
OPERATION AND MAINTENANCE MANUAL
PAGE # 9
PF-63 Series Separator (ver. 7_10)
OPERATION AND MAINTENANCE MANUAL
3a. (Closed circuit or pressurized system) Run an effluent line from the separator return
labeled "OUTLET" back to the system piping (low pressure side).
NOTE:
The effluent line should be piped to the suction side of the process system pump. A flow
control or throttling device is recommended in the effluent line (separator return) to regulate
flow through the separator. A service valve and flange/union should be installed in this line
near the separator.
3b. (Open system or sump) Run an effluent line from the separator return labeled "OUTLET"
back to the system sump on the opposing side of the suction (influent) line.
NOTE:
If the system dynamics dictate a lower or higher discharge pressure, the pump & motor may
require a change to match the actual system dynamics. A flow control or throttling device
could also be installed in the effluent line to regulate flow through the separator.
A service valve and flange/union should be installed in this line near the separator.
TABLE III - SIZE & CONNECTION
MODEL PF-63 INLET(INCHES) OUTLET (INCHES)
PF-63-012 2 (FLNG) 1-1/4 (MPT)
PF-63-015 2 (FLNG) 1-1/2 (MPT)
PF-63-020 3 (FLNG) 2 (MPT)
PF-63-025 3 (FLNG) 2-1/2 (MPT)
PF-63-030 3 (FLNG) 3 (FLNG)
PF-63-040A 4 (FLNG) 4 (FLNG)
PF-63-040B 4 (FLNG) 4 (FLNG)
PF-63-050 6 (FLNG) 5 (FLNG)
PF-63-060A 6 (FLNG) 6 (FLNG)
PF-63-060B 8 (FLNG) 6 (FLNG)
NOTE:
It is important that all piping and components associated with the filter system installation
must be supported to eliminate stress on the filter and piping.
Always follow local, county, state or other government agency requirements for piping
hook-ups.