Pylontech PowerCube-M1 User manual

Lithium-Ion Phosphate Energy Storage System
PowerCube-M1 Operation Manual
Information Version: 2.2

This manual introduces PowerCube-M1 from Pylontech. PowerCube-M1 is a high voltage
Lithium-Ion Phosphate Battery storage system. Please read this manual before you install the
battery and follow the instruction carefully during the installation process. Any confusion, please
contact Pylontech immediately for advice and clarification.
Content
1. SAFETY ...................................................................................................................................................... 1
1.1 Symbol ................................................................................................................................ 1
2. SYSTEM INTRODUCE................................................................................................................................. 3
2.1 Product Introduce............................................................................................................. 3
The parameter of system .......................................................................................................... 3
2.2 System Diagram ................................................................................................................ 4
2.2.1 Multi battery string parallel connection by CAN communication between
MBMS and BMS diagram (battery string qty. ≤6 set) .......................................................... 4
2.2.2 Multi battery string parallel connection by Ethernet communication
between MBMS and BMS diagram (battery string qty. ≥1 set) ......................................... 4
2.2.3 Diagram between BMS and battery modules:.......................................................... 4
3. INSTALLATION .......................................................................................................................................... 5
3.1 Tools .................................................................................................................................... 5
3.2 Safety Gear........................................................................................................................ 5
3.3 System Working Environments Checking....................................................................... 6
3.3.1 Cleaning.......................................................................................................................... 6
3.3.2 Temperature ................................................................................................................... 6
3.3.3 Cooling System............................................................................................................... 6
3.3.4 Heating System............................................................................................................... 6
3.3.5 Fire-extinguisher System................................................................................................. 6
3.3.6 Grounding System.......................................................................................................... 6
3.4 Package Items .................................................................................................................. 7
Accessories................................................................................................................................. 7
Unpacking and check the Packing List:................................................................................. 7
3.5 Handling and placement ................................................................................................ 9
3.5.1 Handling and placement of the battery module ..................................................... 9
3.5.2 Handling and placement of the rack......................................................................... 9
3.5.3 The fix and installation of the rack ............................................................................... 9
3.5.4 Control Module (BMS) and all Battery Modules install into the Rack.................... 10
3.5.5 Install the MBMS into a 19’ standard rack [If configured]....................................... 10
3.5.6 Install the Ethernet Switch into a 19’ standard rack [If configured] ...................... 10
3.6 Cables connection......................................................................................................... 11
3.6.1 Pay attention terms:..................................................................................................... 11
3.6.2 Cables Connection ..................................................................................................... 11
3.6.2.1 CAN Communication Mode between MBMS and BMS (battery string qty.
≤6 set) (battery string qty. ≤6 set) .................................................................................... 12

CAN Communication Mode between MBMS and BMS Cable Diagram : ...................... 12
3.6.2.2 Ethernet communication between MBMS and BMS (battery string qty. ≥
1 set) .......................................................................................................................................... 13
Ethernet communication between MBMS and BMS Cable Diagram: ............................. 13
3.6.3 ADD Switch Setting (Address Assignment) ............................................................... 14
3.6.3.1 Under communication for single BMS (battery string qty. 1 set)......................... 14
3.6.3.2 Under CAN Communication Mode between MBMS and BMS (battery
string qty. ≤6 set).................................................................................................................... 14
3.6.3.3 Under Ethernet communication between MBMS and BMS (battery string
qty. 1~32 set) ............................................................................................................................ 14
3.6.3.4 MBMS Communication Mode................................................................................. 15
3.6.4 System turns on............................................................................................................. 16
3.6.5 System turns off............................................................................................................. 17
4. SYSTEM DEBUG....................................................................................................................................... 20
5. MAINTENANCE ...................................................................................................................................... 21
5.1 Trouble Shooting:............................................................................................................. 21
5.2 Replacement of main component .............................................................................. 23
5.2.1 Replacement of Battery Module ............................................................................... 23
5.2.2 Replacement of Control Module (BMS).................................................................... 24
5.2.3 Replacement of 3rd level Control Module (MBMS).................................................. 25
5.3 Battery Maintenance ..................................................................................................... 25
6. STORAGE RECOMMENDATIONS........................................................................................................... 27
7. SHIPMENT ............................................................................................................................................... 27
ANNEX 1: CABLE CONNECTION DIAGRAM (≤6 SET) .............................................................................. 28
Annex 2: Ethernet communication between MBMS and BMS Cable Diagram:
(>6set)........................................................................................................................................ 29
ANNEX 2: INSTALLATION AND SYSTEM TURN ON PROGRESS LIST .......................................................... 30
ANNEX 3: SYSTEM TURN OFF PROGRESS LIST ........................................................................................... 32

1/ 32
19PIMV0802
1. Safety
The PowerCube-M1 is a high voltage DC system, operated by authorized person only. Read all
safety instructions carefully prior to any work and observe them at all times when working on with
the system.
Incorrect operation or work may cause:
injury or death to the operator or a third party;
damage to the system hardware and other properties belonging to the operator or a third
party.
Skills of Qualified Person
Qualified personnel must have the following skills:
training in the installation and commissioning of the electrical system, as well as the dealing
with hazards;
knowledge of the manual and other related documents;
knowledge of the local regulations and directives.
1.1 Symbol
Danger
Lethal voltage!
Battery strings will produce high voltage DC power and can
cause a lethal voltage and an electric shock.
Only qualified person can perform the wiring of the battery
strings.
Warning
Risk of battery system damage or personal injury
Do NOT pull out the connectors while the system is working!
De-energize from all multiple power sources and verify that
there is no voltage.
Caution
Risk of battery system failure or life cycle reduces.
Read the product manual before operating the battery system!
Danger: Batteries deliver electric power, resulting in burns or a fire hazard when they are short
circuited, or wrongly installed.
Danger: Lethal voltages are present in the battery terminals and cables. Severe injuries or death
may occur if the cables and terminals are touched.
Warning: Do not open or deform the battery module;

2/ 32
19PIMV0802
Warning: Whenever working on the battery, wear suitable personal protective equipment (PPE)
such as rubber gloves, rubber boots and goggles.
Warning: PowerCube-M1 system working temperature range: 10℃~40℃; Optimum temperature:
18℃~28℃.Out of the working temperature range may cause the battery reduces the
cycle of life even cause the battery system over / low temperature alarm or protection.
It will affect the warranty.
Caution: Improper settings or maintenance can permanently damage the battery.
Caution: Incorrect inverter parameters will lead to the premature aging of battery.

3/ 32
19PIMV0802
2. System Introduce
2.1 Product Introduce
PowerCube-M1 is a high voltage battery storage system based on lithium iron phosphate battery,
is one of new energy storage products developed and produced by Pylontech, it can be used to
support reliable power for various types of equipment and systems. PowerCube-M1 is especially
suitable for application scene of high power, limited installation space, restricted load-bearing
and long cycle life.
The parameter of system
No.
Product Type
POWERCUBE-M1
736V148AH
1
Cell Technology
Li-ion (LFP)
2
Battery System Capacity(kWh)
108.9
3
Battery System Voltage(Vdc)
736
4
Battery System Capacity(AH)
148
5
Battery Controller Name
SC1000-200
6
Battery Module Name
H32148
7
Battery Module Quantity(pcs)
23
8
Battery Module Capacity(kWh)
4.74
9
Battery Module Voltage(Vdc)
32
10
Battery Module Capacity(AH)
148
11
Battery Module Cell Series Quantity(pcs)
10
12
Battery System Charge Upper-Voltage(Vdc)
828.0
13
Battery System Charge Current(Standard)
29.6
14
Battery System Charge Current(Normal)
74
15
Battery System Charge Current(Max.)
148
16
Battery System Discharge lower-Voltage(Vdc)
621.0
17
Battery System Discharge Current(Standard)
29.6
18
Battery System Discharge Current(Normal)
74
19
Battery System Discharge Current(Max.)
148
20
Efficiency
95%
21
Depth of Discharge
90%
22
Dimension(W*D*H,mm)
815*659*2130
23
Communication
RS485\CAN
24
Protection Class
IP20
25
Weight (kg)
1250
26
Operation Life(Years)
10
28
Operation Temperature(℃)
10~40
29
Storage Temperature(℃)
-20~60
30
Humidity
5%~95%
31
Product Certificate
TUV, CE, UL
32
Transfer Certificate
UN38.3
33
Pollution Degree (PD)
II
34
Other:
1)Battery Controller Dimensions(W*D*H)
2)Battery Module Dimensions (W*D*H)
3)Battery bottom base Dimensions(W*D*H)
330*628*150.5
330*628*150.5
Remark: The parameter will be changed when the battery modules in different series (1~23 pcs
battery modules).

4/ 32
19PIMV0802
2.2 System Diagram
2.2.1 Multi battery string parallel connection by CAN communication between MBMS and BMS
diagram (battery string qty. ≤conne
2.2.2 Multi battery string parallel connection by Ethernet communication between MBMS and
BMS diagram (battery string qty. ≥1 set)
2.2.3 Diagram between BMS and battery modules:

5/ 32
19PIMV0802
3. Installation
Please check every installation step with <Annex 2: Installation and System Turn ON Progress List>
during the install.
3.1 Tools
The following tools are required to install the battery pack:
Wire Cutter
Crimping Modular Plier
Cable Ties
Screw Driver Set
Electric Screw Driver
Adjustable Wrench
Sleeve Piece
1000VDC Multimeter
NOTE
Use properly insulated tools to prevent accidental electric shock or short circuits.
If insulated tools are not available, cover the entire exposed metal surfaces of the available tools,
except their tips, with electrical tape.
3.2 Safety Gear
It is recommended to wear the following safety gear when dealing with the battery pack
Insulated gloves Safety goggles Safety shoes

6/ 32
19PIMV0802
3.3 System Working Environments Checking
3.3.1 Cleaning
The battery system has high voltage connectors. The clean condition will cause the isolation
characteristic of the system.
Before installation and system working must clean the dust and iron scurf to keep the
environments cleaning. And the environment must have certain anti-dust ability.
The system after long term running must check the humidity and dust cover or not. If heavy dust
cover with high humidity on the system should stop the system running and make clean specially
for the high voltage connectors.
Danger: the power cables and plugs still have high voltage DC power from serial connected
battery modules (battery module can’t be turned off), must be careful to handle the
Power Plugs.
3.3.2 Temperature
PowerCube-M1 system working temperature range: 10℃~40℃; Optimum temperature: 18℃~
28℃.
Caution: Out of the working temperature range may cause the battery reduces the cycle of life
even cause the battery system over / low temperature alarm or protection.
3.3.3 Cooling System
The room must be equipped with cooling system.
Caution: Out of the working temperature range may cause the battery reduces the cycle of life
even cause the battery system over / low temperature alarm or protection.
3.3.4 Heating System
The room must be equipped with heating system. If the environment is lower than 0℃, must turn
on the heating system at first.
Caution: Out of the working temperature range may cause the battery reduces the cycle of life
even cause the battery system over / low temperature alarm or protection.
3.3.5 Fire-extinguisher System
The room must be equipped with fire-extinguisher system for lithium-ion battery.
The fire system needs to be regularly checked to be in normal condition. Refer to the using and
maintenance requirements of local fire equipment relevant.
3.3.6 Grounding System
Before the battery installation must sure the grounding point of the basement is stable and
reliable. If the battery system is installed in an independent equipment cabin (e.g. container),
must make sure the grounding of the cabin is stable and reliable.
The resistance of the grounding system must ≤100mi

7/ 32
19PIMV0802
3.4 Package Items
Accessories
The type and quantity of the accessories are subject to the battery
packing list.
NOTE
Power cable uses water-proofed connectors. It must keep pressing this
Lock Button during pulling out the power plug.
Unpacking and check the Packing List:
Power Cable + (Battery Module
and Main Controller Serial
Connection)
Orange/0.19m/1/0AWG/2 Orange
Surlok Terminal
pcs
1
Power Cable - Battery Module
and Main Controller Serial
Connection)
Black/0.32m/1/0AWG/2 Black
Surlok Terminal
pcs
1
Power Cable (Battery Module
Upper and Lower Serial
Connection)
Orange/0.24m/1/0AWG/1 Orange
& 1 Black Surlok Terminal
pcs
21
Power Cable (Battery Module
Left and Right rack Serial
Connection)
Orange/0.35m/1/0AWG/1 Orange
& 1 Black Surlok Terminal
pcs
1

8/ 32
19PIMV0802
Battery Cascade
Communication Cable (0.18m)
Black/0.18m/8 Core Super 5th
Class Twisted-pair Wire/RJ45
pcs
22
Battery Cascade
Communication Cable (0.5m)
Black/0.5m/8 Core Super 5th Class
Twisted-pair Wire/RJ45
pcs
1
External Battery CAN
Communication Cable (direct)
Black/3.5m/Super 5th Class
Twisted-pair Wire/2 RJ45 terminal
pcs
1
External Power Cable +
Orange/3.5m/1/0AWG/SURLOK
Terminal/50-8 Terminal
pcs
1
External Power Cable -
Black/3.5m/1/0AWG/SURLOK
Terminal/50-8 Terminal
pcs
1
For external power supply control module there is additional AC power cable:

9/ 32
19PIMV0802
AC Power Cable (Australia
Standard)
Black/2.5m/3*0.75mm2/Australia
Standard
pcs
1
3.5 Handling and placement
Warning: The battery rack is IP00. It must be installed in a restricted access area;
Warning: The PowerCube-M1 is a high voltage DC system, operated by qualified and authorized
person only.
3.5.1 Handling and placement of the battery module
Single battery module is 48kg. If without handling tools must more than 2 men to handling with it.
If install in high place of the rack it must more than 3 men.
3.5.2 Handling and placement of the rack
If without handling tools must more than 4 men to handling with it.
3.5.3 The fix and installation of the rack
The rack must be fixed on the basement and carriage on the wall with M10 screws.
Battery rack basement holes bitmap (unit: mm):
Battery rack wall fixed holes bitmap (unit: mm):
Front side

10 / 32
19PIMV0802
3.5.4 Control Module (BMS) and all Battery Modules install into the Rack
Dismantle the rack metal strip (on the left side and right side of the rack). After installed the
control module (BMS) and all battery modules need install these two stop blend back.
Install the buckle nuts. The position of nuts must meet the position of the control module (BMS)
and all battery modules.
Install the control module (BMS) and all battery modules in. Each module uses 4 screws to
fix it.
3.5.5 Install the MBMS into a 19’ standard rack [If configured]
Install the buckle nuts. The position of nuts must meet the position of the MBMS.
Install the MBMS in. Uses 4 screws to fix it.
3.5.6 Install the Ethernet Switch into a 19’ standard rack [If configured]
Install the buckle nuts. The position of nuts must meet the position of the Ethernet Switch.
Install the Ethernet Switch in. Uses 4 screws to fix it.
To the Bottom

11 / 32
19PIMV0802
3.6 Cables connection
3.6.1 Pay attention terms:
Danger: The battery system is high voltage DC system. Must make sure the grounding of the rack
is stable and reliable.
Danger: All the plugs and sockets of the power cables must be orange to orange and black to
black. Otherwise it will cause personal injury.
Danger: No short circuit or reserved connection of the battery system’s anode and cathode.
Caution: Wrong communication cables connection will cause the battery system failure.
Grounding
The PowerCube-M1 modules’ grounding is based on metal directly touch between
the module’s surface and rack’s surface. So it needn’t grounding cables at all. If
uses normal rack, remove the paint at the corresponding place.
Rack Grounding:
If there is a grounding metal frame outside the rack, for example, the metal angle
steel frame at the bottom of the container, the fix hole of the fix frame can be fixed
directly with the metal frame of the container. Then through the grounding of the container to
ensure reliable grounding.
If want to connect the ground cable, it can be connected to the M8 grounding bolt on the
frame base. Grounding cable must blAWG.
3.6.2 Cables Connection
Note: Power cable uses water-proofed connectors. It must keep pressing this
Lock Button during pulling out the power plug.
Grounding Bolt
Fix Hole
×4

12 / 32
19PIMV0802
3.6.2.1 CAN Communication Mode between MBMS and BMS (battery string qty. ≤6 set)
(battery string qty. ≤6 set)
When system configured PowerCube-M1 ≤6 set. The communication between PowerCube-M1s
uses CAN cascade communication mode. The communication between the MBMS and the BMS
of 1st PowerCube-M1 uses CAN communication mode.
CAN Communication Mode between MBMS and BMS Cable Diagram :
Note: The 1st PowerCube-M1 should be installed nearest by the MBMS.

13 / 32
19PIMV0802
3.6.2.2 Ethernet communication between MBMS and BMS (battery string qty. M set)
A. When system configured PowerCube-M1 ≥h set. The communication between
PowerCube-M1s and MBMS uses Ethernet Switch by LAN communication.
Ethernet communication between MBMS and BMS Cable Diagram:
B. Relation of MBMS and battery strings (PowerCube-M1s) in the ports of Ethernet Switch

14 / 32
19PIMV0802
The both side of BMS to MBMS communication cable must be marked with labels.
The last port of Ethernet Switch is for the MBMS.
From the 1st port to the nth port are for the corresponding battery string (PowerCube-M1). So we
can fastest find out the corresponding battery string on the Ethernet Switch.
3.6.3 ADD Switch Setting (Address Assignment)
ADD Switch is a 6 bit dial switches to manually distribute the
communication address of the battery system. Nether position is OFF,
means “0”. Upper position is ON, means “1”. 1st bit to 5th bit is for
address, and the 6th bit dial switch support a 120Ωresistance (Terminal
Resistance).
ADD Switch MBMS is a 6 bit dial switches to manually distribute the
communication address of the battery system. Nether position is OFF,
means “0”. Upper position is ON, means “1”. 1st bit to 4th bit is for
address, the 5th and the 6th bit dial switch support a 120Ωresistance
(Terminal Resistance).
3.6.3.1 Under communication for single BMS (battery string qty. 1 set)
The BMS’s first five bits must set in below <BMS’s Address Configure Table>. The last BMS’s terminal
resistance must set in “1” (X=1);
The address is configured follow ASCII code: (“X” is terminal resistance).
BMS’s Address Configure Table:
3.6.3.2 Under CAN Communication Mode between MBMS and BMS (battery string qty. s6 set)
The BMS’s first five bits must set in below <BMS’s Address Configure
Table>. The last BMS’s terminal resistance must set in “1” (X=1), and
other BMS’s terminal resistance must set in “0”.
The address is configured follow ASCII code: (“X” is terminal
resistance).
BMS’s Address Configure Table:
The MBMS’s ADD Switch set with “000011”. The last 2 bits are terminal
resistances.
Note: the 1st to 4th bit dial for MBMS refer to 3.6.3.4.
3.6.3.3 Under Ethernet communication between MBMS and BMS (battery
CAN M odbus Address dialbit
0 1 00000X
1 1 10000X
2 2 01000X
3 3 11000X
4 4 00100X
5 5 10100X
6 6 01100X
Battery
String Address Bit Battery
String Address Bit Battery
String Address Bit Battery
String Address Bit
110000X 910010X 17 10001X 25 10011X
201000X 10 01010X 18 01001X 26 01011X
311000X 11 11010X 19 11001X 27 11011X
400100X 12 00110X 20 00101X 28 00111X
510100X 13 10110X 21 10101X 29 10111X
601100X 14 01110X 22 01101X 30 01111X
711100X 15 11110X 23 11101X 31 11111X
800010X 16 00001X 24 00011X 32 00000X

15 / 32
19PIMV0802
string qty. 1~32 set)
The BMS’s first five bits must set in above <BMS’s Address Configure Table>. The other BMS’
terminal resistance must set in “0”.
The address is configured follow ASCII code: (“X” is terminal resistance).
BMS’s Address Configure Table:
The MBMS’s ADD Switch set with “000011”. The last 2 bits are terminal resistances.
Note: the 1st to 4th bit dial for MBMS refer to 3.6.3.4.
3.6.3.4 MBMS Communication Mode
In some project it configures multi Energy Storage Systems. In this case will have multi MBMS. The
address of MBMS must follow <MBMS’s Address Configure Table>
Battery
String Address Bit Battery
String Address Bit Battery
String Address Bit Battery
String Address Bit
110000X 910010X 17 10001X 25 10011X
201000X 10 01010X 18 01001X 26 01011X
311000X 11 11010X 19 11001X 27 11011X
400100X 12 00110X 20 00101X 28 00111X
510100X 13 10110X 21 10101X 29 10111X
601100X 14 01110X 22 01101X 30 01111X
711100X 15 11110X 23 11101X 31 11111X
800010X 16 00001X 24 00011X 32 00000X

16 / 32
19PIMV0802
3.6.4 System turns on
Double check all the power cables and communication cables. Make sure the voltage of the
PCS is same level with the battery system. Check all the power switch of every battery system is
OFF.
Warning: MBMS must be turned on after all battery strings self-check finish.
(1) Check the UPS is turned on. And the UPS is power supplying.
(2) Switch the external power or PCS on, to sure all the power equipment can work normally.
(3) Turn on the 1st BMS (Battery Control Modules) of battery string:
The second BMS must be operated after the first battery string’s self-check is successful.
From 1st BMS to the last BMS Then turn on the battery strings on one by one from 1st BMS to the
last BMS.
Turn on the “POWER OUTPUT SWITCH”:
Turn on the “Power Switch”:
Caution: When the breaker is tripped off because the system has over current or short circuit,

17 / 32
19PIMV0802
must after 30min to turn on it again, otherwise may cause the breaker damage.
The battery string’s system will check itself, if work normal the battery string system will go
to self-check mode.
If the BMS and all battery modules are working normally, every status LED will lighting
green, that’s mean self-check are pass. Self-check will be finish within 5sec.
The BMS can’t receive communication from upper equipment because the
communication is off, the “STATUS”lamp will light red after 30sec. That doesn’t means
failure existing, it means this battery string is working normally.
Warning: If has failure during the self-check, must debug the failure then can start next step.
If the “STATUS”lamp shows red from beginning, it means has failure in the battery string,
the Power Relays in BMS will switch ON, must debug at first.
(4) Switch the MBMS on after all the BMS turn on successful:
And check MBMS is working. The “STATUS”lamp will light green.
The Power Relays in BMS will switch ON after 30 seconds, when the MBMS was turned ON.
The “STATUS”lamp of the BMS will light green;
When the voltage distance is smaller than the parameter, the battery string will do the
parallel operation.
When the MBMS was turned ON, the “STATUS”lamp of the BMS will light red, but it is
normal;
Note: If the MBMS can’t build communication with other equipment, the system can’t
work normally. External Power should communicate with battery system through LAN,
CAN or RS485. Otherwise maybe cause battery system work abnormal.
Caution: The whole Battery Energy Storage System (BESS) after installation or restart the system
when long time not in using should charge it to full at first.
3.6.5 System turns off
When failure or before service, must turn the battery system off:
(1) Turn off the switch between PCS and this battery string (PowerCube-M1), or turn off the power
switch of PCS, to make sure no current through this battery string.
(2) Turn off the “Power Output
Switch” of the BMS.
(3) Turn off the “Power Switch” of
the BMS.
Other manuals for PowerCube-M1
2
Table of contents
Other Pylontech Storage manuals

Pylontech
Pylontech amber rock User manual

Pylontech
Pylontech PowerCube-X1 User manual

Pylontech
Pylontech Force-H3 User manual

Pylontech
Pylontech PowerCube-X1 User manual

Pylontech
Pylontech PowerCube-H1-V2 User manual

Pylontech
Pylontech PowerCube-M2 User manual

Pylontech
Pylontech PowerCube-M1-C User manual

Pylontech
Pylontech Force-H1-V2 User manual

Pylontech
Pylontech PowerCube-X1-V2 User manual

Pylontech
Pylontech Force-L2 User manual