www.pulsar.pl Seria SWBH
1.4. Equipment parameters:
- specifications (Tab. 2)
- operation safety (Tab. 3)
- operating parameters (Tab. 4)
Table 2. Specifications.
~ 200 –240 V; 0,7 A; 50/60 Hz
Battery circuit protection SCP and reverse
polarity connection
Deep discharge battery protection UVP
U<9,5 V (± 5%) – disconnection of battery circuit
Overload protection (OLP)
105 –150% PSU power, automatically recovered
Current consumption (durring buffer operation)
Power input: Φ0,63-2,50 (AWG 22-10)
PoE power supply output: DC 2,1/5,5 plug
BAT output: Battery wires 6,3F –45cm
W=240, H=308, D=130 [+/- 2mm]
W=85, H=160, D=105 [+/- 2mm]
Number of cable glands / cable diameter:
2 pc. / 13 - 18 mm + 1 pc. / 10 - 14 mm
2x Ф5mm; 3x Ф5mm (2pcs in each.)
Mounting screws (x5), DC wires, Gland filling inserts
Table 3. Operation safety.
Protection class EN 62368-1
Protection grade EN 60529
Electrical strength of insulation:
- between input and output circuits of the PSU
- between input circuit and protection circuit
- between output circuit and protection circuit
4000 V DC min.
2500 V DC min.
500 V DC min.
Insulation resistance:
- between input circuit and output or protection circuit
Table 4. Operating parameters.
20%...90%, without condensation
Vibrations during operation
Impulse waves during operation
Vibrations and impulse waves during transport
According to PN-83/T-42106
2. Installation.
2.1 Requirements.
Device is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and required
for a given country) with ~230 V mains supply. Unit should be mounted in confined spaces with normal relative humidity
(RH=90% maximum, without condensing) and temperature from -10°C to +40°C. Device must be mounted in a vertical
position with cable glands facing downwards. Mounting in any other position is not permitted. Ensure free convective
airflow around enclosure.
As power supply is designed for a continuous operation and is not equipped with a power-switch, therefore, an
appropriate overload protection in power supply circuit should be provided. Moreover, the user shall be informed about
the method of unplugging (most frequently through separating and assigning an appropriate fuse in the fuse-box).
The electrical system shall follow valid standards and regulations.