manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Protherm
  6. •
  7. Boiler
  8. •
  9. Protherm 24(12) KTO How to use

Protherm 24(12) KTO How to use

Supplied By www.heating spares.co Tel. 0161 620 6677
1
Panther 24 (12) KTO and 24 (12) KOO
The boiler’s Serial No. is shown on the plate which is attached to the rear side of the
control panel. The control panel is accessible after removing the front cover.
In section “Operating Instructions” you will find description of the boiler’s main functions
and guidelines how to handle the boiler safely. Section “Installation Instructions” is for
skilled workers only..
Table of contents
Introduction........................................... 2
OPERATING INSTRUCTIONS
Control and signals............................... 4
Selecting Read mode ........................... 5
Selecting Setup mode ......................... 5
Schematic diagram of boiler control ..... 7
Error codes .......................................... 8
Starting the boiler and shutting it down 9
Boiler control ....................................... 10
Protection functions ............................ 11
Service and maintenance ................... 13
Warranty and warranty conditions ...... 14
Technical parameters ......................... 15
Connection dimensions ...................... 17
Usable presure into system................. 18
Schematic diagram of boiler operation 19
INSTALLATION INSTRUCTIONS
Introduction ......................................... 20
Delivery completness .......................... 22
Preparing for boiler installation ........... 23
Installing boiler .................................... 24
Air supply and comustion gases removal
system (type KTO)............................... 28
Electrical wiring of boiler...................... 32
Interconnecting the boiler to water tank33
Converting to different fuel ................. 34
Electical wiring diagram ...................... 35
Supplied By www.heating spares.co Tel. 0161 620 6677
23
1. The boiler and all associated equipment
must be installed and used in accordan-
ce with the installation design, all appli-
cable legal regulations and technical
standards and with the manufacture’s
instructions.
2. The boiler may be installed only in an
environment for which it is designed.
3. After installation, the boiler may be put
into operation by an authorised service
organisation only.
4. The boiler complies with regulations
applicable in the Czech Republic. When
used in the conditions of other coun-
tries, any deviations from local regula-
tions must be identified and addressed.
5. In the event of a defect, call a manu-
facturer’s service organisation – any
unauthorised interference may damage
the boiler (and possibly also associated
equipment!).
6. The service technician putting the boi-
ler into operation for the first time must
show the user the different parts of the
boiler and how to control the boiler.
7. Check whether the delivery is comple-
te.
8. Check whether the model and type sup-
plied is suitable for the required use.
9. Whenever you are not certain how to
control the boiler, study appropriate
instructions in this Operation and In-
stallation Guide carefully and proceed
accordingly.
10. Never remove or damage any markings
and signs on the boiler.
11. When making any repairs, only original
parts must always be used. It is forbid-
den to make any changes in the boiler’s
internal installation, or to interfere with it
in any way.
12. When shutting the boiler down for a
longer period of time, we recommend
to turn the gas supply off and discon-
nect the boiler from power supply. This
recommendation applies in conjunction
with the general conditions stipulated in
this Operation and Installation Guide.
13. At the end of its useful life, the boilers
or its parts must be disposed of ecolo-
gically, to avoid causing any harm to the
environment.
14. The manufacture disclaims any respon-
sibility for damages caused by the failu-
re to abide by:
• the conditions stipulated in this Ope-
ration and Installation Guide;
• applicable regulations and standards;
• proper installation and operation pro-
cedures;
• conditions stated in the Warranty Cer-
tificate and the Service Book.
Safety of equipment and people
• According to the findings of the SZÚ
Brno (National Testing Institute), the boi-
ler (as well as all its optional accesso-
ries) complies with the requirements of
European Directive 90/396/EEC on gas-
-fuelled appliances and European Dire-
ctive 92/42/EEC on efficiency (which are
equivalent to Act No. 22/1997 [in the
wording of Act No. 71/2000] and Gover-
nment Decree No. 177/1997 [in the wor-
ding of Government Decree No. 287/
2000]), and in addition complies with
ČSN EN 50 165, ČSN EN 437, ČSN EN
483, ČSN EN 625 and ČSN EN 60 335
– 1; it also complies with ČSN 06 1008
and Act No. 513/1991 the Commercial
Code, Act No. 634/1992 and Public Noti-
ce of the Ministry of Health of ČSR No.
13/1997, as well as its all later amend-
ments.
• In order to run and operate the boiler in
Introduction
accordance with the purpose for which it
is designed in actual conditions of use
(hereafter referred to only as use), it is
necessary to abide also by additional
conditions – the most essential ones of
which (i.e. those which must not be omit-
ted) are found in the following regulatory
documents:
- in the design area: ČSN 06 0310 and
ČSN 06 0830 (and for the KOV model
also ČSN 73 4201);
- in the fire safety area: ČSN 06 1008;
- for installation and fitting (and repairs):
ČSN EN 1755 or ČSN 38 6460, (for
the KOV model also ČSN 73 4210),
Public Notice No. 48/1982 (as amen-
ded) and binding occupational health
regulations;
- for running and operation: ČSN
38 6405.
• In addition to the above mentioned docu-
ments, it is necessary when using the
boiler to proceed in accordance with this
Operation and Installation Guide and the
accompanying boiler manufacturer’s do-
cumentation. Any interference by chil-
dren, persons under the influence of
narcotic drugs, certified persons, etc.,
when using the boiler, must be preven-
ted.
Situations might occur in practice, in
which the following essential measures
must be adopted:
• prevent the boiler from (even accidental-
ly) being turned on while conducting in-
spections or working on the combustion
gasses flue route or gas and water distri-
bution pipes, by disconnecting the boiler
from power supply also by other means
than merely turning the main switch off
(e.g. by pulling the power cord plug out
of power socket);
• shut the boiler down every time when
there are any (even temporary) flam-
mable or explosive fumes present on the
premises from which combustion air is
supplied to the boiler (e.g. from paint
when painting, laying and spraying mol-
ten substances, from gas leaks, etc.);
• if it is necessary to drain water from the
boiler or from the whole system, the wa-
ter must not be dangerously hot;
• when water is leaking from the boiler’s
heat exchanger or when the exchanger
is clogged up with ice, do not attempt to
start up the boiler until normal operating
conditions have been restored;
• when gas leak has been detected or the
gas supply failed, or if is suspected that
this has happened, shut the boiler down,
turn the gas supply off and call the gas
supply company or a service organisati-
on.
Supplied By www.heating spares.co Tel. 0161 620 6677
4 5
Setting heating water temperature
Press the button
repeatedly until the LED
underneath the symbol
starts flashing. By
pressing the or but-
tons set the heating wa-
ter temperature to the required value. The
setting range is --, 45, 50, 55, 60, 65, 70,
75, 80, 85˚C.
To set the boiler to the SUMMER mode
(hot water heating only), set the value to
--.
Displaying heating water pressure
By pressing the
button, pressure (in bar) in
the heating water system
will be displayed for 30
seconds. The LED under-
neath the symbol is lit.
Low heating water pressure alert
When the pressure drops
below 1 bar, the LED un-
derneath the symbol
will start flashing. The bo-
iler remains functional, but
the water pressure must
be adjusted to the recom-
mended value of 1.2 – 2 bar.
Displaying HW temperature
After turning the boiler on
with the main switch, the
current heating water tem-
perature will appear on the
display. This status is indi-
cated by the lit LED under-
neath the symbol .
Displaying HW temperature setting
Press button. The cur-
rent hot water temperature
in the tank is displayed on
the control panel display.
This status is indicated by
the lit LED underneath the
symbol . If the hot water is currently hea-
ted, the dot after the number is flashing.
Note:
Press button again to return
to mode of displaying the heating water
temperature.
Operating instructions
Operating instructions
Controls and signals
Main switch
The main switch (Fig. 1, Position 1) is
used to switch the boiler on or off. The
main switch is situated underneath the
boiler’s bottom edge, in the control panel
centreline.
Important:
The boiler must be put into
operation and switched on for the first time
by an authorised service only!
Control panel
On the boiler’s control panel you can mo-
nitor current values and set the required
parameters.
The control panel has the following control
elements (Fig.1):
2.
Heating water pressure LED – indicates
that pressure is being displayed
3.
Hot water LED – indicates hot water
temperature setting or display mode
Selecting read mode
Selecting setup mode
Setting hot water temperature
Press the button
repeatedly until the LED
underneath the symbol
starts flashing. By pres-
sing the or buttons set
the hot water temperature
to the required value. The setting range is
--, 40, 42, 45, 48, 50, 52, 55, 58, 60˚C.
By pressing the button once more,
the set value will be saved in the memory.
If you wish to disable the hot water hea-
ting function, set the value to --.
Note: Function is active only if hot water
tank is connected.
fig. 1
345
678 910
2
1
Note:
Function is active only if hot water
tank is connected.
4.
Heating water LED – indicates hea-
ting water temperature setting or display
mode
5.
COMFORT hot water heating LED
Note:
Function is unavailable for KTO and
KOO boiler models.
6.
MODE button – used to switch to diffe-
rent reading or value setting modes and to
confirm the set values
7.
(-) button – used to decrease the value
of the parameter being set
8.
Display – displays the values of pressu-
re, temperature, service parameters and
error messages
9.
(+) button – used to increase the
value of the parameter being set
10.
RESET button – used to reset the
F1 fault status (short of gas)
Control panel
Supplied By www.heating spares.co Tel. 0161 620 6677
67
Equithermal mode – curve slope
Press the button – letter E with
the characters (-) and (1) through to (9)
attached will appear on the display. By
pressing the buttons, select the
required equithermal curve. The curve’s
slope grows with the growing number (E1
< E9) – see Fig. 2.
If you wish to turn the equithermal control
off, select (E-).
By pressing the button, the selection
is saved in the memory and the system
switches to the next mode
Note:
Equithermal control requires an
outdoor sensor to be connected to the
boiler, which must not be set to the SUM-
MER mode.
Equithermal mode – parallel curve
shift
Press the button – letter P with
the characters (-) and (1) through to (9)
attached will appear on the display. By
pressing the buttons, select the re-
quired shift as described below, or switch
the mode off by selecting (P-).
Values with a minus sign are subtracted
and values with a plus sign added to the
heating water temperature (determined by
the equithermal curve as a function of the
outdoor temperature). By pressing the
button save the setting in the memo-
ry and return back to the starting position.
P- no shift P5 +3
P1 - 15 P6 +6
P2 - 9 P7 +9
P3 - 6 P8 +15
P4 - 3 P9 +21
Example:
x You have selected the E6 curve slope
and the outdoor temperature is - 10˚C.
The corresponding heating water tem-
fig. 2
fig. 3
fig. 4
Schematic diagram of boiler control
Parallel curve shift
Equithermal curves
perature is 73˚C.
• You have selected parallel shift P3 ….
- 6˚C, the resultant heating water tempe-
rature will be 73 – 6 = 67˚C.
Supplied By www.heating spares.co Tel. 0161 620 6677
89
Loss of heating water pressure – F0
Loss of heating water
pressure (below 0.6
bar) in the system. The
boiler is automatically
shut down – the LED
underneath the symbol
 is flashing. Top up
water in the heating system to increase
the pressure to 1.2 – 2 bar. After water
has been topped up, the boiler will restart
itself automatically.
If the too low or too high pressure of the
heating water recurs again, call an autho-
rised service.
No flame – F1
There is no flame be-
cause gas supply to the
boiler has been inter-
rupted. Check the gas
valve below the boiler
and restart the boiler
by pressing the RESET
button (Pos. 10 in Fig. 1). If the fault recurs
again, overheating of boiler may have
occurred and emergency thermostat was
opened. Call an authorised service in this
case.
Heating water sensor – F2
Error code F2 is repor-
ted when input from the
heating water sensor
has been lost. The boi-
ler is shut down. Call an
authorised service.
Boiler overheated – F3
The boiler has tempo-
rarily overheated. The
boiler is automatically
shut down and waits for
the water temperature
to drop. The boiler will
restart itself automati-
cally after the temperature has dropped
to within the operating temperature range.
If error code F3 keeps recurring, call an
authorised service.
Hot water tank sensor – F4
Short-circuit of hot
water tank sensor is
indicated by F4 error
code. The boiler rema-
ins operational, but only
for heating of heating
water. Call an authori-
sed service.
Note:
If the hot water tank sensor is inter-
rupted, all functions related to heating of
hot water are ignored.
Outdoor sensor – F5
Error code F5 can be
displayed only if the
boiler has an outdoor
sensor connected to it
for equithermal control.
If this sensor is connec-
ted, it means that the
sensor is short-circuited.The boiler is shut
down. Call an authorised service.
Until the fault is repaired, the boiler can be
run with the equithermal control function
disabled (see Controls and signals, Boiler
control elements).
Error codes
Starting the boiler up
Important:
Putting the boiler into operati-
on and starting it up for the first time must
be done by an authorised service only!
If you wish to start the boiler up after it has
been put into operation, make sure that:
1.the boiler is connected to power sup-
ply;
2.all stop valves underneath the boiler are
opened;
3.the heating water pressure is within the
range 1.2 – 2 bar.
Turn the main switch (Fig. 1) to the ON
position (I). The display lights up.
In the event of a safety boiler shutdown
due to the loss of flame, reaction by the
emergency thermostat or the combus-
tion gases thermostat (KOO model),
error code F1 will appear on the display.
If the shutdown was caused by the loss
of flame, the boiler can be unblocked by
pressing the RESET button. If the emer-
gency shutdown recurs after a short time
again, or if the boiler cannot be unblocked
by pressing the RESET button, call an
authorised service.
If the emergency shutdown was triggered
by the emergency thermostat, mere pres-
sing the RESET button will not unblock
the boiler. Unblocking the emergency
thermostat must be done by an authori-
sed service technician, and this operation
cannot be regarded as a warranty repair.
Important:
The boiler must not be run
with the emergency or the combustion ga-
ses thermostat disabled or replaced with
a device other than the one specified by
the manufacturer.
Shutting the boiler down
Turn the main switch to the OFF position
(0).
If the boiler is to remain shut down for a
longer period of time, turn the gas stop
valve underneath the boiler off. When
shutting the boiler down, take into consi-
deration the ambient temperature in the
given season. Unless the boiler and sys-
tem is filled in with antifreeze (Alicol Ter-
mo), both the boiler and the system could
get damaged. In such case drain the hot
water reticulation completely (if hot water
tank is connected).
Starting the boiler up and shutting it down
Supplied By www.heating spares.co Tel. 0161 620 6677
10 11
Using the boiler without a room
control unit
When running in this mode, the boiler
maintains the selected heating water
temperature. No room control unit is con-
nected, the terminals for its connection
must be interconnected with a jumper
(standard factory setting).
Setting procedure:
• turn the main switch to the ON position
(I);
• set the required heating water tempera-
ture on the control panel.
Using the boiler with a room control
unit
The boiler maintains the selected heating
water temperature. The
room control unit wiring
terminal jumper is removed
and the room control unit
is wired to the terminals.
The boiler is turned on and
off to maintain the set temperature in the
room in which the control unit is installed.
This room must not have thermostatic val-
ves installed on heating radiators.
When the room control unit turns the
boiler on, this status is indicated by a dot
after the number shown on the display.
Important:
You must set on the boiler
control panel a heating water temperature
(temperature of the water in the system)
which will be capable of covering thermal
losses of the building even in low outdoor
temperatures. We recommend to select
a temperature within the range of 60 -
80˚C.
Using the boiler with equithermal
control
The boiler changes the heating water
temperature as the outdoor temperature
changes.
Important:
An outdoor temperature sen-
sor must be connected to the boiler! The
outdoor sensor should be located on the
coldest wall of the building (facing north
or north-west), approximately 2.5 – 3 m
above ground level. The sensor must not
be exposed to any false heat waves from
open windows or ventilation shafts, or to
sunshine.
A rule applies when selecting a heating
curve that lower number curves are
suitable for buildings with good thermal
insulation and steeper thermal gradient,
and vice versa.
The thermal curve diagram is used as a
primary source of information. The sys-
tem should be fine-tuned by monitoring
outdoor and indoor temperatures for a
few days.
For first setting of the system choose
curve E6.
When setting the system up, all radiator
valves must be fully opened, thermostatic
valves must be set to maximum tempe-
rature and doors and windows must be
shut.
Setting the curve slope as well as the
parallel shift is done in small increments,
and after each step it is necessary to
wait roughly 2 hours and then assess
the change. It is better to do the setting
when the outdoor temperatures fluctuate
significantly, and the final setting should
be done when the outdoor temperature
drops below freezing point.
Setup procedure:
1. Select the “heating water temperature”
mode and make sure that the function
SUMMER is not selected (symbol --). You
must set a temperature value (this tempe-
rature will have no effect on the equither-
mal control mode).
2. Select the “equithermal mode - curve
slope” and set the E6 symbol - see page
6.
3. Select the “equithermal mode – parallel
shift” and set the symbol (P-).
4. By pressing the MODE button, save the
setting in the memory and return back to
the starting position.
After a few days (when the premises have
been heated up), readjust the curve slope
as required:
5. If the indoor temperature does not
significantly changes with outdoor tempe-
rature changes, the curve selection was
correct. The temperature can be changed
to a higher or a lower value by changing
the size of the parallel shift – see the part
“Controls and signals – Equithermal mode
– Parallel shift”.
Important:
If the indoor temperature
changes significantly with outdoor tem-
perature changes, with the indoor tempe-
rature increasing with a dropping outdoor
temperature, select a lower value curve
and vice versa.
Using the boiler with equithermal
control and room control unit
A room control unit extends the equivalent
control mode by time control and a hea-
ting economy mode (e.g. at night).
Setup procedure:
• set the equivalent control as described
above.
• connect the room control unit to the boi-
ler (after removing the wiring terminal
jumper) and set the required temperatu-
re during the comfortable temperature
period on the control unit to about 5˚C
higher than the temperature reached by
the equithermal control. For economy
mode period (at night, when absent), set
on the room control unit the actual requi-
red temperature – it must be always at
least 3˚C lower than the actual comforta-
ble temperature.
Example:
• the (comfortable) indoor temperature
maintained by the equithermal control is
21˚C.
• set the room control unit for the comfor-
table temperature period to 26˚C and for
the economy mode period to the actual
required temperature, e.g. 16˚C.
Setting the boiler output
The boiler is factory-set to its maximum
output.
Important:
Output setting may be chan-
ged only by an authorised technician.
Boiler control
Protection functions
Protection against freezing
The boiler has a protection system which
protects the boiler (but not the heating and
the hot water distribution systems) against
freezing.
When the heating water in the boiler drops
below 10˚C, the boiler pump is automati-
cally switched on. When the heating water
temperature drops below 8˚C, the boiler
is automatically started up and heats until
the heating water temperature reaches
25˚C.
Note:
The freezing protection system
functions independently from the room
control unit and is activated even when
the heating system is turned off (set to
--).
Important:
If the boiler is left in an envi-
ronment with ambient temperature below
3˚C, the boiler cannot be started up by
turning the main switch on.
Pump protection
When the pump is idle for a protracted
period of time, switch it on once every 24
hours for a short while (approximately 30
seconds) to prevent it from ceasing.
Supplied By www.heating spares.co Tel. 0161 620 6677
12 13
Anti-cycling
After the boiler has been shut down during
the heating operation, it cannot be restar-
ted sooner than 3 minutes elapses after
the shutdown. This function is particularly
useful in heating systems where the maxi-
mum heat loss is at the level of the lower
limit of the boiler’s output range.
Disconnecting the boiler from power
supply
If the boiler is disconnect from power sup-
ply for a protracted period of time (conti-
nuously for a month or longer), we recom-
mend to start up the boiler in regular time
intervals (at least once a month). If the
pump ceases, call an authorised service.
Repairing a pump ceased because of dirt
in the heating system is not covered by
the boiler’s warranty.
Important:
When the boiler is disconnec-
ted from power supply, all its protection
functions are disabled.
Power failure
Power failure will turn the boiler off. When
power supply is restored, the boiler will
automatically restart itself without losing
any of the operating parameters settings.
If after power supply restoration the LED
underneath the symbol F1 lights up, pro-
ceed in accordance with the instructions
in section “Controls and signals / Main
switch”.
The boiler may be blocked because of
overheating caused by the pump being
switched off as a result of the power fai-
lure.
Pump switch-off delay
The pump is factory-set to continue
running for 3 minutes after receiving a
request from the room control unit to shut
the boiler down. When the boiler is used
without a room control unit, the pump is
switched on permanently.
Safety valve
The boiler is equipped with a safety valve
with an opening pressure 3 bar. DO NOT
TOUCH THE SAFETY VALVE! If the sa-
fety valve starts releasing heating water,
always turn the boiler off, disconnect if
from power supply and call a service. If
the heating system repeatedly looses
pressure, consult your service organisa-
tion.
Important:
All the mentioned electronic
protection functions are enabled only
when the boiler is connected to power
supply (the power cord plug is inserted
into a power socket and the main switch is
in the ON position (I).
Service and maintenance
Toping up water to the heating
system
KTO/KOO models boilers are equipped
with an inlet fitted with removable plug
(Fig. 5) situated next to heating water in-
let. After removing the plug, it is possible
to connect the so-called heating water
top-up loop (installation of the top-up loop
to be done by professional company upon
installing the boiler).
Note:
Top-up loop is not part of boiler.
When topping up water, the following con-
ditions must be met:
1.Pressure of the water being supplied to
the boiler must be always higher than
the pressure of the water inside the hea-
ting system.
2.When toping up water, the boiler must
be cold (water temperature must not be
higher than 30˚C).
3.Recommended water pressure inside
the cold boiler (temperature not more
than 30˚C) is 1.2 to 2 bar.
Important:
If the pressure in water mains
is lower or equal to the pressure of the wa-
ter inside the heating system, the heating
water may run into the water mains, which
is forbidden. To avoid this, install a non-re-
turn valve downstream the top-up valve.
Note:
Manufacturer disclaims responsibi-
lity for any damages caused by incorrect
manipulation with the top-up loop (valve)
and a failure to abide by the conditions
specified above. Such damages and
defects are not covered by the boiler’s
warranty.
Procedure of topping up heating water to
the boiler:
• make sure that the boiler is connected to
power supply and the main switch is in
the ON position (I);
• if the display on the boiler’s control panel
indicates that the heating water pressure
is below 0.6 bar, the LED underneath the
symbol flashes and error code F0 ap-
pears on the display;
• turn-open the top-up valve with your
hand and watch the pressure increase
on the control panel display (to see the
pressure value on the display, you must
press the MODE button);
• when the pressure has reached the re-
quired value, turn the top-up valve off
with your hand.
•bleed all radiators carefully (water must
be running out smoothly and continu-
ously, without any air bubbles);
• check whether the pressure shown on
the display is within 1.2 and 2 bar. If ne-
cessary, top up the system more.
fig. 5
Water top-up valve
Supplied By www.heating spares.co Tel. 0161 620 6677
14 15
Warranty and warranty conditions
Cleaning
The boiler cover can be cleaned with
a moist cloth and afterwards dried and
polished with a dry cloth. Do not use abra-
sive detergents or solvents.
Important:
Before cleaning turn the boiler
off with the main switch.
Panther 24KOO
Panther 12KOO
Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .II2H3P
Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B11BS
Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .electronic
Fuel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G20 / G31 . . . . . . . . . . . .G20 / G31
Max. thermal input . . . . . . . . . . . . . . . .[kW] . . . . . . . 25,5 / 25. . . . . . . . . . . . . 12,5 / 10
Min. thermal input . . . . . . . . . . . . . . . . . [kW] . . . . . . . 11 / 10,5. . . . . . . . . . . . . 4,0 / 4,0
Max. thermal output . . . . . . . . . . . . . . .[kW] . . . . . . .23,5 / 22,5 . . . . . . . . . . . . 11,5 / 9,0
Min. thermal output . . . . . . . . . . . . . . . .[kW] . . . . . . . . 9,5 / 9. . . . . . . . . . . . . . 3,5 / 3,5
Efficiency. . . . . . . . . . . . . . . . . . . . . . . . . [%] . . . . . . . 90,7 / 90. . . . . . . . . . . . . . 91 / 91
Gas pressure
Supply pressure . . . . . . . . . . . . . . . . [mbar]. . . . . . . . . . . . . . . . . . . 20 / 37
Jet pressure min.. . . . . . . . . . . . . . . . [mbar]. . . . . . . . . 2,2 / 7. . . . . . . . . . . . . . 1,6 / 5,5
Jet pressure max. . . . . . . . . . . . . . . . [mbar]. . . . . . . 12,2 / 35,7 . . . . . . . . . . . . 14,2 / 30
Jet diameter . . . . . . . . . . . . . . . . . . . . [mm]. . . . . . . . 1,2 / 0,7 . . . . . . . . . . . . . 1,2 / 0,73
Gas consumption
(Q max.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,7 [m3/h] / 2,1 [m3/h] . . . 1,34 [m3/h] / 0,8 [kg/h]
(Q min.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,1 [m3/h] / 0,9 [m3/h] . . 0,45 [m3/h] / 0,34 [kg/h]
Heating
Max. operating pressure . . . . . . . . . . . .[bar] . . . . . . . . . . . . . . . . . . . . 3
Min. operating pressure . . . . . . . . . . . .[bar] . . . . . . . . . . . . . . . . . . . . 0,8
Recommended operating pressure. . . . [bar] . . . . . . . . . . . . . . . . . . 1,2 – 2
Temperature range . . . . . . . . . . . . . . . . [°C] . . . . . . . . . . . . . . . . . . 45 – 85
Expansion vessel . . . . . . . . . . . . . . . . . . . [l] . . . . . . . . . . . . . . . . . . . . 5
Max. quantity of heating water in system . [l] . . . . . . . . . . . . . . . . . . . . 70
Max. pressure in expansion vessel . . . .[bar] . . . . . . . . . . . . . . . . . . . . 3
Utility hot water (if hot water tank is connected)
Max. supply pressure . . . . . . . . . . . . . .[bar] . . . . . . . . . . . . . . . . . . . . 6
Adjustable temperature range . . . . . . . [°C] . . . . . . . . . . . . . . . . . . 42 – 70
Electrical data
Voltage . . . . . . . . . . . . . . . . . . . . . . . [V/Hz] . . . . . . . . . . . . . . . . . . 230/50
Input (max) . . . . . . . . . . . . . . . . . . . . . . .[W] . . . . . . . . . . . . . . . . . . . . 95
Protection cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 45
Current . . . . . . . . . . . . . . . . . . . . . . . . . . [A] . . . . . . . . . . . . . . . . . . . .0,5
Extraction of combustion gases - method
. . . . . . . . . . . . . . . . . into chimney
Flue diameter . . . . . . . . . . . . . . . . . . . [mm] . . . . . . . . . 130. . . . . . . . . . . . . . . . . 110
Combustion gases temperature . . . . . . [°C] . . . . . . . . . . . . . . . . . .95 - 120
Combustion flow mass . . . . . . . . . . . . . [g/s] . . . . . . . . . . 20 . . . . . . . . . . . . . . . . . .16
Min. required stable chimney thrust . . . [Pa] . . . . . . . . . . . . . . . . . . . . 2
Noise (1 m from the boiler at 1,5 m height)[dB] . . . . . . . . . . . . . . . . . do 55
Dimensions - height/width/depth. . . . . [mm] . . . . . 740 / 410 / 320 . . . . . . . .740 / 320 / 320
Weight without water. . . . . . . . . . . . . . . [kg] . . . . . . . . . . 30 . . . . . . . . . . . . . . . . . .27
Technical parametres 24 (12) KOO
The PROTHERM Panther 12 / 24 KTO
and 12 / 24 KOO gas-fired boilers are
covered by a warranty defined in the War-
ranty Certificate, the Service Book and by
other conditions specified in this Operati-
on Guide and Installation Guide (chapters
Introduction and Boiler installation).
Regular servicing
To assure continuous and safe running of
your boiler, we recommend that the boiler
is checked and serviced in regular yearly
intervals. These inspections are not co-
vered by the boiler’s warranty. The works
to be done are specified in the Service
Book and must be done by an authorised
service.
Supplied By www.heating spares.co Tel. 0161 620 6677
16 17
Panther 24 KTO Panther 12 KTO
Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .II2H3P
Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C12, C32, C42, C52, C82
Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .electronic
Fuel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G20 / G31 . . . . . . . . . . . G20 / G 31
Max. thermal input . . . . . . . . . . . . . . . .[kW] . . . . . . . . 26 / 25 . . . . . . . . . . . . . 12,5 / 10
Min. thermal input . . . . . . . . . . . . . . . . . [kW] . . . . . . . 11 / 10,5. . . . . . . . . . . . . 4,0 / 4,0
Max. thermal output . . . . . . . . . . . . . . .[kW] . . . . . . . 24 / 22,5. . . . . . . . . . . . . 11,5 / 9,0
Min. thermal output . . . . . . . . . . . . . . . .[kW] . . . . . . . . 9,5 / 9. . . . . . . . . . . . . . 3,5 / 3,5
Efficiency. . . . . . . . . . . . . . . . . . . . . . . . . [%] . . . . . . .91,7 / 90,5 . . . . . . . . . . . . . 91 / 91
Gas pressure
Supply pressure . . . . . . . . . . . . . . . . [mbar]. . . . . . . . .20 / 37
Jet pressure min . . . . . . . . . . . . . . . [mbar]. . . . . . . . . 2,2 / 7. . . . . . . . . . . . . . 1,6 / 5,5
Jet pressure max . . . . . . . . . . . . . . . [mbar]. . . . . . . 12,2 / 35,7 . . . . . . . . . . . . 14,2 / 30
Jet diameter . . . . . . . . . . . . . . . . . . . . [mm]. . . . . . . . 1,2 / 0,7 . . . . . . . . . . . . . 1,2 / 0,73
Gas comsumption
(Q max.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2,7 [m3/h] / 2,1 [kg/h] . . 1,34 [m3/h] / 0,8 [kg/h]
(Q min.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,1 [m3/h] / 0,9 [kg/h] . . 0,45 [m3/h] / 0,34 [kg/h]
Heating
Max. operating pressure . . . . . . . . . . . .[bar] . . . . . . . . . . . . . . . . . . . . 3
Min. operating pressure . . . . . . . . . . . .[bar] . . . . . . . . . . . . . . . . . . . . 0,8
Recommended operating pressure. . . . [bar] . . . . . . . . . . . . . . . . . . 1,2 – 2
Temperature range . . . . . . . . . . . . . . . . [°C] . . . . . . . . . . . . . . . . . . 45 – 85
Expansion vessel . . . . . . . . . . . . . . . . . . . [l] . . . . . . . . . . . . . . . . . . . . 5
Max. quantity of heating water in system . [l] . . . . . . . . . . . . . . . . . . . . 70
Max. pressure in expansion vessel . . . .[bar] . . . . . . . . . . . . . . . . . . . . 3
Utility hot water (if hot water tank is connected)
Max. supply pressure . . . . . . . . . . . . . .[bar] . . . . . . . . . . . . . . . . . . . . 6
Adjustable temperature pressure . . . . . [°C] . . . . . . . . . . . . . . . . . . 42 – 70
Electrical data
Voltage . . . . . . . . . . . . . . . . . . . . . . . [V/Hz] . . . . . . . . . . . . . . . . . . 230/50
Input (max) . . . . . . . . . . . . . . . . . . . . . . .[W] . . . . . . . . . . . . . . . . . . . 120
Protection cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 45
Current . . . . . . . . . . . . . . . . . . . . . . . . . . [A] . . . . . . . . . . . . . . . . . . . .0,6
Extraction of combustion gases - method
. . . . . . . . . . . . . . . . . . . . turbo
Flue diameter . . . . . . . . . . . . . . . . . . . [mm] . . . . . . . . . . . . . . 100 / 60 (80 / 80)
Max. length of concentric flue 60/100 . .[Em] . . . . . . . . . . . . . . . . . . . . 9
Max. lenght of detached flue 80 + 80 . .[Em] . . . . . . . . . . . . . . . . . . . . 18
Combustion gases temperature . . . . . . [°C] . . . . . . . . . . . . . . . . . 115 - 145
Combustion flow mass . . . . . . . . . . . . . [g/s]. . . . . . . . . . 18 . . . . . . . . . . . . . . . . . .15
Noise (1m from boiler at 1,5 m height) . .[dB]. . . . . . . . . . . . . . . . . . . do 55
dimensions - height/width/depth . . . . . [mm] . . . . . 740 / 410 / 320 . . . . . . . . 740 / 320 / 320
Weight without water. . . . . . . . . . . . . . . [kg] . . . . . . . . . . 31. . . . . . . . . . . . . . . . . . 28
Technical parameters 24 (12)KTO Connection dimensions 24 KTO / KOO
fig. 6
4
2
1 3
1. Outpup of HW G3/4“ / 2. Gas input G3/4“
3. Plug (top-up) G1/2“ / 4. Input of HW G3/4“
KOO layout
Supplied By www.heating spares.co Tel. 0161 620 6677
18 19
fig. 9
Connection dimensions 12 KTO
Připojovací rozměry kotle
Usable pressure into system
Flow through heating system (l/h)
Useable pressure into heating system
(10 kPa = 1 m H2O)
fig. 8
fig. 7
1. Gas input G3/4“ / 2. Outpu of HW G3/4“
3. Plug (top-up) G1/2“ / 4. Input of HW G3/4“
1*. Combustion geses thermostat 8. Pump with bleed valve 17. HW temperature sonsor
1. Air manostat 9. Safety valve 18. Emergency thermostat
2*. Thrust breaker 10. HW input
Interconnection of boiler with
ta
nk
2. Fan 11. Top-up inlet 19. HW input from tank
3. Combustion gas collector 12. Gas input 20. T-piece
4. HW exchanger 13. HW output 21. 3-way valve
5. Burner 14. Draining valve 22. HW output into tank
6. Gas valve 15. Presuure sensor 23. 3-way valve actuator
7. Expansion vessel 16. By-pass
Schematic diagram of boiler operating
24 (12) KTO
24 (12) KOO
Connectig boiler
to water tank
KOO layout
Supplied By www.heating spares.co Tel. 0161 620 6677
20 21
a combined calcium and magnesium
concentration greater than 1.8 mmol/l, it
is useful to implement other “non-chemi-
cal” measures against incrustation (e.g.
magnetic water treatment combined with
a desludging device).
Problems caused by clogging the system
with dirt from the heating system or in-
crustation sediments or problems caused
by other clogging (e.g. clogging of the
heat exchanger, pump defects) are not
cover by the boiler’s warranty.
The distance from flammable materials
(e.g. PVC, chipboard, polyurethane, syn-
The PROTHERM Panther 24 (12) KTO
and 24 (12) KOO boilers are compatible
with common types of hot water heating
systems and heating radiators.
Important:
The PROTHERM boilers must
be put into operation only by authorised
organisations according to Czech Bureau
of Occupational Safety and Czech Safety
Inspectorate Notice No. 21/1979 (in the
wording of Public Notice No. 554/1990).
The boiler must be put into operation and
warranty and post-warranty service must
be performed by the manufacturer’s con-
tracted service organisation which meets
the above specified requirements.
The boiler is designed to work in a normal
AA5/AB5 environment according to ČSN
22 2000-3 and ČSN 33 2000-5-51 (i.e.
within temperature range +5 to +40˚C and
humidity depending on temperature but
maximum 85%).
The 24 (12) KTO and 24 (12) KOO boilers
are suitable for the conditions of zones
1, 2 and 3, in rooms with a bath tub or
shower and washing rooms according
to ČSN 33 2000-7-71; they may not be
installed in zone 0 environment (Fig. 10).
When installed in the above rooms, the
boilers must be have a protection against
electric shock in accordance with the
same standard.
The boilers are designed to run with he-
ating water compliant with ČSN 07 7401
(which under no circumstances can be
acidic, i.e. its pH factor must be greater
than 7 and must have a minimal carbona-
te hardness).
Requirements on utility water properties
are defined in ČSN 83 0618 (on drinking
water in ČSN 75 7111). If the water has
Installation instruktions
Installation instruktions
Introduction
obr. 10
and fresh air supplied through a special
for this purpose designed dual ducting.
Practically any required dual ducting route
can be constructed from standard com-
ponents supplied by the manufacturer.
The exhaust route must be constructed in
such a way that condensed water vapour
contained in the combustion gases can
be removed from the ducting. This is done
using special components which can be
built into the exhaust route. Problems cau-
sed by condensate penetration are not
covered by the boiler’s warranty. Because
of the considerable variety of particular
solutions, the dual ducting is not part of
the boiler delivery and is not included in
the price. Principles for route construction
are described in chapter Air supply and
combustion gases removal ducting.
The 24 (12) KOO is designed for combus-
tion gases to be removed and discharged
into a chimney (through a chimney inlet)
with a minimum stabilised thrust of 2 Pa.
The boiler is connected to the chimney
inlet by a flue of a diameter corresponding
to the size of the boiler’s gas exhaust
outlet. It is forbidden to place inside the
combustion gases exhaust ducting any
objects which impair the combustion
gasses flow (e.g. various types of heat
exchangers to utilise their residual heat).
The combustion gases exhaust ducting is
not part of the boiler accessories.
Construction of the combustion gases ex-
haust ducting as well as that of the chim-
ney must comply with the requirements of
ČSN 06 1610 and ČSN 73 4201. Compli-
ance with the requirements specified by
these standards will prevent undesirable
phenomena from occurring, such as ex-
cessive cooling of the combustion gases,
penetration of dampness into brickwork
and fluctuations in the chimney thrust,
and thus prevent undesirable effects on
the boiler’s functioning.
The boiler takes combustion air from the
300 mm
300 mm
300 mm
300 mm
600 mm
Installation distances
fig. 11
Zones
thetic fibres, rubber and others) must be
sufficient so that the surface temperature
of these materials does not exceed 80˚C.
Important:
Surface temperature of upper
parts (particularly the side walls and the
cover) of a working boiler might exceed
the ambient temperature by up to 50˚C.
A minimum manipulation (free) space
maintained around the immediate vici-
nity of the boiler must be sufficient for
a person to work on it safely with bare
hands and with common hand tools.
Recommended distances are shown in
Fig. 11.In the 24 (12) KTO models, com-
bustion gases must be always removed
space in which it is installed. Air must be
supplied in sufficient quantity in accordan-
ce with applicable regulations.
Supplied By www.heating spares.co Tel. 0161 620 6677
22 23
fig. 12
Content of delivery
Delivery
The PROTHERM Panther 24 (12) KTO
and 24 (12) KOO boilers are supplied
completely assembled and functionally
tested.
The delivery includes (Fig. 12):
1.The boiler
2.Operation and Installation Guide
3.Service Book
4.List of service centres
5.Warranty Certificate
6.An installation bar with fasteners
Special delivery
On request the following accessories can
be supplied:
1.Outdoor sensor for equithermal control,
order No. 4180
2.Combustion gases exhaust ducting
components diameter 60100 for model
KTO e.g.:
-
S5D-1000
Horizontal set (90˚ flanged
elbow, 1 m end-piece), Order No.
7194
-
K1D
90˚ elbow, Order No. 2842
-
T1D-1000
Extender, Order No. 2825
-
S3
Chimney kit (roof end-piece), Or-
der No. 2805
-
Z1
Condensate catcher, Order No.
2857
3.Combustion gases exhaust ducting
components diameter 80 for model KTV,
e.g.:
-
S2
Separate set (distributor, 2 × 90˚
elbow, 2 × 1 m end-piece), Order No.
2803
-
K2A
90° elbow, Order No. 2830
-
T2
Separate duct section (1 m exten-
der), Order No. 2819
-
S4
Chimney kit (roof end-piece), Or-
der No. 2809
- Z2
Condensate catcher, Order No.
2858
Delivery completeness
Reticulation
Nominal pipe internal diameter is chosen
in the usual way, using the pump chara-
cteristic. Reticulation is designed accor-
ding to the requirements for the system
performance, not according to the boiler’s
maximum output. The system must allow
sufficient flow so that the water tempe-
rature difference in the supply and the
return pipe is less than or equal to 20˚C.
Minimum flow must be 500 l/h.
The piping system construction must pre-
vent air bubbles from developing, making
permanent bleeding of the system easier.
Bleeding valves should be situated on
all high points of the system and on all
radiators.
It is recommended to install before the bo-
iler a set of heating water, hot water and
gas stop valves.
Before final installation of the boiler, the
heating distribution system pipes must
be flushed a few times with pressurised
water. In old, already used systems, the
flushing must be done in the direction op-
posite to the flowing heating water.
Important:
Before connecting the boiler
to the heating system, remove the plas-
tic plugs located inside all connection
outlets.
Heating system cleanliness
Before installing a new boiler, it is es-
sential to clean the system thoroughly. In
old systems it is necessary to remove all
sludge settled at the bottom of radiators
(gravity system).
In new systems it is necessary to remove
all conservation material used by majority
of radiator manufacturers.
It is recommended to install before the
boiler (i.e. to the heating water return
pipe) a sludge separator. The sludge se-
parator should be constructed in such a
way that it is easy to empty in regular time
intervals without the necessity to drain a
lot of water from the heating system. The
separator can be combined with a filter,
but a filter with a sieve alone is not a suf-
ficient protection. The filter and the sludge
separator must be checked and cleaned
regularly.
Heating water circulation
Although the boiler is equipped with a
bypass, we recommend to design the
heating system so that the heating water
flows through at least some of the radia-
tors all the time.
Using antifreeze
We do not recommend to use antifreeze
because of their unsuitable properties for
the boiler. It is mainly their reduced heat
transfer, large volume expansion, aging
and adverse effect on rubber parts.
If it is necessary to use antifreeze, we re-
commend Alicol Termo (manufactured by
Slovnaft Bratislava and distributed in the
Czech Republic by Slovnaft Praha) – the
manufacturer’s experience shows that
using this material does not reduce the
boiler safety and has not any significant
impact on the boiler’s functioning. If under
specific conditions this method of protecti-
on against heating system freezing is not
possible, then failure to meet the specified
functional parameters or any defects of
the boiler caused by using a different an-
tifreeze will not be covered by the boiler’s
warranty.
Preparing for boiler installation
Supplied By www.heating spares.co Tel. 0161 620 6677
24 25
Thermostatic radiator valves
If a room control unit is installed, at least
one of the radiators in the reference room
must be without a thermostatic valve. For
better temperature comfort we recom-
mend to leave all radiators in the referen-
ce room without a thermostatic valve.
Hot water system
Pressure inside the hot water system
must be within the range of 1 to 6 bar. If
the pressure exceeds 6 bar, a pressure
reduction valve must be fitted on the sup-
ply side, combined with a safety valve.
In areas with very hard water we recom-
mend to implement suitable measures to
reduce the water hardness.
Installing the boiler
Mounting the boiler on the wall
When mounting the boiler on the wall, pro-
ceed in accordance with the installation
design conditions (e.g. wall load bearing
properties, chimney inlet, pipe inlet and
outlet connections).
The mounting procedure (Fig. 13):
1.Project and mark the boiler position in
the place of installation (5). Use libel or
lead). Mind outlets of gas and water reti-
culation.
2.Using the connection dimensions (see
pages 17-18), mark points for fixing the
mounting bar (part of boiler delivery).
3.If you are installing a boiler with forced
combustion gases removal (KTO), and
the gases will discharged directly from
the building’s façade, project and mark
an opening for a pass of the concentric
ducting.
4.Outlets of gas and water reticulation
must conform to connection dimensions
(see pages 17-18). Upon installation,
mind the connection of stop valves (4)
including heating water top-up valve
(stop valves are not part of boiler delive-
ry).
5.Drill the required holes.
6.Insert wall plugs into the holes for the
mounting bar and then fasten the bar
properly with the screws provided.
7.Hang the boiler on the mounting bar (3).
8.If you are installing a KTO boiler, install
the combustion gases removal ducting
(2). Fill-in the gaps between the ducting
and the wall opening with a non-flam-
mable material.
9.Connect heating water reticulation and
gas distribution pipes to the boiler.
Connecting the boiler to heating
water reticulation and gas
distribution pipes (and possibly hot
water pipes)
The boiler pipe connection pieces must
not be subjected to any forces from the
heating water, hot water or gas piping sys-
tem. This requires accurate positioning of
all connection pipes, vertically (height) as
well as the distance from the wall and mu-
tual distance between inlets and outlets.
We recommend to design the heating
system in such a way that when making
repairs, it will be possibly to drain the
boiler only.
After reconstructions, in unfavourable
building dispositions, etc., it is possible to
connect the boiler to the heating system,
the hot water system as well as the gas
mains by means of flexible hoses, but only
those designed for this purpose. Flexible
components should be as short as possi-
ble, must be protected against mechani-
cal and chemical loads and damage, and
must be replaced with new ones before
the end of their useful life or before their
reliability to meet their nominal parame-
ters (as stated by their manufacturers) is
diminished.
Operating pressure in the heating
system
The heating system (measured on the
boiler) must be filled in at least to the
hydraulic pressure of 1 bar (corresponds
to the hydrostatic water column of 10 m).
We recommend to maintain the pressure
within the range 1.2 – 2 bar. The expansi-
on vessel capacity is sufficient for up to 70
l of heating water in the heating system (at
temperature 85˚C).
Expansion vessel
Before filling up the heating system, check
pressure in the expansion vessel. The ini-
tial pressure inside the expansion vessel
should be by 0.2 bar higher than the assu-
med pressure in the heating system.
If the heating system is already filled up,
it is necessary to shut the heating water
valves located underneath the boiler and,
using the draining valve, relieve the boiler
from pressure. Then you can check the
expansion vessel pressure and if neces-
sary increase the pressure.
Mounting the boiler
fig. 13
Supplied By www.heating spares.co Tel. 0161 620 6677
26 27
Important:
Make sure that the expansion
vessel capacity is sufficient for the volume
of water in the heating system (see instal-
lation design documentation).
Safety valve
At the bottom of the boiler among the hyd-
raulic group is on the right side located a
safety valve (Fig. 14). When the maximum
pressure in the system is exceeded, wa-
ter or steam can be discharged from the
safety valve, therefore we recommend to
attach a hose to the safety valve, dischar-
ging the water into the building’s water
waste system.
Important:
Under no circumstances may
anyone manipulate with the safety valve
while the boiler is in operation.
Connecting gas supply
The ZP (natural gas) version of the
PROTHERM 24 (12) KTO and 24 (12)
KOO boilers is designed to be fuelled by
natural gas of nominal pressure in the gas
mains 2 kPa, for which the calorific value is
most commonly stated as being between
9 and 10 kWh/cu.m. The indoor gas distri-
bution pipes and the gas meter must be
sized adequately, taking into account also
the user’s other gas appliances.
All gas distribution pipes must be installed
in accordance with ČSN EN 1775.
If your boiler is fuelled by propane gas
and the gas supply piping is installed
below the terrain level, the space around
the connection point must be sufficiently
ventilated or equipped with a valve which
shuts off the section below the terrain le-
vel when the boiler flame is off. The valve
must also shut when the ventilation fails,
i.e. when the forced ventilation system
fails or when natural ventilation is moni-
tored by a detector (when the detector
sends a warning signal).
Important:
The boiler’s gas connection
point is a 3/4” gas valve coupling with a
technological flattening. This technolo-
gical flattening prevents the thread from
being sealed in a conventional way by
a pipe union and sealers such as for in-
stance “combing”, Teflon, paste, etc. The
coupling must be sealed by merely tighte-
ning the cap nut on the coupling end over
an appropriate 24×15×2 flat sealing ring.
After completing the gas supply connecti-
on to the boiler, the coupling must be
checked for potential leaks.
fig. 14
Safety valve
Filling up the heating system with
water
Important:
If the pressure in water mains
is lower or equal to the pressure of the wa-
ter inside the heating system, the heating
water may run into the water mains, which
is forbidden. To avoid this, install a non-re-
turn valve downstream the top-up valve.
• Make sure that the boiler gas stop valve
is closed.
• Unscrew the automatic bleeding valve
cap situated on the pump.
• Check and adjust the expansion vessel
pressure according to the prescribed
static pressure in the system.
• Connect the boiler to power supply.
• Turn the main switch (Fig. 1) to the ON
(I) position; about 20 seconds after tur-
ning the switch to the ON position, the
boiler will shut down, error code F0 will
appear on the control panel display and
the LED underneath the symbol will
start flashing.
• Display orientation values of the heating
water system pressure by pressing the
MODE button once (see the Pressure dis-
play mode on page 5.
• Open the heating system top-up valve
and at the same time watch on the dis-
play the boiler pressure rising.
• Fill up the system with water, the pressu-
re should be within the range 1.2 – 2
bar.
• Bleed all radiators carefully (water must
run smoothly without any air bubbles).
• Leave the automatic bleeding valve cap
unscrewed (even while the boiler is run-
ning).
• Make sure that the pressure shown on
the display is within the range 1.2 – 2
bar. If necessary pressure the system
up.
• Open hot water taps to bleed the hot
water circuit.
Important:
If the pressure inside the bo-
iler is not at least 0.6 bar, the boiler will
not start up. If while the boiler is running
the pressure inside the boiler drops below
0.6 bar, the protection system will shut
the boiler down and the error code F0 will
appear on the display. If the pressure indi-
cator LED is flashing, it means that water
pressure inside the boiler has dropped
below the optimum value, and the pressu-
re inside the heating water system must
be adjusted.
Draining water from the boiler
The draining valve’s main function is to
relieve water pressure in the boiler during
repairs (Fig. 15). Water from the boiler can
be drained using this valve only partially.
Complete draining of water either from
the boiler only or from the whole heating
system and refilling it again must be done
through a fill-up (discharge) point situated
in a suitable location in the heating sys-
tem.
Draining and filling up heating system
water and the follow-up operations (blee-
ding, adjusting expansion vessel) are not
covered by the boiler’s warranty.
If there is a danger that the hot water
system water inside the boiler or the
distribution pipes may freeze, measures
must be implemented to prevent this from
happening.
fig. 15
Draining valve
Supplied By www.heating spares.co Tel. 0161 620 6677
28 29
fig. 17
In the KTO models, combustion gases
must always be removed and air supplied
through a dual ducting specially designed
for this purpose.
Horizontal ducting sections must have
a gradient allowing condensate to be
discharged to the outside space or to
condensate removal components. This
is achieved by combining elbows with
straight components which will result in a
gentle slope of the straight section. Ver-
tical sections must be always fitted with
condensate removal components. These
must be whenever possible installed in
an immediate vicinity of the boiler’s com-
bustion gases discharge outlet. Defects
caused by condensate penetrations are
not covered by the boiler’s warranty.
Air supply/combustion gases
removal methods (according to ČSN
EN 483) and permitted ducting route
lengths
Unless stated for the following dual du-
cting route design methods and their
termination outlets otherwise, the ducting
route lengths (from the boiler connection
point to the termination outlet) must be as
specified in Table 1 below.
Note:
As 1 Em is regarded either 1 m of
straight section or one 90˚ elbow.
Important:
When the lengths specified
in Table 1 are exceeded, it is necessary
to remove the combustion gases diffuser
(aperture) from the fan outlet (Fig. 16).
The following methods of air supply and
combustion gases removal are permitted
for this boiler:
Method C12 – horizontal routes with ho-
rizontal termination outlets discharging
combustion gases to free space.
When using separate ducting (80 mm) in
horizontal routes with horizontal termina-
tion outlets, the air supply inlet and the
combustion gasses outlet from the same
boiler must be situated inside a square of
a 0.5 m side.
An example of a dual horizontal ducting
route – method C12 (according to ČSN EN
483) is illustrated by Fig. 17.
Method C32 – vertical routes with vertical
termination outlets into free space. For
termination outlet of separate ducting,
the same applies as for method C12. An
example of a dual vertical ducting route
– method C32 (according to ČSN EN 483)
is illustrated by Fig. 18.
fig. 16
Air supply and combustion gases removal system (KTO)
Combustion gases diffuser
Method C
12
Method C42 – connection to common dual
chimneys. Dual ducting from each boiler
(individual routes) may be terminated in
a common chimney; the chimney’s trans-
portation sufficiency is assessed from
the data stated by the manufacturer of
the used chimney flue. If the routes are
terminated in the chimney in two mutually
perpendicular directions, the minimum
vertical distance between them must be
0.45 m. If the routes are terminated in
the chimney from opposite directions,
Flue diameter min. length max. length with
aperture
max. length
without aperture
100 / 60 1,5 Em 3 Em 9 (5) Em
80 / 80 2 x 2 Em 2 x 3 Em 2 x 9 Em
the minimum vertical distance between
them must be 0.60 m. Outlets of routes
terminated in a common dual chimney are
never fitted with end pieces (used in rou-
tes discharging to free space). Both route
sections (the outside – air, and the inside
– combustion gases) must be safely in-
serted into the chimney inlet, but not too
deep, so that it does not form an obstacle
to the flowing combustion gases or air.
In this case a concentric ducting route
must not exceed the length of 9 Em and a
separate ducting route the sum of the air
part and the combustion gases part must
not exceed 18 Em.
Method C52 – dual ducting separated and
terminated at two different points (with dif-
ferent parameters, mainly pressures).
Separate ducting can also be used to
remove combustion gases and supply
combustion air (see Fig. 19).The separate
ducting routes must not be terminated at
mutually opposite building walls.
Method C82 – ducting with the air part ter-
minated in free space and the combustion
gases part in a common chimney.
Air may also be taken from free space
(or a space with plentiful air supply) and
combustion gases discharged into a com-
mon chimney (or back into a space with
common presence of combustion gases).
Into this method falls also the special case
described in the second paragraph of se-
ction Special cases – see below.
fig. 18
fig. 19
Table 1
Method C
32
Method C
52
Supplied By www.heating spares.co Tel. 0161 620 6677
30 31
Termination of horizontal ducting
sections on the building’s façade
Terminating horizontal sections on the
building’s façade is a method which
should be used only when there is no
other way. Ducting routes may be termi-
nated using the rules described in this
Operation and Installation Guide (or in
a separate Protherm flue catalogue), or
other rules can be applied, e.g. TPG 800
01 of GAS s.r.o.
• 2 m above terrain level in publicly acces-
sible places (0.4 m in other places).
• 0.5 m from window sides, permanently
opened ventilation openings (grills) or
doors.
• Above the top edge of windows, ventila-
tion grills or doors.
• 1 m underneath windows (never under
ventilation grills!)
• in depth R under overhangs, balconies
and roof edges.
Minimum distance between façade out-
lets:
• horizontal: 1 m
• vertical: 2 m
Outlets must be always directed in such
a way that the discharged combustion
gases flow away from the façade into free
space (particularly away from windows,
ventilation grills, doors). If this is not
possible, the following minimum horizon-
tal distances must be maintained:
a) façade-to-façade (i.e. between the
outside edge of the outlet cage and the
opposite façade) (Fig. 22):
2 m – if the opposite façade has no win-
dows or ventilation grills
1 m – if neither façade has any windows
or ventilation grills
4 m – if the opposite façade has windows
or ventilation grills (or when it has similar
outlets)
b) on adjacent façades (corners), with
distance between the outlet axis and a
façades parallel to this axis at least:
2 m – if the adjacent façade has windows,
windows, ventilation grills or doors
0.5 m – if the adjacent façade has no win-
dows, ventilation grills or doors
Corners smaller than 0.5 m are not taken
into account.
All the above distances are measured
from the outside edge (frame) of windows,
ventilation grills and doors, to the ducting
centreline.
Special cases
Outlets may also be situated under over-
hangs, provided the ducting is extended
so that its horizontal length measured
from the façade at least touches a circle of
radius “R” circumscribed from the corner
formed by the overhang and the façade
(Fig. 20).
Boiler exhaust ducting may be also ter-
minated in vertical shafts terminated into
free space, provided the shaft cross se-
ction along its entire length including the
open top is at least 1.25 sq.m. The shaft
must not have any other similar outlets or
windows, or ventilation grills.
Vertical outlet (above roof)
Concentric ducting routes as well as se-
parate combustion gases and air supply
ducting may be terminated above the
building’s roof at 0.4 m distances from
each other and extending above the top of
a 40 cm thick layer of snow (copying the
roof outlines).
Permissible exhaust outlet locations
fig. 20 - Overhangs
fig. 21- Facades
fig. 22 - Corners
Supplied By www.heating spares.co Tel. 0161 620 6677
32 33
The boiler is connected to power supply by
a three-core flexible cord without a plug. A
fixed socket through which the boiler is
connected to power mains must comply
with the provisions of ČSN 33 2000-4-46.
It must always have a protective (earth)
contact (peg), reliably connected by a
PE or PEN wire (yellow-and-green). The
boiler must be always connected to the
protection wire (earth) through its power
cord and must be always installed in such
a way that the socket and plug are acces-
sible. Using adapters, extension cords
etc., is not permitted.
The boiler has two tubular fuses (T 80 mA/
250 V and 1.6 mA/250 V), situated on the
boiler’s control panel – see the schematic
diagrams on pages 35 and 36.
Important:
The plug and the socket as
well as a room control unit, which requires
interfering with the boiler’s internal wiring,
must be always connected by a qualified
electrician as defined by Public Notice No.
50/1978. Likewise servicing of the boiler’s
electrical system must be done by a per-
son with the above qualification only. Befo-
re carrying out any works on its electrical
system, the boiler must be disconnected
from power supply by pulling the power
cord plug from the power socket!
Only zero-potential output room control
units may be used with the boiler, i.e.
units which send no foreign voltage to
the boiler.
Minimum required current carrying capa-
city of the control unit’s output terminals is
24 VAC/0.1 A.
The room control unit must be connected
to the boiler by a two-core cable. The re-
commended copper wire cross-section is
0.5 to 1.5 sq.mm.
The room control unit connection cable
must not run in parallel with power wires
or cables.
The outdoor sensor is connected by a
two-core cable of a cross-section of 0.75
sq.mm. Maximal ohmic resistance of the
connection is 10 ohms and a length shall
not exceed 30m. The terminal box for
wiring the outdoor sensor and the room
Electrical wiring
control unit is located at the bottom of the
boiler.
The terminal box is accessible after re-
moving the external cover and dropping
down the control panel (Fig. 23).
Important:
The outdoor sensor connecti-
on wires and room control unit must not
run together with power distribution.
fig. 23
Room control unit wiring
The Panther boiler is assumed to be used
predominantly with Protherm B60Z hot
water tank, for which interconnecting sets
are available, tailored always for specific
combination of the boiler and this tank.
The tank is wall mounted - on the left
(right) from the boiler or directly under
the boiler.
The boiler may be combined with other
models of PROTHERM tanks (B 100 MS,
B 100 Z, B 200 Z, etc.). In this cases, set
B100M-24KXO15 must be used, distin-
guished by absence of interconnecting
hoses and of a cover sheltering all con-
nection.
A detail set of instructions, which is a
part of delivery of every interconnecting
set, make installation of sets with B60Z
easier.
An installation of set (boiler and tank) re-
quires constructional preparedness. This
includes namely projecting and marking
of all connections (hot and heating water,
gas).
Connection of boiler to hot water tank
Safety measures
The distance between any flammable
material and the combustion gases part
of a separate ducting system must be
such that the surface temperature of this
material does not exceed 80˚C.
Combustion gases outlets must not be
located in:
• places with the danger of explosion (as
defined by ČSN 33 2320)
• building’s interior (attics, corridors, stair-
cases, etc.)
• places which can be closed, e.g. in gate-
way passages, etc.)
• underground structures (even when they
constitute no obstacle and are open),
such as tunnels, subways, etc.
Positioning of independent inlet (suction)
of air supply shall be assessed similarly to
these regulation.
The opening through the wall for dual du-
cting for air supply and flue removal shall
be made with adequate clearance (ca 120
to 130 mm) and sealed upon completion
of installation. Only incombustible material
may be used for sealing (with flammability
grade A according to ČSN 73 0823) as
e.g. plaster, gypsum etc. Penetrations
through flammable wall or ceiling must be
made in accordance with the first paragra-
ph of this section.
Supplied By www.heating spares.co Tel. 0161 620 6677
34 35
Connecting of 3-way valve
fig. 24
Electrical wiring diagram PROTHERM Panther 24 (12) KOO
fig. 25
Installation procedure:
1 Attach 3-way valve with actuator to hea-
ting water outlet using screw cap. The
actuator must face forward. (Not to
wall).
2 Attach distribution T-piece to heating
water inlet into the boiler.
3 Connect pipe leading heating water into
the tank to the outlet of 3-way valve,
which is closer to actuator.
4 Connect pipe leading heating water into
the heating system to other outlet (fur-
ther from actuator).
5 Connect outlet of heating water coming
from the tank and return pipe from hea-
ting system to distribution T-piece.
6 Plug the larger connector of intercon-
necting cable to the actuator of 3-way
valve. Plug the other connector into the
boiler control panel, position XT8.
7 Plug a temperature sensor into the tank
sump. The lengths of insertion: 450 mm
for B60Z under the boiler, 300 mm for
B60Z next to the boiler, 430 mm for
B100MS. Always fix the sensor wire with
attached clamp.
8 Plug the other connector of the tempera-
ture sensor into the boiler control panel,
position XT3.
9 Cover the actuator of 3-way valve with
protective hood, which is attached to the
bottom cover of boiler.
Heating water stop valves, filter and other
elements shall be located outside the
set, if handling these elements is difficult.
Interconnecting set for B60Z tanks may
not be combined with connecting set. If
interconnecting hoses from B60Z tank
sets are not used, the same material and
joint type must be used, as in the heating
water reticulation.
If different PROTHERM tank is used, re-
move capillary of the original thermostat
and insert temperature sensor from the
set into the same sump and in the same
length.
The Panther 24 (12) KTO and 24 (12)
KOO boilers are in their basic versions
designed to use natural gas as fuel. If it
is necessary to use propane gas instead,
the gas valve must be replaced and the
boiler parameters set as specified. The
modifications required to switch to a
different fuel must be carried out by an
authorised technician with a valid manu-
facturer’s certificate.
Converting to different fuel
The propane gas valve is part of the
conversion kit for switching from natural
gas to propane gas. The kit contains all
necessary parts and instructions how to
do the conversion.
Technical instructions for converting to a
different fuel form a separate part of the
Service Manual.
Supplied By www.heating spares.co Tel. 0161 620 6677
36 37
Electrical wiring diagram PROTHERM Panther 24 (12) KTO
fig. 26
Supplied By www.heating spares.co Tel. 0161 620 6677
Protherm spol. s r.o.
Jurkovičova 45
909 01 Skalica
Tel.: 034 6966 101
fax: 034 6966 111
www.protherm.sk
Operation and
Installation Guide
24 (12) KTO - v.17
24 (12) KOO - v.17
Wall - hung boiler
Output 9,5 (3,5) - 23 (11,5) kW
Equithermal control
Panther
7855 - v.1 9/2004

Other Protherm Boiler manuals

Protherm 23 BTVE Manual

Protherm

Protherm 23 BTVE Manual

Protherm 80E User guide

Protherm

Protherm 80E User guide

Protherm Panther 30 KTV User manual

Protherm

Protherm Panther 30 KTV User manual

Protherm Lion 24 KKV Quick start guide

Protherm

Protherm Lion 24 KKV Quick start guide

Protherm Panther Condens 12 KKO Installation guide

Protherm

Protherm Panther Condens 12 KKO Installation guide

Protherm Provitherm 28 KTV Manual

Protherm

Protherm Provitherm 28 KTV Manual

Protherm Leopard 24 BTV Operating instructions

Protherm

Protherm Leopard 24 BTV Operating instructions

Protherm 80EC Manual

Protherm

Protherm 80EC Manual

Protherm 80E Manual

Protherm

Protherm 80E Manual

Protherm 40 Operating manual

Protherm

Protherm 40 Operating manual

Protherm Gepard User manual

Protherm

Protherm Gepard User manual

Protherm 60 User manual

Protherm

Protherm 60 User manual

Protherm Gepard 23 MOV v.19 User manual

Protherm

Protherm Gepard 23 MOV v.19 User manual

Protherm Ray User manual

Protherm

Protherm Ray User manual

Protherm 100 User manual

Protherm

Protherm 100 User manual

Protherm 20/26 KKV-CS/1 User manual

Protherm

Protherm 20/26 KKV-CS/1 User manual

Protherm 100EC Manual

Protherm

Protherm 100EC Manual

Protherm Gepard Series Installation guide

Protherm

Protherm Gepard Series Installation guide

Protherm Tiger 24 (12) KTZ User manual

Protherm

Protherm Tiger 24 (12) KTZ User manual

Protherm 65 User manual

Protherm

Protherm 65 User manual

Protherm Bear 20 KLZ Quick start guide

Protherm

Protherm Bear 20 KLZ Quick start guide

Protherm Leopard 24 BOV Operating instructions

Protherm

Protherm Leopard 24 BOV Operating instructions

Protherm Ray 6 KE /14 EU User manual

Protherm

Protherm Ray 6 KE /14 EU User manual

Protherm 20 KLO Operation manual

Protherm

Protherm 20 KLO Operation manual

Popular Boiler manuals by other brands

NBE RTB manual

NBE

NBE RTB manual

Hendi 211403 user manual

Hendi

Hendi 211403 user manual

Laars Mighty Therm AP Installation and operation instructions

Laars

Laars Mighty Therm AP Installation and operation instructions

Cordivari Bolly1 ST user manual

Cordivari

Cordivari Bolly1 ST user manual

Sime AQUA INOX EV 25 User, installation and servicing instructions

Sime

Sime AQUA INOX EV 25 User, installation and servicing instructions

Potthof & Co Potterton Gold Combi 24 HE A Installation & service instructions

Potthof & Co

Potthof & Co Potterton Gold Combi 24 HE A Installation & service instructions

A.O. Smith Epsilon EB-40 user manual

A.O. Smith

A.O. Smith Epsilon EB-40 user manual

Excel HE C24 user guide

Excel

Excel HE C24 user guide

THERMOSTAHL MULTIPLEX MCL instruction manual

THERMOSTAHL

THERMOSTAHL MULTIPLEX MCL instruction manual

Worcester GREENSTAR 24i junior instruction manual

Worcester

Worcester GREENSTAR 24i junior instruction manual

Unical Osa S 24 Installation and Servicing Manual

Unical

Unical Osa S 24 Installation and Servicing Manual

Riello Tregi NK Series INSTALLATION, USER-OPERATION, MAINTENANCE AND SYSTEM MANAGEMENT MANUAL

Riello

Riello Tregi NK Series INSTALLATION, USER-OPERATION, MAINTENANCE AND SYSTEM MANAGEMENT MANUAL

Heatrae Sadia Amptec Installation instructions and user guide

Heatrae Sadia

Heatrae Sadia Amptec Installation instructions and user guide

Bryan Boilers BE-210-W4T7 specification

Bryan Boilers

Bryan Boilers BE-210-W4T7 specification

Bosch Worcester Greenstar Danesmoor 12/18 Installation, commissioning and servicing instruction manual

Bosch

Bosch Worcester Greenstar Danesmoor 12/18 Installation, commissioning and servicing instruction manual

Sime MERIDIAN HE 25 Installation and servicing instruction

Sime

Sime MERIDIAN HE 25 Installation and servicing instruction

Super Hot MG series Installation and service manual

Super Hot

Super Hot MG series Installation and service manual

Slant/Fin VICTORY II VHS Series Brochure & specs

Slant/Fin

Slant/Fin VICTORY II VHS Series Brochure & specs

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.