.foxon.cz

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 18/26
DENMARK
ProSaiCon T: +45 70 20 52 01
Jernbanegade 23B F: +45 70 20 52 02
Denmark W: www.prosaicon.dk
EGYPT
Mas Trading T: +2 02 2524 2842
37, 105 Street F: +2 02 2524 2843
Al-Etihad Square E: aya.elshafei@masautomation.com
Egypt W: www.masautomation.com
ESTONIA
Saksa Automaatika OU T: +372 605 2526
Peterburi Tee 49 F: +372 605 2524
Tailinn E: info@saksa-automaatika.ee
EE-11415 Estonia W: www.saksa-automaatika.ee
FINLAND
Hantekno Oy T: +358 40 8222 014
04360 Tuusula W: www.hantekno.fi
Finland
FRANCE
AGILiCOM T: +33 247 76 10 20
Bâtiment B F: +33 247 37 95 54
1, rue de la Briaudière E: jy.bois@agilicom.fr
Z.A. La Châtaigneraie W: www.agilicom.fr
37510 BALLAN-MIRE
France
GERMANY
PROCENTEC GmbH T: +49 721 831 663-0
Benzstrasse 15 F: +49 721 831 663-29
D-76185 Karlsruhe E: [email protected]e
Germany W: www.procentec.de
INDIA
UL Engineering Services & Software Pvt Ltd T: +91 202 696 0050
Nirman Classic, F: +91 202 696 2079
Katraj-Kondhwa Road, E: dileep.miskin@ulepl.com
Katraj, Pune-411046 W: www.ulepl.com
India
Automation Combine T: +98 452 84 550 / +98 452 030 47
B.R. House 4th Floor, F: +93 421 375 34 / +93 425 002 90
Hennur Main Road E: info@automationcombine.com
Bangalore 560043 W: www.automationcombine.in
India
IRELAND
PROFIBUS Ireland T: +353 61 202 107 or +353 61 240 240
Automation Research Centre F: +353 61 202 582
University of Limerick E: info@PROFIBUS.ie
National Technology Park, Plassey W: www.PROFIBUS.ie
Limerick
Ireland
ISRAEL
Instrumetrics Industrial Control T: +972 9 835 70 90
8 Hamlacha St. F: +972 9 835 06 19
New Industrial Zone E: info@instrumetrics-ic.co.il
Netanya, 42170 W: www.inst-ic.co.il
Israel
ITALY
PROCENTEC Italy T: +39 030 200 8610
Via Branze n. 43/45 F: +39 030 238 0059
25123 Brescia E: www.procentec.it
Italy W: www.procentec.it

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 19/26
JAPAN
TJ Group T: +81 3 6450 3739
C/O Japanese PROFIBUS Organisation F: +81 3 6450 3739
West World Building 4F E: info@PROFIBUS.jp
3-1-6 Higashi-Gotanda,
Shinagawa-ku,
Tokyo, 141-0022
Japan
KOREA
Hi-PRO Tech. Co., Ltd. T: +82 82 31 216 2640
#2802, U-Tower, 1029 F: +82 82 31 216 2644
Youngduk-dong, Giheung-gu E: chays@hiprotech.co.kr
Yongin-Si, Kyunggi-do, W: www.PROFIBUS.co.kr
446-908 Korea
LEBANON
Industrial Technologies S.A.L. (ITEC) T: +961 1 491161
Point Center, Boulevard Fouad Chehab F: +961 1 491162
Sin El Fil E: sales@iteclb.com
Beirut W: www.iteclb.com
Lebanon
MEXICO
Grid Connect Inc. T: +1 530 219 2565 (Spanish)
E: tomf@gridconnect.com
W: www.gridconnect.com
NETHERLANDS
PROCENTEC B.V. T: +31 (0)174 671 800
Klopperman 16 F: +31 (0)174 671 801
Netherlands W: www.procentec.com
NORWAY
Nortelco Automation AS T: +47 22 57 61 00
Johan Scharffenbergs vei 95 E: post@nortelcoautomation.no
N-0694 Oslo I: www.nortelcoautomation.no
Norway
PERU
ControlWare T: +51 163 737 35
Jr. Los Silicios 5409 F: +51 152 804 54
Los Olivos - L39 E: info@controlware.com.pe
Peru W: www.controlware.com.pe
POLAND
INTEX Sp. z o.o. T: +48 32 230 75 16
ul. Portowa 4 F: +48 32 230 75 17
44-102 Gliwice E: [email protected].pl
Poland W: www.intex.com.pl
PORTUGAL
IndustrialSys T: +351 96 716 16 05
Mangualde, 3530-144 W: www.industrialsys.pt
Portugal
ROMANIA
S.C. SVT Electronics S.R.L. T: + 40 744 383 666
Brǎila 7 F: +40 365 809 305
540331 Tg-Mure E: sajgo.tibor@svt.ro
Romania W: www.svt.ro
SAUDI ARABIA
ASM Process Automation T: +966 2 691 27 41
Al-Zahra Dist. – Attas st. F: +966 2 682 89 43
Villa no.25 W: www.asmestablishment.com
Jeddah-21553
Saudi Arabia

ProfiHub F1 User Manual v1.0.1 | September 2018 | ©PROCENTEC 20/26
SINGAPORE / SOUTH EAST ASIA
Allegro Electronics T: +65 628 780 63
236 Serangoon Avenue 3 07-98 E: sales@allegro.com.sg
Singapore 550236 W: www.allegro.com.sg
SLOVAKIA
ControlSystem s.r.o. T: +421 486 115 900
Stúrova 4 F: +421 486 111 891
Slovakia W: www.controlsystem.sk
SOUTH AFRICA
IDX ONLINE CC T: +27 (11) 548 9960
1 Weaver Street F: +27 (11) 465 8890
Fourways E: [email protected]om
Johannesburg W: www.idxonline.com
South Africa - 2191
SPAIN
LOGITEK, S.A T: +34 93 588 67 67
Ctra. de Sant Cugat, 63 Esc. B Planta 1ª E: xavier.cardena@logitek.es
Rubí (BARCELONA), 08191 W: www.logitek.es
Spain
SWEDEN
P&L Nordic AB T: +46 451 74 44 00
S-281 23 Hässleholm W: www.pol.se/PROFIBUS
Sweden
SWITZERLAND
Berner Fachhochschule T: +41 (0) 34 426 68 32
PROFIBUS Kompetenzzentrum F: +41 (0) 34 426 68 13
Jlcoweg 1 E: max.felser@bfh.ch
CH-3400 Burgdorf W: www.profitrace.ch
Switzerland
TAIWAN
Full Data Technology T: +886 2 8751 99 41/90 97
6F., No.200, Gangqian Rd. F: +886 2 8751 95 33
114, Taiwan W: www.fulldata.com.tw
TURKEY
Emikon Otomasyon T: +90 216 420 83 47
DES Sanayi sitesi 103 sokak F: +90 216 420 83 48
B-7 blok No:16 Yukari Dudullu / Umraniye E: tolgaturunz@emikonotomasyon.com
Istanbul 34776 W: www.emikonotomasyon.com
Turkey
UNITED ARAB EMIRATES
Synergy Controls T: +971 4 326 26 92
907, IT Plaza Silicon Oasis : F: +971 4 326 26 93
DubaiI E: sales@synergycontrols.ae
United Arab Emirates
UNITED KINGDOM and N. Ireland
Verwer Training & Consultancy T: +44 (0)1625 871 199
5 Barclay Road E: andy@verwertraining.com
Poynton, Stockport I: www.verwertraining.com
Cheshire SK12 1YY
United Kingdom
Hi-Port Controls T: +44 (0)8452 902 030
The Hub 2 Martin Close F: +44 (0)2392 552 880
Lee-on-Solent E: sales@hiport.co.uk
Hampshire PO13 8LG W: www.hiport.co.uk
United Kingdom
Table of contents