Pulsar DC/DC50HV User manual

1
DC/DC50HV
v.1.0
DC/DC 5A HV Step down DC/DC converter
with adjustable output voltage
EN**
Edition: 1 from 26.08.2015
Supercedes the edition: --------
The module’s features:
Step down DC/DC converter with adjustable output voltage
Example of use: step down from 48V to 12V DC
The input voltage range: 28÷60V DC
The output voltage range: 12÷24V DC
The maximum load current 5A (60W)
The PSU technical output indicating converter failure
triggered by:
Short-circuit of the output
Output overload
Protections:
Short-circuit protection SCP
Overload protection OLP
High efficiency: 92%
Optical LED indication
Warranty –2 years from the production date
Mounting:
Mounting strip with adhesive tape
Mounting screws
Schematic diagram of the converter operation.
Adjustment of the converter output voltage: 12V÷24V DC, 5A max.
1. Technical description
The step down converter DC/DC 5A (DC/DC50HV) is used for step down the input voltage from the range between 28V÷60V
DC to the voltage range of 12V÷24V DC at the output, adjusted with the VADJ potentiometer. The maximum load current is Imax=5A
(Pmax=60W). The module does not feature galvanic isolation between input/output (IN-AUX) and operates on common "ground" (0V)
potential (IN- and AUX- terminals are galvanically connected = common terminal).
1.1. Block diagram (Fig.1).
Fig.1. Block diagram of the converter’s module.

2
1.2. Description of components and connectors (Fig. 2, Table 1, Table 2).
Table 1.
No.
[fig.2]
Component’s description
[1]
IN LED light - red
[2]
Power connector of the DC/DC module
[3]
V ADJ voltage adjustment (12÷24V)
[4]
Jumper –voltage adjustment
[5]
AUX LED light –green
[6]
The DC/DC module’s connector (power supply and PSU)
[7]
PSU LED light –red
[8]
Mounting strip
Table 2.
[2], [6]
Description of module’s connectors
+IN
- IN
DC supply input
28V÷60V DC
+AUX
- AUX
DC supply output
(+AUX= +U, -AUX=GND)
PSU
Technical output of failure: OLP/SCP activation (short-circuit or overload protection)
Failure status: hi-Z (high impedance), normal status: L (0V, GND)
Fig.2. The converter module’s view.
1.3. Technical parameters:
- Electrical parameters (Table 3)
- Mechanical parameters (Table 4)
Table 3.
The input voltage range (power supply)
28V÷60V DC
The output voltage range
12V÷15V, 15V÷24V
Jumper adjustable.
Factory setting: 12V.
P module power
60W max. (see fig.3)
Energy efficiency
85%÷ 92%
Ripple voltage
80mV p-p
Output current
5A max. (See fig.3)
Current consumption by module systems
20 mA max.
Short-circuit protection SCP
electronic, automatic recovery
Overload protection OLP
110-150% of the module’s power, manual restart (the failure
requires disconnection of the DC output circuit)
Technical outputs
- PSU output indicating failure –overload or short-
circuit in the AUX output
- OC type, 50mA max. Failure status: hi-Z state (high
impedance), normal status: L level (0V)
Optical indication
- IN LED indicating DC power status
- AUX LED indicating DC supply status at the output
- PSU LED indicating failure - overload or short-
circuit in the AUX output
- red, normal status: is lit continuously
- green, normal status: is lit continuously
- red, normal status: does not lit, failure: is lit continuously
Operating conditions
II environmental class, -10°C ÷40°C, ensure air flow around
the unit for convection cooling
Declarations, Warranties
CE, 2 years from the production date

3
Table 4.
Dimensions
140 x 43 x 45 (LxWxH)
Mounting
tape or mounting screw x 2
Terminals
Ф0,41÷1,63 (AWG 26-14)
Net/gross weight
0,15/0,20 kg
2. Installation.
2.1. Requirements.
The DC/DC converter is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and required
for a given country) for step down installations. The module should be mounted in confined spaces with normal relative humidity
(RH=90% maximum, no condensation) and temperature range from -10°C up to +40°C. The module should operate in vertical position
in order to provide free and convectional air flow.
Proper operation of the module requires adequate current capacity of the power source; the power supply capacity should be
calculated using the formula below: PIN = 1,15 x PAUX
(PIN = 1,15 x IAUX x UAUX)
Example:
The converter will supply the receivers with a capacity of PAUX = 48W drawing a total current of IAUX = 4A at the voltage
UAUX = 12V. The minimum power supply capacity must therefore amount to: PIN = 1,15 x 4A x 12V = 55,2W.
The device should be mounted in a metal enclosure (cabinet). The rules for power supply, enclosures and shielding - according to
application - must be observed in order to meet the requirements of LVD and EMC directives.
2.2. Installation procedure.
1. Mount the enclosure (cabinet, etc.) and lead cables through cable glands.
2. Mount the DC/DC converter with adhesive tape or mounting screws.
3. Supply DC voltage to the + IN, -IN terminals with correct polarization.
4. Switch on the DC voltage.
5. Use the jumper to set the required voltage range and adjust the required output voltage with the V ADJ potentiometer. Default setting:
12V.
6. Switch off the DC voltage.
7. Connect the receivers’ cables to the +AUX, -AUX connectors of the terminal block on the module’s board.
8. Connect the device cables (alarm control panel, indicator, LED light, etc.) to the PSU technical output if necessary.
9. Switch on the DC voltage (the red IN LED should be permanently illuminated, the AUX green LED should be permanently
illuminated).
10. Once the tests and operation control are performed, close the enclosure, cabinet, etc.
3. Converter 's module operation indication.
3.1. Technical output.
The converter is equipped with three diodes indicating operation status: IN, AUX, and PSU.
IN- red LED: during normal status (DC power supply) it is lit continuously. No DC supply is indicated by switching off the IN LED.
AUX- green LED: indicates DC supply status at the module’s output. During normal status, it is lit continuously, in case of short
circuit or overload the AUX led is off.
PSU- red LED: indicates module’s overload. During normal status, it is off, in case of short circuit or overload the LED lights
continuously.
3.2. Technical output.
The converter is fitted with one technical output indicating failure of the DC / DC module.
PSU- OLP/SCP (overload/short-circuit) output: - OC type output indicating overload/short-circuit of the module’s output.
During normal operation, the output is shorted to the AUX - (0V). In case of failure, the module disconnects the output and it is in the hi-
Z (high impedance) state during failure.
4. Maintenance and operation.
4.1. Converter overload.
The AUX output is protected with the PTC polymer fuse. If the load current exceeds Imax (110% ÷ 150% @ 25ºC of the
converter capacity), the output voltage will be automatically disconnected, which will be signaled by switching off the green AUX LED,
switching on the red PSU LED and a change in the status of the technical output. Voltage restoration requires disconnecting the output
load for approx. 1 min.
The module's load balance should be
done prior to installation. During normal
operation, the total current of the receivers should
not exceed I=5Awhile the power drawn from the
module should not exceed Pmax=60W, as shown
in the Fig. 3.
Fig.3. The maximum output current
depending on the output voltage.

4
5. Maintenance.
All maintenance procedures can be performed after disconnecting the converter from the power network. The converter does
not require any specific maintenance; however, its interior should be cleaned with compressed air if used in dusty conditions.
WEEE LABEL
Waste electrical and electronic equipment must not be disposed of with normal household waste.
According to the European Union WEEE Directive, waste electrical and electronic equipment should
be disposed of separately from normal household waste.
GENERAL WARRANTY CONDITIONS
1. Pulsar (manufacturer) grants a two-years quality warranty for the equipment, starting from the production date.
2. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (selected by the manufacturer) if the
malfunction is due to the manufacturer. It includes manufacturing or material defects, provided that such defects have been
reported within the warranty period (point.1).
3. The equipment subjected to warranty should be brought to the place of purchase or directly to the main office of the
manufacturer.
4. The warranty applies to complete equipment, accompanied by a properly filled warranty claim with a description of the defect.
5. Should the claim be accepted, the manufacturer is obliged to provide warranty repairs, at the earliest convenience, however not
later that within 14 days from the delivery to the service centre of the manufacturer.
6. The repair period mentioned in point 5 may be prolonged, if there are no technical possibilities to carry out the repairs, or if the
equipment has been conditionally accepted, due to the breaking warranty terms by the claimant.
7. All the services are carried out at the service centre of the manufacturer, exclusively.
8. The warranty does not cover the defects of the equipment, resulting from:
- reasons beyond the manufacturer's control,
- mechanical damage,
- improper storage and transport,
- use that violates the operation manual or equipment’s intended use
- fortuitous events, including lightning discharges, power failures, fire, flood, high temperatures and chemical agents,
- improper installation and configuration (failure to follow instruction).
9. The warranty is void in case of construction changes and repairs carried out by any unauthorized service center or in case of
damage or modifications to warranty stickers and serial numbers.
10. The liability of the manufacturer towards the buyer is limited to the value of the equipment determined according to the
wholesale prices suggested by the manufacturer on the day of purchase.
11. The manufacturer takes no responsibility for the defects that result from the damaging, malfunctioning or inability to operate
the equipment especially when resulting from failure to comply with the recommendations and requirements contained in the
manual.
Pulsar
Siedlec 150, 32-744 Łapczyca, Poland
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
http:// www.pulsar.pl, www.zasilacze.pl
Table of contents
Other Pulsar Media Converter manuals

Pulsar
Pulsar HDMI-VGA User manual

Pulsar
Pulsar DCDC10 User manual

Pulsar
Pulsar DC/DC52230 User manual

Pulsar
Pulsar DC/DC50SD User manual

Pulsar
Pulsar DC/DC25SU User manual

Pulsar
Pulsar DC/DC50SE-SEP User manual

Pulsar
Pulsar DC/DC20SD User manual

Pulsar
Pulsar DC/DC30HV User manual

Pulsar
Pulsar DC/DC20SD User manual

Pulsar
Pulsar DCDC15H User manual
Popular Media Converter manuals by other brands

Yamaha
Yamaha AD808 Operation manual

PVI
PVI VEPLAYER Pro Series user manual

Hengstler
Hengstler AC 58 Interbus installation instructions

True blue power
True blue power TC2000 Series Installation manual and operating instructions

prophecy
prophecy GoFanco PRO-MSTDP2HD user guide

e+p Elektrik Handels
e+p Elektrik Handels HDK 22 instruction manual