Technical Guide
SER-IP
Vin
Vo
I
OL
UV
OV
AF
MA
OPERATING INSTRUCTIONS
SER-1P
INDEX
• 1.0 Introduction
• 2.0 Salient Features
• 3.0 Display/Front Panel
• 4.0 Technical Specification
• 5.0 Relay Card Description:
• 6.0 Switches Description
• 7.0 LEDs Description
• 8.0 Parameter Mode
• 9.0 Setting Procedure: How to Enter in Parameter Mode
• 10.0 Setting Procedure: How to Restore Factory Settings
• 11.0 Setting Procedure: How to Enter in View Mode
• 12.0 Setting Procedure: How to Reset Password
• 13.0 Terminal Numbers
• 14.0 Connection Diagram
• 15.0 Dimensional Detail
0 1.0 Introduction
SER-1P is digital controller equipped with 3 row alphanumeric seven segment
display and 5 navigator keys simplifies configuration of controller.
0 2.0 Salient Features:
• 32 Bit RISC floating point microprocessor.
• Response time 60mSec.
• Fast Fourier Transformation to eliminate Harmonics & Surges/Sag.
• High performance & Accuracy.
• Simultaneous display of all measured quantity.
• Password protection for user programmable parameters.
Auto Mode
Selection
Switch
Output
Voltage
Increment
Switch
LED
Indication
Output
Voltage
Decrement
Switch
Reset
Switch
Manual
Mode
Selection
Switch
SER-IP
Vin
Vo
I
OL
UV
OV
AF
MA
0 3.0 Display/Front Panel:
• Fault Indication LEDs
• Manual /Auto mode LEDs
• Limit switches LEDs
• Manual/Auto selection switch.
• Output voltage Increment/Decrement switch.
• Reset switch.
0 4.0 Technical Specifications
Measurement Accuracy : Class 1(± 1% Of Full Scale)
Input Voltage : Vph, VN
Input Voltage Measured Range :10-350V AC (L-N)
Voltage Withstand : 800V L-L Max., 1000V for 1 Minute
Isolation Between Terminal & Body : 2kV
Input Current : Iph
Input Current Range : 0-6 A
Current Withstand : 10A Continuous, 50A for 1 Second
Input Frequency : 45 To 55 Hz
Auxiliary Supply : Ph-N(50-350V AC/DC)
Input/output Voltage Display : 1 Row 3 Digit
Input Current Display : 1 Row 3 Digit
Response Time : 60msec
Operating Temperature : -20°C to +70°C
Storage Temperature : -25°C to +80°C
Mounting : Panel Mount
Cut out Dimensions : 91mm X 91mm
0 5.0 Relay Card Description:
! For SER-1P four potential free output contacts are provided :
1. Phase Increase 2. Phase Decrease
3. Hooter 4. Trip.
! Relay Specifications
Contact Arrangement : 1 C/O
Contact Rating : 10A @ 230 VAC
6
Mechanical life expectancy : 10
5
Electrical life expectancy : 10
Auto Mode
By pressing the Auto switch for 3 sec ,
controller enters in Auto Mode.
Increment
By pressing the increment switch, the
output voltage limit can be increased.
Decrement
By pressing the decrement switch, the
output voltage limit can be decreased.
Reset
By pressing the Reset switch, hooter
and fault signals are reseted.
Programming
Mode
entry
Next
By pressing both switches (Auto &
Reset) the controller will enter in
programming mode.
After entering in programming mode
the Reset switch is used to select the
next parameter to be programmed.
A
Switch Symol
Switch Function
Description
Manual Mode
By pressing the Manual switch, for 3
sec controller enters in manual mode.
M
0 6.0 Switches Description:
PSR-3/PSR-1 has 6 switches provided on its front panel. The table below
describes the operation of these:
A
&
Low
Low LED glows continuously when low voltage
limit is reached.
High
High LED glows continuously when high voltage
limit is reached.
AF
AF LED glows continuously when auto
correction of set system output voltage is not
perceived.
OV
OV LED glows continuously when Over Voltage
is perceived.
UV
UV LED glows continuously when Under Voltage
is perceived.
OL
OL LED glows continuously when overload is
perceived.
0 7.0 LEDs Description
SER-1P has 8 LEDs provided on its front panel. The table below describes
the operation of these.
Nomenclature
Symbol
Description
Auto
Auto LED glows continuously when controller is
in Auto Mode.
Manual
Manual LED glows continuously when controller
is in Manual Mode.
M
A
Set Vol (Set output
voltage limit)
Set the desired output voltage.
230
200-550
Set Vol Hys
The desired output voltage
hysteresis.
10
1-20
CT Pri
The desired primary turns of CT
005
1-999
CT Sec
The desired secondary turns of CT
5
1-10
OV
The desired over voltage limit
280
200-300
OV HYS
The desired over voltage
hysteresis.
10
1-20
OV DLY
The desired over voltage fault
delay.
3
1-20
UV
The desired under voltage limit
200
100-300
UV HYS
The desired under voltage
hysteresis.
10
1-20
UV DLY
The desired under voltage fault
delay.
3
1-20
OL
The desired over load limit
005
1-999
OL DLY
The desired over load fault delay.
5
1-20
Hot
Hooter
120
1-999
Parameter
Name
on Display
Explanation of Parameter
Factory
Setting
Setting
Range
Ent PAS (Enter
password)
System settings are password
protected. Password is a three digit
number.
1
1-999
0 8. Parameter Mode
The following tables gives the detailed descriptions of parameter name/settings
0 9. Setting Procedure: How to Enter in Parameter Mode
• Press AUTO & RESET switches simultaneously. The controller shall
display, "Edt".
• To enter in edit parameter mode
Press Auto & Reset switch together
Edt appears on display.
Press "Reset" switch to move forward
Press Keys above
Together
Edt
&
Display will show PAS 1
Press INC or DEC switch to reach 1 which is the
default password. Once 1 is set Press "Reset "
switch to move forward
Ent PAS 1
Display will show PAS Ok
PAS OK
Press "Reset" switch to move forward
Display will show SET VOL 230
SET VOL 230
Press INC or DEC switch to select the desired Output
voltage. Press "Reset" switch to move forward
SVL HYS 1 Display will show SVL HYS 1
Press INC or DEC swtich to select the desired
Hyseteresis. Press "Reset" switch to move forward
A
OV DLY 3
UV 200
UV HYS 10
Display will show OV DLY 3
Press INC or DEC switch to select the desired
Over voltage fault delay. Press "Reset" switch to move
forward.
Display will show UV 200
Press INC or DEC switch to select the desired Under
voltage limit. Press ""Reset" switch to
move forward
Display will show UV HYS 10
Press INC or DEC switch to select the desired CT
Primary turns .Press "Reset" switch to move forward
Display will show CT SEC 005
CT SEC 005
Press INC or DEC switch to select the desired
CT Secondary turns. Press "Reset" switch to
move forward
OV 280 Display will show OV 280
Press INC or DEC switch to select the desired Over
Voltage limit. Press "Reset" switch to move forward
OV HYS 10 Display will show OV HYS 10
Display will show CT PRI 005
CT PRI 005
Press INC or DEC switch to select the desired Under
voltage Hysteresis.
Press "Reset" switch to move forward
Press INC or DEC switch to select the desired Over
voltage Hysteresis.
Press "Reset" switch to move forward
HOT 120 Display will show HOT 120
Press INC or DEC switch to select the desired Hooter
enable time.
Press "Reset" switch to move forward.
UV DLY 3
OL 005
OL DLY 5
Display will show UV DLY 3
Press INC or DEC switch to select the desired Under
voltage fault delay.
Press "Reset" switch to move forward
Display will show OL 005
Press INC or DEC switch to select the desired Over
Load limit. Press "Reset" switch to move forward
Display will show OL DLY 05
Press INC or DEC switch to select the desired Over
Load fault delay.
Press "Reset" switch to move forward.
DEF SET Display will show DEF SET
Press "Reset" switch to move forward.
Ent PAS 1
Press INC/DEC switch to enter desired password
Press "Reset" switch to move forward.
PAS Ok Display will show PAS Ok
Press "Reset" switch to move forward.
Display will show Ent PAS 1
Def Set No Display will show DEF SET No
Press INC/DEC switch to choose between yes or no
Press yes to restore default factory settings
Press "Reset" switch to move forward.
0 10. Setting Procedure: How to Restore Factory Settings
Press Keys above
Together Press AUTO & RESET switch together
Press INC switch to choose DEF SET
Press "Reset" switch to move forward.
0 12.0 Setting Procedure: How to Reset Password
Press Keys above
Together Press AUTO & RESET switch together
Press INC switch to choose RST PAS
Press "Reset" switch to move foreward.
Ent PAS 001 Display will show Ent PAS 001
Press INC or DEC switch to select desired password.
Press "Reset" switch to move forward.
PAS Ok Display will show PAS Ok
Press "Reset" switch to move forward.
NEW PAS 001 Display will show Rev PAS 001
Press INC or DEC switch to select desired password.
Press "Reset" switch to move forward.
Display will show PAS UPT (Password Updated)
0 11.0 Setting Procedure: How to Enter in View Mode
Press Keys above
Together Press AUTO & RESET switch together
Press INC switch to choose VIE
Press "Reset" switch to move foreward.
VIE Display will show VIE
Press "Reset" switch to move forward.
By pressing "Reset" switch browse through all the set parameters one by one.
0 13.0 Terminal Numbers:
Terminal No.
Description
1
Voltage I/P
2
Blank
3
Neutral
4
Voltage O/P
5
CT S2
6
Blank
7
CT S1
8
Motor UP
9
Motor Down
10
Hooter
11
Trip
12
Common for Triac
13
Remote UP
14
Remote Down
15
Common
16
Hig-Cut
17
Low-Cut
18
Blank
19
Neutral
0 14.0 Connection Diagram:
Remote Down
Neutral
High Cut
Low Cut
Common
Remote UP
Motor UP
Motor Down
Hooter
Trip
Com Triac
Voltage I/P
Voltage O/P
Blank
Blank
CT S2
CT S1
®
MRM Pvt. Ltd. PROCOM
Plot No. 20-21, Sector-59 (II) HUDA Faridabad, Haryana,
Tel : 0129-4700400 (10 Lines) www.mrmprocom.com
171615
14
13
12
11
109
819
18
7
6
5
4
321
SER-1P
Blank
Neutral
To Triac Card
0 15.0 Dimensional Detail
All dimensions are in mm.

Other Procom Controllers manuals

Procom ECON-F User manual

Procom

Procom ECON-F User manual

Procom ECON-A User manual

Procom

Procom ECON-A User manual

Procom DGC-7RR User manual

Procom

Procom DGC-7RR User manual

Procom DGC-6D User manual

Procom

Procom DGC-6D User manual

Procom DGC-202 Series User manual

Procom

Procom DGC-202 Series User manual

Procom ECON-A-4C User manual

Procom

Procom ECON-A-4C User manual

Popular Controllers manuals by other brands

Irritrol Junior Plus 2 instruction manual

Irritrol

Irritrol Junior Plus 2 instruction manual

Ltech LT-3800-6A quick start guide

Ltech

Ltech LT-3800-6A quick start guide

Fisher 480-12 instruction manual

Fisher

Fisher 480-12 instruction manual

Lab.gruppen NLB 60E supplementary guide

Lab.gruppen

Lab.gruppen NLB 60E supplementary guide

Team Orion YDS2HV 1605 INSTRUCTION MANUAL AND WARNINGS

Team Orion

Team Orion YDS2HV 1605 INSTRUCTION MANUAL AND WARNINGS

CHIAROSCURO ST50 User and maintenance manual

CHIAROSCURO

CHIAROSCURO ST50 User and maintenance manual

VECTOR CONTROLS TCX2 Product data sheet

VECTOR CONTROLS

VECTOR CONTROLS TCX2 Product data sheet

IMI NORGREN R74G Installation & maintenance instructions

IMI NORGREN

IMI NORGREN R74G Installation & maintenance instructions

Sonnet TEMPO-X SATA 4+4 quick start guide

Sonnet

Sonnet TEMPO-X SATA 4+4 quick start guide

Boston Scientific SpyGlass DS user manual

Boston Scientific

Boston Scientific SpyGlass DS user manual

THK KSF instruction manual

THK

THK KSF instruction manual

Dometic DTD01A instruction manual

Dometic

Dometic DTD01A instruction manual

Mitsubishi MELSEC-F Training manual

Mitsubishi

Mitsubishi MELSEC-F Training manual

Carlisle BINKS 85-448 Service manual

Carlisle

Carlisle BINKS 85-448 Service manual

Eaton CGLine+ Web Controller Quick installation manual

Eaton

Eaton CGLine+ Web Controller Quick installation manual

LEGRAND 0 766 22 Installation and user guide

LEGRAND

LEGRAND 0 766 22 Installation and user guide

SJE Rhombus Ultra Nator System Installation Instructions

SJE Rhombus

SJE Rhombus Ultra Nator System Installation Instructions

Siemens RVP550 installation instructions

Siemens

Siemens RVP550 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.