1
PS-20012140
PS 12V/14A enclosed switch mode power supply
Edition: 3 from 04.02.2013
Supersedes edition: 2 from 25.05.2012 EN
Features of the power supply unit:
•power output 14A/12÷15VDC
•wide AC input voltage range 176÷264V
•high efficiency 85%
•LED optical signalisation
•protections:
•SCP short-circuit protection
•overvoltage OVP
•overvoltage protection
•overload (OLP)
•warranty – 3 year from the production date
1. Technical description.
1.1.General description.
The power supply unit is intended for the feeding of alarm system equipments, which require 12V DC supply
voltage and current load I=14A. The design enables simple changing of the output voltage, within the range of 12V÷15V
DC, using a potentiometer. The power supply unit is protected against short-circuit, overload and overvoltage.
1.2.Technical parameters.
Supply voltage 176 ÷ 264 V AC 50÷60Hz
Current consumption 1,36A@230VAC max.
Supply power 200W max.
Efficiency 85%
Output voltage 12V DC
Output current 14A
Output current t
AMB
<30°C 14A - see graph 1.
Output current t
AMB
=40°C 10A - see graph 1.
Voltage adjustment range 12 V ÷ 15V DC
Ripple voltage 100mV p-p max.
Short-circuit protection SCP electronic, automatic recovery
Overload protection OLP 105-150% of power supply, automatic recovery
Surge protection varistors
Overvoltage protection OVP >16V (automatic return)
Optical signalisation green LED – presence of DC voltage
Operation conditions 2-nd enviromental class, temperature: -10
o
C÷40
o
C
relative humidity 20%...90%, without condensation
Dimensions (LxWxH) 226 x 115 x 50 [mm]
Net/gross weight 0,82kg / 0,90kg
Protection class PN-EN 60950-1:2007 I (first) – requires a protective conductor (PE)
Connectors power-supply:Φ0,63-2,50 (AWG 22-10)
outputs : Φ0,63-2,50 (AWG 22-10)
Electrical strength of insulation:
- between input (network) circuit and output
circuits of power-supply (I/PO/P)
- between input circuit and PE protection circuit
(I/P-FG)
- between output circuit and PE protection circuit
(O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection
circuit
100 MΩ, 500V/DC
Storage temperature -20ºC...+60ºC
Vibrations and impulse waves during transport according to PN-83/T-42106