Pyropress PYRP-28 User manual

DTR.PYRP.PYRD.PYRL-28.
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
PRESSURE TRANSMITTERS
PYRP-28, PYRP-28IS
DIFFERENTIAL PRESSURE TRANSMITTERS
PYRD-28, PYRD-28IS
HYDROSTATIC LEVEL TRANSMITTER PROBES
PYRL-28, PYRL-28IS
JULY 2012
Rev. C
The Pyropress Engineering Company Limited.
Bell Close, Newnham Industrial Estate, Plympton,
Plymouth, Devon, United Kingdom PL7 4JH
Tel: +44 (0) 1752 333933 Fax: +44 (0) 1752 336681
Email: sales@pyropress.com Website: www.pyropress.com

DTR.PYRP.PYRD.PYRL-28
Symbols used
BASIC REQUIREMENTS AND SAFE USE
- The manufacturer is not responsible for any damage to property or personnel resulting
from incorrect installation, failure to maintain the product in a suitable condition, or use
of the product other than for its intended purpose.
- Installation should be carried out by qualified personnel having the required authorisation to
install electrical and pressure measuring devices. The installer is responsible for performing
the installation in accordance with these instructions and with the electromagnetic compatibility
and safety regulations and standards applicable to the type of installation.
- If a product is deemed to be not functioning correctly, disconnect it and send it for repair to the
manufacturer or to a firm authorised by the manufacturer.
To minimise the risk of malfunction and associated risks to personnel, the product is not to be
installed or used in particularly excessive arduous conditions, where the possibility of the
following hazards may be present.
- Possibility of mechanical impacts, excessive shocks and vibration;
- Excessive temperature fluctuation,
- Condensation of water vapour, dust, icing.
The installation of intrinsically safe versions should be carried out in accordance with the latest
hazardous area installation regulations and standards.
The manufacturer reserves the right to make any product changes (not having a negative impact on
the operational parameters of the products) without updating the contents of the technical manual.
Symbol
Description
Warning –Installer to proceed strictly in accordance with the information contained
within the manual in order to ensure the safety and full functionality of the product.
i
Denotes information applicable during installation and operation of all listed products.
Denotes information essential to Exia certified products.
Denotes information on disposal of used equipment

DTR.PYRP.PYRD.PYRL-28
CONTENTS
1. INTRODUCTION............................................................................................................................................. 3
2. CONSIGNMENT CONTENTS.......................................................................................................................... 3
3. APPLICATIONS AND MAIN FEATURES........................................................................................................ 3
4. IDENTIFYING MARKS. ORDERING PROCEDURE ........................................................................................ 4
5. TECHNICAL DATA......................................................................................................................................... 4
5.1. PYRP–28. TECHNICAL DATA ....................................................................................................................... 4
5.1.1. PYRP–28. MEASUREMENT RANGES..........................................................................................................................4
5.1.2. PYRP–28. OPERATING PARAMETERS........................................................................................................................4
5.2. PYRD–28. TECHNICAL DATA ....................................................................................................................... 5
5.2.1. PYRD–28. MEASUREMENT RANGES..........................................................................................................................5
5.2.2. PYRD–28. OPERATING PARAMETERS .......................................................................................................................5
5.3. PYRP-28, PYRD-28.- COMMON PARAMETERS .............................................................................................. 5
5.3.1. PYRP–28, PYRD–28 .ELECTRICAL PARAMETERS....................................................................................................5
5.3.2. PYRP–28, PYRD–28. PERMITTED ENVIRONMENTAL CONDITIONS..............................................................................5
5.3.3. PYRP–28, PYRD–28. CONSTRUCTION MATERIALS...................................................................................................6
5.4. PRESSURE CONNECTORS............................................................................................................................. 6
5.4.1. PYRP–28. PRESSURE CONNECTORS.........................................................................................................................6
5.4.2. PYRD–28. PRESSURE CONNECTORS ........................................................................................................................6
5.5. PYRP–28,PYRD–28ELECTRICALCONNECTORSANDIPRATING.......................................................................... 6
6. CONSTRUCTION............................................................................................................................................ 6
6.1. MEASUREMENT PRINCIPLES ......................................................................................................................... 6
6.2. CONSTRUCTION........................................................................................................................................... 6
6.3. CASING,ELECTRICAL CONNECTIONS............................................................................................................. 7
7. INSTALLATION LOCATION OF TRANSMITTERS ......................................................................................... 8
7.1. GENERAL NOTE ........................................................................................................................................... 8
7.2. LOW AMBIENT TEMPERATURE....................................................................................................................... 8
7.3. HIGH PROCESS TEMPERATURES. .................................................................................................................. 8
7.4. MECHANICAL VIBRATION,CORROSIVE MEDIA................................................................................................. 8
8. INSTALLATION AND MECHANICAL CONNECTIONS................................................................................... 9
9. ELECTRICAL CONNECTION.......................................................................................................................... 9
9.1. GENERAL RECOMMENDATIONS...................................................................................................................... 9
9.2. CONNECTIONS FOR TRANSMITTERS WITH PD-TYPE CONNECTOR..................................................................... 10
9.3. CONNECTIONS FOR TRANSMITTERS WITH PK OR PM12-TYPE CONNECTOR...................................................... 10
9.4. CONNECTIONS FOR TRANSMITTERS WITH TERMINAL BOX (PZ-TYPE CONNECTOR)............................................. 10
9.5. PROTECTION FROM OVER VOLTAGE ............................................................................................................. 10
9.6. EARTHING................................................................................................................................................. 11
10. ZERO AND RANGE (SPAN) ADJUSTMENT............................................................................................... 11
11. SERVICES AND SPARE PARTS. ............................................................................................................... 11
11.1. PERIODIC SERVICE................................................................................................................................... 11
11.2. UNSCHEDULED SERVICES ......................................................................................................................... 11
11.3. CLEANING THE DIAPHRAGM AND OVERLOAD DAMAGE................................................................................. 11
11.4. SPARE PARTS.......................................................................................................................................... 12
12. PYRL-28 LEVEL PROBES.......................................................................................................................... 12
12.1. APPLICATIONS......................................................................................................................................... 12
12.2. PYRL–28. TECHNICAL DATA.................................................................................................................... 12
12.3. PRINCIPLES OF OPERATION,CONSTRUCTION.............................................................................................. 12
12.4. INSTALLATION AND FITTING ..................................................................................................................... 12
12.5. ELECTRICAL CONNECTION.SETTINGS ........................................................................................................ 13
12.6. EARTHING............................................................................................................................................... 13
13. PACKING, STORAGE AND TRANSPORT.................................................................................................. 13
14. GUARANTEE.............................................................................................................................................. 13
15. ADDITIONAL INFORMATION..................................................................................................................... 13
15.1. RELATED DOCUMENTS.............................................................................................................................. 13
15.2. RELATED STANDARDS.............................................................................................................................. 13
16. FIGURES (DIAGRAMS) .............................................................................................................................. 14
APPENDIX 01 (FOR INTRINSICALLY SAFE ATEX CERTIFIED VERSIONS) .................................................. 27

DTR.PYRP.PYRD.PYRL-28
1. INTRODUCTION
1.1. This manual covers the PYRP–28 pressure transmitter, PYRD–28 differential pressure transmitter and
PYRL–28 hydrostatic level probe, and contains all the necessary information and guidelines to understand their
functioning and how to correctly put them to work. It includes instructions and recommendations concerning their
installation and use.
1.2. The transmitters comply with the requirements of all the relevant EU directives and this is indicated on the
transmitter labelling and the relevant Declaration of Conformity.
1.3. Additional data relating to the ATEX certified Intrinsically Safe versions PYRP-28IS, PYRD-28IS
transmitters and PYRL-28IS level probes is provided under the appendix (see page 27).
This appendix must be referred to during the installation and putting to work of these transmitters.
2. CONSIGNMENT CONTENTS
Transmitters are delivered in single and/or multiple packs.
A single batch of transmitters will be supplied with a copy of this manual (more can be supplied on application)
If requested at the ordering stage Calibration Certificates for each transmitter or a common Certificate Of
Conformity can be supplied and will accompany the goods.
Non order specific documentation/certificates such as ATEX, SIL 1, PED etc. would be provided when applicable
(these can also be downloaded from us at www.pyropress.com)
3. APPLICATIONS AND MAIN FEATURES
3.1. The PYRP-28 pressure transmitters are designed to measure gauge pressure, vacuum pressure and
absolute pressure of gases, vapours and liquids that are compatible with the wetted parts material.
3.2. PYRD–28 differential pressure transmitters are designed to measure the difference between two separate
inputted pressures on applications such across filters (blocked filter monitoring), orifices (liquid or gas flow
monitoring) or liquid levels in closed tanks.
PYRD–28 differential pressure transmitters with N4,GA,GB or P connections are suitable for a maximum static
pressure 40 Bar (see fig.7 –typical representation only).
PYRD–28 differential pressure transmitters with C type manifold connection blocks are suitable for a maximum
static pressure of 250 Bar (320 Bar and 420 Bar options available) (see fig.8).
3.3. The PYRP-28 and PYRD–28 can be fitted with a range of additional process connectors and/or
isolating seals enabling them to be used on various challenging media, such as high viscosity,
reactive/corrosive to standard wetted parts, and temperature extremes (high and low) etc.
Data on these options and ancillary items can be found in a separate technical literature.
3.4. For depth measurements in open tanks the PYRL-28 hydrostatic level probe variant would be used, this is a
pressure transmitter fitted with sensing modules with an extension tube to suit the depth of level required. (see
Section 12).
3.5. The PYRP-28 or PYRD-28 transmitters and the PYRL-28 probes provide a 2 wire, 4 - 20mA output signal.
Alternatively, the PYRP-28 and PYRD-28 can as an supplied with either a 3 wire, 0 - 20mA or 0 - 10V output
signal.
i

DTR.PYRP.PYRD.PYRL-28
4. IDENTIFYING MARKS. ORDERING PROCEDURE
4.1. Every transmitter and probe supplied is fitted with an information label containing at least the following:
CE mark, notified body certificate references/codings, Pyropress’ name, transmitter model no., unique serial
number, measurement range, output signal and power supply voltage.
Additionally, Intrinsically Safe certified versions would have the full ATEX markings as detailed in the Appendix
(see page 27).
5. TECHNICAL DATA
5.1. PYRP–28 Pressure Transmitter Technical Data
5.1.1. PYRP–28 Measurement Ranges
The PYRP-28 pressure transmitter can be supplied specifically calibrated with any desired range contained within
the below spans:
Gauge pressure : 0 - 10 mbar to 0 - 1000 Bar
Absolute pressure : 400mbar to 80bar.
Recommended standard ranges:
Gauge pressure : 0 to -1; -0,4; -0,1; 0,1; 0,4; 1; 2,5; 6; 10; 16; 25; 60; 160; 250; 400, 600, 1000 Bar
Absolute pressure : 0 to 0,4; 1; 2,5 6; 10; 16; 25; 60 Bar
5.1.2. PYRP–28 Operating Parameters
Table 1
Measurement Range
100 mBar
400 mBar
0 - 1 to 1000 Bar
Overpressure limit
(repeatable, no hysteresis)
1 Bar
2.5 Bar
4 x range
Max 1200 Bar
Burst pressure
2 Bar
5 Bar
8 x range,
Max 2000 Bar
Accuracy
0.3%
0.2% (0.16 % - special version)
Thermal error
Typically 0.3% / 10º C; Max 0.4% /10º C
Typically 0.2% /10º C; Max 0.3% /10º C
Long term stability
0.2 % / year
0.1 % / year
Hysteresis and repeatability
0.05%

DTR.PYRP.PYRD.PYRL-28
5.2. PYRD–28 Differential Pressure Technical Data
5.2.1. PYRD–28 Measurement Ranges
The PYRD–28 differential pressure transmitters can be supplied specifically calibrated with any desired range
contained within the spans of 0 - 16mbar to 0 - 25 bar.
Recommended standard ranges: 0.4; 1; 2,5; 6; 10; 16; 25 Bar
(-0,1 to + 0,1); (-1.0 to +1.0) Bar
5.2.2. PYRD–28 Operating Parameters
Table 2
Parameters
Measurement Ranges
100 mBar
1 Bar
2 Bar
25 Bar
Overpressure limit
Static pressure limit
C type connection: 250 Bar - (320 and 420 Bar option)
N4, GA, GB and P Type connection : 40 Bar
Accuracy
0.4%
0.25%
Long term stability
0.2%/year
0.1%/year
Thermal error / 10C
typical 0.3%/10°C
max 0.4%/10°C
typical 0.2%/10°C,
max 0.3%/°C
Zero shift error for static pressure *
0.1% / 10 Bar
Hysteresis and repeatability
0.05%
*- This error can be eliminated by zeroingthe transmitter instatic pressure conditions with zero differential pressure.
5.3. PYRP-28 Pressure and PYRD-28 Differential Pressure Transmitters -
Common Parameters
5.3.1. Electrical Parameters
Power supply 10.5 - 36V DC, nominally 24V DC (2 wire, 4 - 20mA version)
15 - 30V DC (3 wire, 0 - 10V or 0 - 20mA version)
Note: For power supply for Intrinsically Safe versions see Appendix 01 of this manual.
Output signal 4 - 20mA two-wire transmission
0 - 10 V three-wire transmission
0 - 20 mA three-wire transmission
Error due to supply voltage changes 0.005 % /V
Load resistance
(for 4 - 20mA version)
Load resistance
(for 0 - 10V and 0 –20mA versions R ≥ 5kΩ
Error due to supply voltage changes 0.005 %/V
Voltage for insulation strength testing 500 VAC or 750 VDC, see p.9.5.
Excess voltage protection see Point 9.5 (page 10)
5.3.2. PYRP–28, PYRD–28. Environmental Condition Limitations
Ambient temperature limit -40 to +80°C (for PYRP-28)
Ambient temperature limit -25°C to +80°C (for PYRD-28)
(For ambient temperature limits for Intrinsically Safe versions see Appendix 01.
Process temperature limit -40 to +120°C –direct measurement of process.
For temperatures in excess of 120ºC a diaphragm seal,
radiator, looped siphon tube or impulse line must be used.
Thermal compensation range -10 to +80ºC (for PYRP-28) or special by arrangement
Thermal compensation range 0 - 70ºC (for PYRD-28) or special by arrangement
R[Ω] =
Usup.[V] –10.5V
0.02A

DTR.PYRP.PYRD.PYRL-28
Relative humidity 0 - 98%
Vibration during operation Max 4g
5.3.3. Construction Materials
Diaphragm Stainless steel 316L
(Hastelloy C-276 option on pressure transmitter only)
Sensing module Stainless steel 316L
Casing for electronic parts Stainless steel 304
PZ-type terminal box Stainless steel 304
Angular connector, DIN 43650, PD type Itamid
Internal sensor liquid fill Silicone oil, chemically inactive liquid for measurement of
oxygen.
Cable shield in PK connector Polyurethane, special version –Teflon
5.4. Pressure Connectors
5.4.1. PYRP–28. Pressure Connectors
M & MG-type connector with M20x1.5 thread –see figure 3a
P & PH -type connector with M20x1.5 thread –see figure 4a.
T, TH or MF-type connector with flush diaphragm –see figure 5a.
RM-type connector with M20x1.5 thread and radiator –see figure 3a
RG-type connector with G1/2” thread – see figure 6a
GB or GH -type connector with G1/2” thread – see figure 6a
GF-type connector with G1/2” thread and flush diaphragm –see figure 6c
GD-type connector with G1” thread and flush diaphragm – see figure 6e
N2-type connector with 1/2"NPT thread (male) and with internal G1/4” thread (female).
X-type Diaphragm seal –refer to literature
Other connection types by arrangement
5.4.2. PYRD–28. Pressure Connectors
Type N4 - ¼” NPT F, Type GA –G¼, Type GB –G½, Type P –M20 x 1.5 M type see typical representation fig.7.
C type connection for direct mounting with a 3 or 5 valve manifold see Fig. 8.
5.5. PYRP–28 and PYRD–28 Electrical Connectors and IP Ratings.
PYRP-28, PYRD-28 with PD-type connector, DIN 43650, PG-11 gland. IP65 rated (EN 60529:1991/A1:2000)
PYRP-28, PYRD-28 with PZ-type terminal box, M20x1,5 packing gland. IP66 rated (EN 60529:1991/A1:2000)
PYRP-28, PYRD-28, PYRL-28 with PK-type cable connector. IP67 rated (EN 60529:1991/A1:2000)
PYRP-28 with PM12-type connector. IP67 rated (EN 60529:1991/A1:2000)
6. CONSTRUCTION
6.1. Measurement Principles
The PYRP-28, pressure transmitters, PYRD-28 differential pressure transmitters and the PYRL-28 level probes
operate by converting changes in the piezoresistive bridge, which are proportional to the measured pressure, into
a standard current or voltage output signal.
The active sensing device is a silicon diaphragm with diffused piezoresistors, separated from the medium by an
isolating diaphragm and oil.
6.2. Construction
The basic component of the transmitter and probe is the sensing module, in which the input pressure is converted
into an electrical signal. The sensing modules are fitted with process connections (see para. 5.4). The second
element of the transmitter is an electronic unit which amplifies and conditions the output signal. This is fitted with
potentiometers which can be used to set the zero and the range positions.
For the measurement of dense, chemically reactive, or high temperature media, the transmitters are fitted
additionally with various types of diaphragm seal connectors, depending on the type of medium and
environmental conditions (details can be found within separate literature).

DTR.PYRP.PYRD.PYRL-28
6.3. Casing and Electrical Connections
6.3.1. The casing of the PYRP-28 and PYRD-28 transmitters is manufactured from ø27 tube (304 st steel or 316
st. steel), fixed to the the sensing module as shown in figure 1b and 7. At the electrical connection end is the PD
type electrical connector with PG-11 packing gland. By loosening the fixing screw and removing the connector
access can be gained to the potentiometers for zero and span adjustments.
6.3.2. The PYRP-28, PYRD-28 transmitters may be fitted with a PK cable connector (see figure 1c) or PM12
(PYRP-28 only) (see figure 1f), mounted similarly to the PD connector. The body of the connector contains a
permanently fixed and sealed cable of standard length 3m (other lengths can be supplied to order). The cable
contains a capillary which references the non media side of the measuring diaphragm to atmosphere.
6.3.3. The PYRP-28, PYRD-28 transmitters with a PZ type connector has a terminal box permanently mounted
on the upper part of the casing (figure 2). The box is sealed with a threaded a lid. Mounted internally are
terminals marked 1, 2 and 3.
PZ type terminal housing has an internal earth terminal, whilst the Intrinsically Safe certified version also has an
external earthing terminal.

DTR.PYRP.PYRD.PYRL-28
7. INSTALLATION LOCATION OF TRANSMITTERS
7.1. General note
7.1.1. The PYRP-28 transmitters can be installed both indoors and outdoors. It is recommended that transmitters
with DIN type electrical connectors (PD and PM12) intended for outdoor use be provided with an additional form
of mechanical protection.
There is no need for a cover in the case of transmitters with PZ and PK type connectors.
7.1.2. The location of the installation should be selected to both allow easy access to the transmitter but also to
ensure it cannot be subjected to accidental mechanical damage. In planning the installation of the transmitter and
configuration of the impulse lines, consideration should be given to the following requirements:
- The impulse lines should be as short as possible, with a sufficiently large cross-section, and be free of
sharp bends, in order to prevent blockages;
- Where the medium is a gas, the transmitters should be installed above the measuring point ensuring
any condensation flows down towards the tapping point. Where the medium is a liquid or where a
diaphragm seal is used, the transmitters should be installed below the tapping point.
- The impulse lines should be inclined at a gradient of at least 10cm/M
- The levels of filling liquid in the impulse lines should be equal or a constant difference maintained.
- The impulse lines and the valve connection system configuration should be implemented taking into
consideration the measurement conditions, the need to access the transmitters for maintenance and
access the impulse lines for water or gas removal and flushing purposes.
7.1.3. Transmitters should be as much as possible be protected from any physical damage.
Should the installation location compromise the integrity of the process connection or the
electrical connection causing leaking of the medium or making the electrical connection
unreliable or hazardous a more appropriate location should be selected.
7.2. Low Ambient Temperature
When the solidification point of a liquid process medium is greater than the ambient temperature,
steps should be taken to protect the sensor from freezing effects such as fluid expansion.
This is particularly important in the of case open air installations.
Protection by filling the impulse lines with an ethylene glycol and water mixture, or another liquid whose
solidification point ensures the minimum working temperature is not exceeded. The transmitter case and electrical
connection protects the transmitter from short exposure to low temperatures only. Where the temperature is very
low (less than -25°C), the transmitter and impulse lines should be heated.
7.3. High Process Temperatures.
The PYRP-28 and PYRD-28 transmitters may be used to measure media with temperatures of up to 120°C.
To protect the sensing module from temperatures in excess of 120ºC, suitably long impulse lines should be
incorporated to disperse the heat and to reduce the process temperature at the transmitter inlet.
Where it is not possible to use impulse lines of necessary length, PYRP-28 transmitters with alternative protection
methods should be used i.e. cooling elements/radiators or diaphragm seals (see these options in separate
literature)
For the Intrinsically Safe version also see the Appendix at page 27 onwards.
7.4. Mechanical Vibration, Corrosive Media.
7.4.1. The transmitters will operate satisfactorily without hindrance when subjected to vibration with amplitudes up
to 1.6 mm and accelerations to 4g.
If high levels of vibration are transmitted to the equipment via the pressure line, a more flexible line with vibration
dampening properties should be adopted, or alternatively the connection to the transmitter interrupted via a
diaphragm seal and capillary.
7.4.2. On the PYRP-28 pressure transmitters, where the process medium is incompatible with the
standard 316L stainless steel diaphragm, the option of Hastelloy C276 should be considered. (The
PYRD-28 differential pressure transmitter is fitted with Hastelloy C276 diaphragm as standard).
If this material is also not compatible then other means of protection should be adopted such as
chemical/diaphragm seals. Please refer to separate literature for these items.
i

DTR.PYRP.PYRD.PYRL-28
8. INSTALLATION AND MECHANICAL CONNECTIONS
8.1. The PYRP-28 transmitters can be mounted directly on rigid impulse lines.
Where connectors as in figures 3a, 4a, 5a, 6a, 6c, 6e are used it is recommended that connection sockets as
figures 3b, 4b, 5b, 6b or 5c, 6d, 6f are also incorporated.
Where the connectors as figures 4a, 5a and 6c, 6e are used then flat gaskets are also to be fitted.
The socket shown as in figure 5c, 6d and 6f can be obtained from the Pyropress.
The seal material is to be selected based on the pressures involved, type of medium and the process temperature.
If the pressure is applied via flexible tubing the transmitter should be mounted on a fixed surface or support.
The material and characteristics of the impulse tubes are to be selected in the same way as the seal material
above, i.e. based on pressure, medium and temperature.
8.2. The PYRD–28 transmitters can be mounted directly on rigid impulse lines.
To connect the basic versions of transmitters, with two threaded connections (N4,GA,GB or P), one can use
standard stainless steel threaded tube connectors.
The PYRD–28 transmitters can be installed using mounting bracket (BF) for wall mounting or attachment to a
ø25 pipe (Figure 11).
The PYRD–28 with manifold style (C-type connector) are designed for installation on 3 valve or 5 valve manifolds.
When fitted with a manifold BU mounting bracket can be used for wall mounting (figure 13) or without manifolds
mounting bracket BCZ (zinc plated steel) or BCS (stainless steel) can be used for wall mounting or 2” pipe
mounting (figure 12).
8.3. The PYRP-28 and PYRD-28 transmitters can be installed and will operate satisfactorily in any orientation.
When directly mounted on equipment with a high process temperature (up to 120°C) or radiated heat it is
recommended that the transmitter is mounted (if possible) to the side of the equipment and not directly in the flow
of a continuous rising heat source.
The PYRP-28 can be fitted to a Pyropress syphon loop to protect against high temperature vapour applications,
see Fig. 14.
In the case of narrow pressure spans, the accuracy can be affected by the location of the transmitter, the
configuration of the impulse lines and the way in which they are filled with the liquid process medium.
This error can be corrected using the zero setting function.
8.4. In selecting the correct assembly components, Pyropress would be pleased to provide information and
recommendations for connection elements, adapters, sockets, valves and other ancillary items.
Further details of these items can be found in the transmitter catalogue.
Pressure may be applied to the transmitter only after checking that the item has a measurement
range and maximum withstand rating that is equal to or greater than the value of the pressurised
system. Additionally gaskets must have been have been properly selected and fitted, and the
pressure connections have been correctly secured.
Attempts to undo fasteners or fixing connector pipes on a transmitter whilst pressurised may
cause the medium to leak and create hazards for the personnel.
When removing the transmitter it must be isolated from the process pressure or the pressure
reduced to atmospheric level. It is also important that due care is taken with regard to the
characteristics of medium which may be highly reactive, caustic, explosive, high temperature or
otherwise hazardous to personnel.
If necessary, rinse out this part of the system before removing the transmitter and wear suitable
protective clothing based on the recommendations in the Material Safety Data Sheet (MSDS).
Transmitters with flanged diaphragm seals are to be fitted to identical mating flanges on the facility.
It is recommended that the user matches the screw joints material to the pressure, temperature, flange
material and seal to ensure tightness of the flange joint in the expected operating conditions.
Coarse threaded screws complying with ISO 261 are to be used for flanges used in the transmitters.
9. ELECTRICAL CONNECTION
9.1. General recommendations
It is recommended that twisted pair cabling be used for the signal lines. If the transmitter and signal line are
subject to a large amount of electromagnetic interference, then screened twisted pair cable should be used.
The signal wires should not run alongside network power supply cables or near to equipment that draws high
levels of electrical current.
i

DTR.PYRP.PYRD.PYRL-28
Any associated equipment used in conjunction with the transmitters should be equally resistant to
electromagnetic interference from the transmission lines in accordance with compatibility requirements.
It is also recommended to have EMC filters on the primary side of the transformers, power supplies used for the
transmitters and apparatus used in conjunction with them.
9.2. Connections for transmitters with PD DIN Type connector.
The PYRP-28 and PYRD-28 transmitter and PYRL-28 probe fitted with PD type connectors are to be connected
as shown in Fig.1a.
To connect, loosen the retaining screw and remove the connector from the contact pins together with its cover.
Then remove the block from its cover, levering it off carefully with the end of a small screwdriver inserted into the
slot provided for this purpose. Connect the wires to the block as shown in Fig 1a (page 14).
When cabling to the DIN connector through the PG11 gland, should the wire sizes be insufficient to provide
a full seal when tightened then the gland should sealed with an elastic sealing compound to maintain the
IP65 seal. It is recommended that a loop is incorporated in the cable prior to the PG11 gland to prevent
condensation from running down in the direction of the gland.
9.3. Connections for transmitters with PK or PM12 Type connector.
The PYRP-28 and PYRD-28 transmitter with PK connection or PYRP-28 transmitter with PM12 connector should
be wired via a separate terminal box, in which the transmitter’s cable is terminated.
The terminal box must not be fully airtight as the transmitter must be able to reference atmospheric pressure
through the capillary in the connector cable.
9.4. Connections for transmitters incorporating terminal housing (PZ Type)).
The PYRP-28 and PYRD-28 transmitters with PZ terminal housing should be wired to the terminal block as shown in
figure 2 (page 15). Tighten the packing gland ensuring there is a water tight seal on the cable, and refit the screwed
terminal cover and gasket.
9.5. Over-voltage Protection
9.5.1. If subjected to over-voltage through incorrect supply connections or atmospheric electrical discharges the
transmitters can fail or be irreparably damaged, therefore all models are fitted with Transient Voltage Suppression
(TVS) diodes (see Table 3, Column 2).
9.5.2. Over-voltage protection between the signal lines and the casing or earth (not prevented by the TVS diodes)
is provided by plasma surge arresters (see the Table 3, Column 3).
When the signal lines have lengthy runs it is recommended that additional similar protection is installed near the
transmitter, with another adjacent to electrical connection points of any equipment used in conjunction with the
transmitter.
Details of fitted transmitter over-protection
Table 3
1
2
3
Type of transmitter and electrical
connector.
Protection between wires (TVS
diodes) –permitted voltage.
Protection between wires and
earth and/or casing –type of
protection, permitted voltage
1
PYRP-28, PYRD-28 with PZ
connector
39V DC
Plasma surge arresters - 100VDC
2
PYRP-28 with PD, PK or PM
connector
39V DC
Installed by arrangement
3
PYRL-28 with PD, PK connector
39V DC
Installed by arrangement
4
PYRD-28 with PD connector
39V DC
Installed by arrangement
9.5.3. The voltage in the protective elements must not exceed the maximum permitted values given in columns 2
and 3 of the table.
The insulation test voltages (500V AC or 750V DC) given in 5.1.1 refer to transmitters plasma surge
arresters - such protection is not applied to Intrinsically Safe (Exia) models.
i
i

DTR.PYRP.PYRD.PYRL-28
9.6. Earthing
The transmitter earthing methods are detailed in figures 1a and 2.
If the transmitter is directly mounted or connected to an fully earthed electrically conductive structure or pipework
system via a metal bodied fitting then additional earthing would not be necessary.
10. ZERO AND RANGE (SPAN) ADJUSTMENT
The transmitter is factory calibrated in accordance to the requirements stated in the customer’s purchase order.
After the transmitter has been installed it may be necessary to reset the zero point, see Point 6.3 and Fig’s 1e or
2 (depending on the electrical connection version) for access to the zero adjusting potentiometer.
To carry out range adjustment, power the transmitter in accordance with its electrical requirements as specified in
this document and as as stated on the transmitter label.
Apply a pressure equal to the lower limit of the measurement range, and adjust the “zero” potentiometer
(clockwise to increase/anti-clockwise to decrease) to provide an output signal of 4mA (or 0mA or >*0V).
After carrying out this zero-ing procedure, apply supply a pressure equal to the upper limit of the range, and use
the “range” potentiometer to provide an output signal of 20mA (or 10V on the voltage output version).
Once the top of the range has been set, re-check the zero out and repeat the procedure if necessary.
Potentiometers can be used to adjustthe zero point and the range by up to 10%.
*Obviously on Transmitters with a 0 –10 Vdc output it is not possible to achieve an output of 0 volts.
11. SERVICING AND SPARE PARTS.
11.1. Periodic servicing
Periodic servicing should be carried out at intervals to suit the installation but we recommend annual checks are
made as follows:
1. Pressure connectors should be checked for loose connections and leaks.
2. The electrical connections should be checked for tightness, ensuring there has been no ingress of water or
dust and the condition state of the gaskets inspected.
3. Diaphragm seals (if fitted) should be checked for tarnishing and corrosion.
4. The transmitter calibration and output should be checked.
11.2. Unscheduled services
If the transmitters are installed in a location or system where there is the possibility of accidental
mechanical damage, excess pressure, hydraulic impulses or over-voltage, or if the diaphragm is at risk of
sedimentation build up, crystallization or erosion, inspections should be carried out more regularly.
The sensing element (diaphragm) should be inspected and carefully cleaned (see 11.3 below), the
protective diodes should be checked for shorting, and the calibration and output checked..
Where it is found that there is no value signal within the circuit or the value is incorrect, a check should be
made on the integrity of the circuit and its electrical connections. Additionally the power supply and load
resistance should be checked. If the electrical circuit is proven to be secure, check the operation of the
transmitter.
After checks have been made, take steps to eliminate the faults detected.
11.3. Cleaning the Diaphragm and Overload Damage
11.3.1. Sediment and dirt which have formed on the diaphragm in the course of operation must not be removed
by mechanical means, as this may damage both the diaphragm and the transmitter itself.
The only approved method to dissolve or flush out any sediment build up
11.3.2. Transmitter malfunction can be due to damage caused by overloading, e.g. in cases of:
- over pressurisation.
- freezing or solidification of the process medium.
- action of a hard or sharp object, such as a screwdriver.
In the above instances, typical symptoms are that the output current falls below 4mA or rises above 20mA, or the
transmitter fails to respond to input pressure.
i
i
i

DTR.PYRP.PYRD.PYRL-28
11.4. Spare parts.
The following transmitter parts may need replacing due to damage or normal wear:
PD connector –DIN plug and gasket, connector base screwed clamping ring, information/rating label.
PK connector –the entire connector.
PZ/PS housing –cover seal/gasket and electrical packing gland.
In the Exia version, the user may replace only the terminal block with angled cover and the seal in the PD
connector, or the seal and packing gland in the PZ/PS housing version
Replacement or repair of any other parts should not be carried out by anyone other than the
manufacturer or their authorised servicing affiliates.
12. PYRL-28 TRANSMITTER LEVEL PROBES
12.1. Applications
These transmitter level probes are designed to measure the depth of a liquid medium from the top in the vertical
plane and used in applications such as open tanks, sumps, watercourses, open channels etc.
12.2. Technical Data
12.2.1. The level transmitters are designed to measure levels from 200 to 3000mm H2O.
12.2.2. Operating Parameters
Measurement Range
0 - 200 to 500mm H2O 0 - 700 to 3000mm H2O
Accuracy
0.25%
0.16%
Thermal error of zero
Typically 0.3%/10°C, Max 0.5%/10°C
Typically 0.2%/10°C, Max 0.3%/10°C
Thermal error of span
Typically 0.2%/10°C
Max 0.3%/10°C
Typically 0.2%/10°C
Max 0.3%/10°C
Hysteresis, repeatability
0.05%
12.2.3.PYRL-28 electrical parameters see para. 5.5.
12.2.4.PYRL-28 permitted environmental and operating conditions:
Thermal compensation range 0 to 25°C - standard
-10 to 70 - special version on application.
Process/medium temperature -25 to 80°C
Other parameters as stated in paras 5.3 and 5.4
12.3. Principles of Operation, Construction
The PYRL-28 level transmitter probe functions by converting the pressure of a column of liquid into a standard
transmitter signal. The standard version provides a two wire 4 - 20mA output, however there are options for three
wire 0 - 20mA or 0 - 10V output versions.
The transmitter comprises of a sensing module and an electronic assembly, connected with an extension tube
whose length is determined by the required depth of the process to be measured. The tube can be fitted with a
flange for mounting on the cover of the tank (figure 9). The electrical connection options are the PD or PK type
connectors, (see figures 1b, 1c and 9).
12.4. Installation and Fitting
The probe is inserted into the liquid being measured vertically from the top with the electronic assembly and
connector kept clear of the maximum level of the liquid. When installing the transmitter, the zero position should
be precisely determined. When the tube is >2M it should also be additionally secured at or near the bottom. If
there is a current or turbulence in the fluid process, a protective tube should be fitted. When fitted outdoors it is
recommended that a cover be provided.
The process medium must not be allowed to freeze around the probe. The sealing diaphragms should be
checked regularly, and sediment deposits, blockages etc. should be prevented. Any accumulations should
be removed by dissolving or careful washing.
i

DTR.PYRP.PYRD.PYRL-28
12.5. Electrical connection. Settings
12.5.1. The transmitter probe should be connected as detailed in figure 1a.
The user may adjust the span by 10%using the zero and range potentiometers as detailed in point 10.
12.5.2. The probes are protected against over voltage as stated in 9.5.
12.6. Earthing.
On level transmitter probes with PD, PK or PZ connectors, if overvoltage protection is fitted, the probe’s extension
tube should be earthed.
When supplied with the PZ connector on the Intrinsically Safe Exia version earthing should be made via the
external earth terminal.
13. PACKING, STORAGE AND TRANSPORT
13.1. The transmitters should be packed in such a way as to protect them from damage during transportation.
The transmitters should be stored in multiple packs under cover, in a place free of damp and corrosive
substances, with an air temperature between +5°C and +40°C, and relative humidity of not more than 85%.
Transmitters stored without packaging, should have protective covers fitted over the diaphragm.
During transportation, the transmitters should be packed and secured so as to prevent them from moving in
transit. Any means of transport may be used, provided the items are isolated from atmospheric conditions.
13.2. The level transmitters are individually packed, thereafter bound together in packages containing several
probes where multiples are ordered. Storage and transport as above.
14. GUARANTEE
14.1 The manufacturer guarantees the correction functioning of the PYRP-28 pressure and PYRD-28 differential
pressure transmitters for a period of 24 months from the date of purchase and servicing, the specific details being
as stated in the product warranty supplied with the goods. In the case of non standard models the guarantee
period shall be agreed by the manufacturer and the user, but shall not be less than 12 months.
14.2. The manufacturer guarantees the correct functioning of the PYRL-28 level transmitters for a period of 12
months from the date of purchase or servicing the specific details being as stated in the product warranty
supplied with the goods.
15. ADDITIONAL INFORMATION
The manufacturer reserves the right to make design improvements and changes without notice which do not
negatively effect the quality of the transmitters.
15.1. Related documents
Catalogue “Diaphragm seals”
15.2. Related standards
EN 60529:1991/A1:2000 Degrees of protection provided by enclosures (IP Code)
EN 61010-1:2010 Safety requirements for electrical equipment for measurement, control and
laboratory use. General requirements
EN 1092-1:2007 Flanges and their joints –Circular flanges for pipes, valves, fittings and
accessories. –Part 1: Steel flanges.

DTR.PYRP.PYRD.PYRL-28
16. FIGURES
L
L
green - cable shield
_
+
capillary x0,5
black (correspond to terminals "3")
_
+
green - cable shield
10,5...36V DC
R
SUPPLY
DIN 43650 connector with PG-11
PD electrical connector
packing gland IP67 rated
Fig.1a. Wiring diagram for PCE-28, PRE-28 transmitters and PCE-28P probe
Fig.1b. PCE-28 transmitter with PD connector
Functional earth
terminal.
Not to be used
as a protective
terminal.
M20x1,5
25
5
8
2-wire
4...20mA
as in 5.4.1.
or connector
24...20mA
3
1_
+ 15...30V DC15...30V DC
0...10V
3-wire
116 (131-Ex)
3-wire
0...20mA
3
1
2+
Output signal 0...10V
_
+
black (correspond to terminals "2")
red (correspond to terminals "1")
red (correspond to terminals "1")
(output 0...10V, 0...20mA)
blue (correspond to terminals "2")
142
IP67 rated
PK cable connector
PK cable connector, IP67 rated
Fig.1c. PCE-28 transmitter with PK connector - (three-wire transmission 0...10V or 0...20mA).
Fig.1f. PCE-28 transmitter with PM12 connector
of zeroof span
Fig.1e.
(PD, PK or PM12)
View of potentiometers
of zero and span
as in 5.4.1.
or connector
setting
or connector
setting
as in 5.4.1.
for output signal 4...20mA
Fig.1d. PCE-28 transmitter with PK connector
128
diag. 1c or 1d
PM12 cable connector
IP67 rated
cable as in connector PK
L max. by arrangement
L nom. - 3m
1
23
+
0...20mA R
+ _
SUPPLY SUPPLY
(Not applicable to Ex version)
Figure 1. PYRP-28 transmitter with PD, PK and PM12 connectors: dimensions and methods of connection.

DTR.PYRP.PYRD.PYRL-28
Span- setting of span
Zero- setting of zero
terminal
Control
Terminal 2 - Supply "-" (minus)
Terminal 1 - Supply "+" (plus)
Terminal 3 - TEST_SIGNAL
Earthing terminal
Terminal 2 - Output signal
Terminal 1 - Supply "+" (plus)
Terminal 3 - Supply "-" (minus)
Terminals designation to: 0 ... 20mA and 0 ... 10V output signals:
connect a multimeter to control terminals 2 and 3 (max. voltage fall on the milliammeter: 200mV).
Terminals designation to 4 ... 20mA output signal:
To measure the output without disconnecting the signal circuit
internal
IP66 rated
PZ connector
Or connectors
as in 5.4.1.
M20x1,5
packing gland
135
Terminal 2
Terminal 3
Terminal 1
48
110
Figure 2. PYRP-28 transmitter with PZ connector: dimensions and connection method.

DTR.PYRP.PYRD.PYRL-28
15
M30x2
+0,1
1,25
2
diaphragm seal
M20x1.5
25
M20x1,5
5
M30x2
16
2
30°
1,25
M20x1.5
2
min.15
M20x1,5
19
1,25
3
min.15
+0,1
15
diaphragm seal
2
2
M30x2
The ring in Fig.5c must be welded in place with the word TOP upwards
i
TOP
Fig.3a. M connection
with M20x1.5 thread
Fig.3b. Socket for M connection.
Fig.4a. P connection
with M20x1.5 thread
Fig.4b. Socket for P connection
Fig.5a. T connection
with flush diaphragm
with M30x2 thread,
Fig.5b. Socket for
T connection
Fig.5c. Weldable fitting ring for
T connection
Sealing: teflon
Order code Socket T

DTR.PYRP.PYRD.PYRL-28
+1
min.
19
24,5
14,5
-0.5
A
2,5
+0,1
0.5 10,5
Sealing: teflon
0,1 A
33,2 x 36,4 x 1,8
41-6kt.
20.5
10
-0,05
G1"
O-ring
26x2
2,5
O33.5-0,2
+0,1
G1
2,5
90°
2,5
A
+0,1
Sealing: teflon
21,2 x 24,4 x 1,7
0,1 A
20,5-0,1
27-6kt.
O-ring
10
18
15x2
G1/2A
.min
15
21.5
-0,2
-0,2
G1/2
2,5
2,5
90°
G1/2
20
3
G1/2
0.5 15
min.10,5
21,5
-0,2
1,25
Figure 6. Process connections G1/2” and G1”.
Fig.6a. GB connection
with G1/2" thread
Fig.6b. Socket for GB connection.
Fig.6c. GF connection
with flush diaphragm
with G1/2" thread,
Fig.6d. Weldable fitting ring for
GF connection
Order code Socket CG1/2
Fig.6e. GD connection
with flush diaphragm
with G1" thread,
Fig.6f. Weldable fitting ring for
GD connection
Order code Socket CG1

DTR.PYRP.PYRD.PYRL-28
Figure 7. PYRD-28 differential pressure transmitter with PD, PK connectors.
_
+
L
L nom. - 3m
green - cable shield
PK cable connector, IP67
_
capillary x0,5
Lgreen - cable shield
+
with PK connector
PRE-28 transmitter
for output signal 4...20mA
PRE-28 transmitter
(three-wire transmission
with PK connector
0...10V or 0...20mA).
red (correspond to terminals "1")
black (correspond to terminals "2")
blue (correspond to terminals "2")
(output 0...10V, 0...20mA)
PK cable connector
IP67 L max. by arrangement
black (correspond to terminals "3")
red (correspond to terminals "1")
Example connection
Connector to weld
Flat seal
with C type nut 94,5
15
M20x1,5
180
degree of protection IP65
PD electrical connector
DIN 43650 connector with PG-11
PYRD-28 transmitter
with PK connector
(three-wire transmission
0…10V or 0…20mA).
PYRD-28 transmitter
with PK connector for
output signal 4…20mA.

DTR.PYRP.PYRD.PYRL-28
M10 or
DIN 43650 connector with PG-11
PD electrical connector
degree of protection IP65
191
46
185
IP66
PZ connector
packing gland
M20x1,5
155
HL
54
106
41,3
7/16" UNF
4 holes
Figure 8. PYRD-28 differential pressure transmitter with C process connection to be mounted together with valve
manifold.
This manual suits for next models
5
Table of contents
Other Pyropress Transmitter manuals