quiko QK-CE220BATRL User manual

E
N
G
L
I
S
H
I
T
A
L
I
A
N
O
ELECTRONIC CONTROL BOARD FOR
TWO 230VAC MOTORS
g
u
i
d
a
a
l
l
’
i
n
s
t
a
l
l
a
z
i
o
n
e
u
s
e
r
m
a
n
u
a
l
QK-CE220BATRL
WARNING!
Before installing, thoroughly read this manual that is an integral part of this
Kit. QUIKO declines any responsibility in the event current standards in the
country of installation are not complied with
The symbol CE conforms with European Directive R&TTE 99/05CE
ELECTRONIC CONTROL BOARD FOR
TWO 230VAC MOTORS

QK-CE220BATRL ENGLISH
www.quiko.biz 2
1. INTRODUCTION .......................................................................................... 3
2. MAIN FEATURES ........................................................................................ 3
3. TECHNICAL SPECIFICATIONS .................................................................. 3
4. CONNECTION AND SET UP OF THE CONTROL UNIT ............................. 4
4.1 GENERAL DIAGRAM OF SETTINGS AND CONNECTIONS ..................................5
4.2 SIMPLIFIED LEARNING PROCEDURE (also see pages 8-10)..............................6
4.3 PROFESSIONAL LEARNING PROCEDURE (see also pages 8-10)......................7
5. CONTROL UNIT OPERATING LOGIC (ANALYTIC EXAM)........................ 8
5.1 PROGRAMMING AND CANCELLATION OF THE REMOTE CONTROLS .............8
5.2 OPERATION OF THE SAFETY DEVICES ...............................................................8
5.3 TRIMMER “FOR”- MOTOR SPEED .........................................................................9
5.4 TRIMMER “DEL”- DELAY BETWEEN MOTORS ....................................................9
5.5 TRIMMER “PAU” - “OPENING AND CLOSING” OPERATING MODE ..................9
5.6 “PEDESTRIAN OPENING” FUNCTION.................................................................11
5.7 TRIMMER “OBS” - “OBSTACLE SENSITIVITY” DETECTION.............................11
5.8 FLASHING LIGHT ..................................................................................................11
5.9 GATE OPEN WARNING LIGHT .............................................................................11
5.10 SLOW-DOWN .........................................................................................................11
5.11 ELECTRIC LOCK ...................................................................................................12
5.12 COURTESY LIGHT.................................................................................................12
5.13 LOGICAL STOP (STP INPUT)................................................................................12
5.14 CONTROL UNIT MEMORY FAULT........................................................................12
6. SIGNALLING LED ..................................................................................... 12
7. ACCESSORIES ABSORPTION CHECK INFORMATION ......................... 13
8. TROUBLESHOOTING ............................................................................... 14
SAFETY WARNINGS FOR INSTALLATION AND USE ...................................................14
SAFETY WARNINGS FOR INSTALLATION AND USE ...................................................15
1
Stabilimento 2
Via Seccalegno, 19
36040 Sossano (VI) - Italia
Tel: +39 0444 785513 Fax: +39 0444 782371
Quiko
®
è un marchio:
Borinato F.lli Snc
E-mail: info@quiko.biz
Web: www.quiko.biz
Sede legale e stabilimento 1
Via Chiesa, 59
36040 San Germano D.B. (VI) - Italia
Tel: +39 0444 868126 Fax: +39 0444 868126
CONTENTS
INTRODUCTION 2
MAIN FEATURES OF THE CONTROL BOARD 2
TECHNICALDATA 2
INSTALLATION 2
LAYOUT AND CONNECTIONS 3
OTHERSETTINGS 4
RADIORECEIVER SETUP 4
SETUP 5
FINALTESTING 6
TROUBLESHOOTING 6
DECLARATION OF COMPLIANCE 7
QUIKO
®
GUARANTEE: GENERAL CONDITIONS 8

3
E
N
G
L
I
S
H
QK-CE220BATRL ENGLISH
www.quiko.biz 3
1. INTRODUCTION
QK-CE220BATRL is a universal self-learning control unit especially designed for the automatic control of
230VAC powered, 1 or 2 motor driven accesses. It is fitted with an innovative self-learning procedure
allowing rapid installation and four trimmers for fine adjustment of the main parameters; force, pause
time, obstacle detection sensitivity and out of phase closing when two motors are used.
The following are available:
- simplified programming, thanks to which the unit automatically performs a learning operation to acquire
running time and determine slow-down setting at 85% of opening and closing runs;
- A professional programming in which the installer can determine the instant in which the gate starts to
slow-down, the enabling of the pedestrian opening via radio, the safety device trigger mode.
2. MAIN FEATURES
• Management and control of 230VAC (max 400W) powered, 1 or 2 motor-driven automated accesses
• Motors closing offset adjustable from 0 to 15 seconds using trimmers
• Opening motors delay settable at 0 or 3 seconds
• Double limit switch input open close
• Motor force (speed) adjustable from 50-100%.using a trimmer.
• Customisable partial opening (for pedestrian transit)
• 0 to 60” stand-by time adjustment via trimmer.
• 0.1 to 3.0” obstacle detection triggering time adjustment via trimmer.
• Initial settings using dip-switches
• Signalling LEDs (8)
• Handling electric lock 12V 15W max
• Expansion for courtesy light (optional board QK-ELC)
• Built-in 433MHz rolling-code receiver with 180 memorisable codes
• Built-in flashing logic management
• Built to European reference Directive Standards (R&TTE 99/05/CE)
DECLARATION OF CONFORMITY
QUIKO declares that QK-CE220BATRL IS IN ACCORDANCE with the 99/05/EC (R&TTE) direcitve
The complete declaration of conformity is available in QUIKO or to the internet address www.quiko.biz
3. TECHNICAL SPECIFICATIONS
Transformer power supply: primary230 / secondary 18V 20VA / secondary12V 20VA
Control unit power: 230VAC
Motor output: 2 x 400W
Max current peak of motor: Max 8 Ampere
Accessories power: 24 VDC - 500 mA protected by fuse (see info page 13)
Environmental operating temperature : -20°C / + 55°C
Programming parameters: memorised in EEPROM
Functions handler: microprocessor with watch-dog
BOX IP rating: IP54

4
QK-CE220BATRL ENGLISH
www.quiko.biz 4
4. CONNECTION AND SET UP OF THE CONTROL UNIT
a) Before installing the QK-CE220BATRL control unit, read the “General safety warnings
and notes” (page 15).
b) Mount a differential thermo-magnetic circuit breaker 6A (IC=30mA) on the mains supply
as specified in the current reference standards (IC = differential current).
c) * Fix the box using the special fixing holes.
d) * Place the supplied cable-ways and insert the cables keeping the power and supply
cables separate from each other.
e) Connect the motors to the terminal blocks “MOT1” e “MOT2”; if only one motor is used
connect it to the terminal blocks “MOT1”.
f) Connect the external accessories making sure that the total of the average absorption
of all the connected accessories is less than the maximum current available (see info
page 13).
g) ATTENTION: Connect the limit switches if present, otherwise do not bridge inputs
FC1, FC2, FO1, and FO2 in the terminal board.
h) ATTENTION: To avoid noisy or irregular operating when the control panel is used
with hydraulic operators, the following is recommended:
• set the Force to 100% (“FOR” trimmer completely clockwise).
• do not use the slow-down (carry out the professional learning procedure).
• do not use the obstacle detection (trimmer OBS to MAX),
i) During the learning with no electric limit switches present and with the obstacle
detection disabled (e.g. with hydraulic operators), or else with no mechanical
STOP (strike plate) present, to define the manoeuvre times:
• Press pushbutton 1 of the remote control or pushbutton P1/SET to stop the gate in the
desired position.
• Press pushbutton 2 of the remote control or pushbutton P2/SET to stop the gate in the
desired position.
j) Check the correct connection and operation of all the accessories connected to the
terminal board.
INITIAL FACTORY SETTINGS
If there is no programming, the control unit will operate as follows:
• Step by step mode with automatic closing disabled
• No slow-down
• Closing safety present
• No opening safety
• Obstacle detection trigger time (OBS) 1 second
• 3 second opening and closing time of the motors
• Pushbutton 1 of transmitters enabled
• Safety test disabled
• Kick-back disabled

E
N
G
L
I
S
H
QK-CE220BATRL ENGLISH
www.quiko.biz 5
4.1 GENERAL DIAGRAM OF SETTINGS AND CONNECTIONS
NOTE: The control unit is supplied with a trimmer to adjust the force of the motors set on maximum value (100%).
Maintain this setting, which facilitates installation in difficult conditions (worn-out or not lubricated hinges, stress points etc.).
Afterwards, reduce the force to obtain an operator movement that is slower and requires less force. After having adjusted
the force the learning procedure must be repeated.
Flashing Light
230V max 100W
Sock
Condense
r
Condense
r
Pedestrian
opening
STOP
Open/
Step - Step
+-
NC C NO
+-
Mains
230 VAC
Lamp. 230V
max 500W
QK-ELC
AERIAL
PHO and STP inputs – must
be bridged if not used
MOTORS 230VAC
max 400W
230 VAC (MAINS)
Install differential
thermo-magnetic
circuit breaker 6A
(I
=30mA)
LINE FUSE 8A
transformer
230/18-12VAC
FROLUDOM
SIGNALLING LED
Signal
FUSE 2 A
(accessory)
Gate Open LED
24 VDC max 3W
OFF
Photocells
DIP SWITCHES
Electric lock
ON
Closing limit switch motor 1
Opening limit switch motor 1
Closing limit switch motor 2
Opening limit switch motor 2
FORCE /
SPEED
STANDBY
TIME
GATE
DELAY
OBSTACLE
SENSITIVITY
Pushbutton
P2/RADIO
Pushbutton
P1/SET
Pushbutton
OPEN
Pneumatic or
mechanical edge
RX TX
30 31 32 33 34
M1 M2

6
QK-CE220BATRL ENGLISH
www.quiko.biz 6
4.2 SIMPLIFIED LEARNING PROCEDURE (also see pages 8-10)
1. Verify the initial settings.
2. Program the remote controls (if needed) with the gate stopped (green LED GC turned on) according
to the following:
a) Press the program button P2/RAD for two seconds: the red LED “RAD” lights up.
b) Press the desired button on each transmitter.
c) Press the program button P2/RAD to exit the programming mode.
LEARNING START:
Position the
gates half
open
Yellow LED
flashes
Yellow LED stays on
The control unit briefly open
If motors turns in reverse,
invert wires and start
procedure again from
RESET.
Within 5
seconds, press
the programming button
P1/SET for 1 second
Adjust trimmers if necessary
ATTENTION
A variation of trimmer “FOR” (speed)
requires the repetition of the learning procedure
from RESET (the manoeuvre time changes)
Closing.
RESET:
press and hold
the programming
button P1/SET for
2 seconds
1
3
4
5
8
6
7
2
DIP Description DIP STAUS Operation
OFF OFF Button 1 of the TX enabled
OFF ON Button 2 of the TX enabled
ON ON Button 3 of the TX enabled
1, 2 CH. RAD
See pag. 8 ON OFF Button 4 of the TX enabled
OFF Rapid re-closing disabled 3 FAST
See pag. 10 ON Rapid re-closing enabled
OFF Lock stroke disabled 4 STRIKE
See pag. 12 ON Lock stroke enabled
OFF Flashing light fixed 5 LAMP
See pag. 11 ON Flashing light flashing
OFF OPEN/PAUSE/CLOSE Mode 6 STEP
See pag. 9 ON STEP by STEP mode
OFF Automatic closing disabled 7 AUTO
See pag. 9 ON Automatic closing enabled
OFF Safety test disabled
Gate open spy activated
8 PHTEST
See pag. 9
ON Safety test enabled
Gate open spy deactivated
INITIAL SETTINGS OF THE CONTROL UNIT (Dip
-
switches)
1
2
Pause time
(PAU)
Obstacle sensitivity
(OBS)
Leaves delay
(DEL)
TRIMMERS
Reg. from 50 to
100%
Reg. from 0 to
60 sec.
Obstacle
intervention time
from 0,1 to 3 sec.
(At MAX obstacle
detection disabled)
Closing leaves
delay reg.
from 0 to 15 sec. At
MIN delays are
nuls.
Forza/Velocità
(FOR)
Close second gate.
Clo
se first gate.
Opening.
Pause for 1
9
Yellow LED turns off.
End of learning procedure.

7
E
N
G
L
I
S
H
QK-CE220BATRL ENGLISH
www.quiko.biz 7
4.3 PROFESSIONAL LEARNING PROCEDURE (see also pages 8-10)
Using the professional learning procedure the installer can determine:
a) the instant in which the opening and closing slow-down starts
b) the pedestrian function
c) the safety device trigger mode.
When the motor and safety devices are connected and the initial set-up has been completed, programme the
remote controls that will be used (see page 8) with the gate stopped (green LED GC turned on).
Yellow LED
flashes
Yellow LED
stays on
The control unit briefly opens
If motors turns in reverse, invert wires
and start procedure again from RESET.
Closes the secon
d gate
and then the first.
RESET:
press and hold the
programming button
P
1/SET for 2 seconds
Position the
gates half open
Within 5 seconds, press
the programming button
P2/RAD for 1 second
Stop then
invert
Stop then
invert when
cleared
Yellow LED turns off.
End of learning.
When the slow
-
down is to
start press button 1 of a
remote control for leaf 1
and button 2 for leaf 2.
Press P1/SET or
remote control
button 1.
The gate closes
Will pedestrian
function be used?
Press
together
P1/SET and
P2/RAD
Press the button of the remote
control that will be used for the
pedestrian function (different from 1)
Control unit starts pedestrian
opening
Press P1/SET or button 1 of
the remote control to stop
pedestrian opening
Press P1/SET or button 1 of the
remote control
NO
YES
on
ly by
wire
Photocell “PHO”
in closing must:
Press P2/RAD or
button 2 of the
remote control
Opening slow
-
down
Pedestrian function
Safety
intervention in
closing
Safety intervention
in opening
The “EDG” safety in
opening must:
Stop then
open when
cleared
Stop then
invert for 2
sec.
Press P1/SET or
remote control
button 1
Press P2/RAD or
button 2 of the
remote control
Limit switches or mechanical
stop intervention or press
button 1 of a remote control
for leaf 1 and button 2
for leaf 2.
YES
NO
E
nd of opening
When the slow
-
down is to
start press button 1 of a
remote control for leaf 1 and
button 2 for leaf 2.
Closing slow
-
down
Limit switches or mechanical
stop intervention or press
P1/SET for leaf 1 and P2/RAD
for leaf 2.
YES
NO
End of closing
Adjust trimmers if necessary.
ATTENTION
A variation of trimmer “FOR” (speed) requires the repetition
of the learning procedure from RESET
.
MANUAL INTERVENTION TO CHANGE THE FUNCTIONS
YES
by radio
+ by wire
The gate opens
Control unit carries out
STOP and re-closing
Limit switches or mechanical
stop intervention or press
P1/SET for leaf 1 and P2/RAD
for leaf 2.
Limit switches or mechanical
stop intervention or press
button 1 of a remote control
for leaf 1 and button 2
for leaf 2.

8
QK-CE220BATRL ENGLISH
www.quiko.biz 8
5. CONTROL UNIT OPERATING LOGIC (ANALYTIC EXAM)
5.1 PROGRAMMING AND CANCELLATION OF THE REMOTE CONTROLS
With the receiver built into the control box, QUIKO dip-switch, fixed code and rolling code remote controls can
be indifferently learned.
5.1.1 Programming
Power the control panel and with the automation stopped (green LED GC turned on):
• Press the “P2/RAD” pushbutton: the red LED lights up to indicate that the programming is activated.
• Make a transmission by pressing one of the pushbuttons on the transmitter
• The code is memorised. During code insertion, the red LED flashes slowly. At the end, the red LED returns
to a fixed light to indicate that a new remote control can be inserted.
• Memorise all the transmitters by carrying out a transmission with a chosen channel.
• At the end of the operation press the “P2/RAD” pushbutton again to exit the procedure. The red LED
switches off.
ATTENTION: The exit from the procedure occurs automatically 10 seconds after the last transmission.
5.1.2 Total cancellation of the codes
• Press and hold down the “P2/RAD” pushbutton for 3 seconds; the red LED starts flashing quickly.
• Press the “P2/RAD” pushbutton again (within 6 seconds) to confirm the cancellation. The confirmation is
signalled when the red LED starts flashing more rapidly.
5.1.3 Choosing the transmitter pushbutton
To select the radio channel that will activate the manoeuvre cycle set DIP 1 and 2 as follows:
DIP- SWITCH 1 DIP- SWITCH 2 Pushbutton Active
OFF OFF Pushbutton 1
OFF ON Pushbutton 2
ON ON Pushbutton 3
ON OFF Pushbutton 4
5.2 OPERATION OF THE SAFETY DEVICES
5.2.1 Photocell (PHO input)
When triggered, the photocell provokes:
- in closing phase, an inversion of the motion, either immediate or when cleared, according to the programming,
- in opening phase it has no effect,
- when the access is closed it has no effect on the opening commands if set for immediate inversion,
otherwise it delays the opening until it is cleared,
- if the access is open it inhibits the closing commands.
The control unit has a function of rapid access closing after the triggering of the photocell (see paragraph 5.3.4).
5.2.2 Safety in Opening (EDG input)
Safety devices can be connected (self-testing or not) to the “EDG” input on the control unit (e.g. fixed wire ribs,
pneumatically-operated ribs, etc.).
The safety acts as follows:
- in closing phase it has no effect
- in opening phase it provokes an inversion of direction for 2 seconds,
- when the gate is closed the opening commands are inhibited,

9
E
N
G
L
I
S
H
QK-CE220BATRL ENGLISH
www.quiko.biz 9
- when the gate is open the closing commands are inhibited,
Using the professional learning, the PED input can be set as internal photocell:
- in closing phase it provokes an inversion of direction when cleared,
- in opening phase it provokes a STOP and opening continues when cleared,
- when the gate is closed it delays opening until it is cleared,
- when the access is open it inhibits the closing commands.
5.2.3 Safeties Self-test
The control unit has a self-test function of the safeties connected to the “PHO” input of the control unit; it
switches off the transmitter to check the commutation of the corresponding receiver contact before the
execution of each manoeuvre. In this case, the “gate open warning light” is not available.
To activate this self-test function proceed as follows:
- switch DIP 8 “PTST” to ON
- connect the positive of the photocell transmitter power to terminal 10 (“+TX”)
With the Self-test function active the photocell transmitters are only powered when the manoeuvre is
taking place, thus giving a major saving of energy.
If the enabling of the safety self-test is not required
- switch DIP 8 “PTST” to OFF
- connect the positive of the photocell transmitter power to the terminal 11 (“+V”)
5.3 TRIMMER “FOR”- MOTOR SPEED
Trimmer “FOR” adjusts the voltage applied to the motors during operations, which means adjusting the speed of
the motors. With the trimmer turned fully counter-clockwise the speed of the motor if 50% of the maximum
speed. With the trimmer at half travel the speed of the motor if 75% of the maximum speed.
ATTENTION: Changing the setting of trimmer “FOR” requires repeating the learning procedure, since
the travel times and the slow-down start times change.
EXAMPLE
Force/Speed 50%
EXAMPLE
Force/Speed 75%
EXAMPLE
Force/Speed 100%
5.4 TRIMMER “DEL”- DELAY BETWEEN MOTORS
Trimmer “DEL” can be used to adjust the delay between the two motors in opening and closing operations.
If the trimmer is turned fully counter-clockwise, the delay is 0 both in opening and in closing, and the two leaved
will move together.
In all the other positions of the trimmer, the delay in opening is 3 seconds and the delay in closing varies from 0
to 15 seconds according to the position of the knob.
EXAMPLE
delay 0 in opening
delay 0 in closing
EXAMPLE
delay 3 seconds in opening
delay 7 seconds in closing
EXAMPLE
delay 3 seconds in opening
delay 15 seconds in closing
5.5 TRIMMER “PAU” - “OPENING AND CLOSING” OPERATING MODE
5.5.1 Time controlled automatic closing mode
Switch the dip-switch 7 to ON and the dip-switch 6 to OFF.
Set the “ PAU ” trimmer in an intermediate position according to the pause time desired. The pause time can be
set between 3 and 60 seconds and is increased by rotating the trimmer clockwise.
EXAMPLE
pause time about 1 sec.
EXAMPLE
pause time about 30 sec.
EXAMPLE
pause time about 60 sec.
In this mode, if a command is received via radio or via the “STR” input, the control unit does the following:
- carries out a fixed one second pre-flash

10
QK-CE220BATRL ENGLISH
www.quiko.biz 10
drives the two motors without 2nd motor delay if the DEL trimmer is turned fully counter-clockwise, with a 2nd
motor delay of 3 seconds for all the other positions of the DEL trimmer.
- activates the operator for one second at maximum speed and then at the speed set with the “FOR” trimmer.
- the opening terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed. If other commands are given during opening, they will have no effect.
- with the automation stopped and in automatic standby each time the timer restarts from zero.
When the standby time has elapsed, the closing manoeuvre occurs and the control unit:
- carries out a fixed one second pre-flash
- drives the two motors with a 2nd motor delay as set on the DEL trimmer
- if other commands are issued during closure, the control unit carries out a complete re-opening.
- the closure terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed.
ATTENTION: Maintaining the opening contact (“STR” terminal) closed, with a temporised relay for
example, the control unit will command opening and the automation will remain open with automatic
closing disabled until the contact is re-opened again (Company Function).
5.5.2 Step by step mode without automatic closing
Switch the dip-switch 6 to ON and the dip-switch 7 to OFF.
The step by step command sequence is OPEN-STOP-CLOSE-STOP
The opening and closing manoeuvres take place as described in the previous paragraph.
5.5.3 Step by step mode with automatic closing
Switch the dip-switch 6 to ON and the dip-switch 7 to ON.
The step-step logic is OPEN/STOP/CLOSE/STOP.
When the opening manoeuvre has been completed and the pause time set on the PAU trimmer has elapsed the
control unit effects automatic closing.
If, when the automation is closed, a radio command is given, either through the “STR” input command or the
START pushbutton on the board, the control unit:
- commands a one second fixed pre-flash
drives the two motors without 2nd motor delay if the DEL trimmer is turned fully counter-clockwise, with a 2nd
motor delay of 3 seconds for all the other positions of the DEL trimmer.- the opening terminates when the limit
switch or the obstacle detection device are triggered, the manoeuvre time has elapsed or there is a radio or
manual command. In the latter case, the control unit disables the automatic closing and to restart the
manoeuvre, a further command is required.
If the automation is completely open, once the standby time has elapsed the closing manoeuvre occurs and the
control unit:
- carries out a fixed one second pre-flash.
- drives the two motors with a 2nd motor delay as set on the DEL trimmer
- the closing terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed.
5.5.4 Automatic closing and rapid re-closing mode
Switch the dip-switch 6 to OFF and the dip-switch 7 to ON.
Switch the dip-switch 3 to ON.
The control unit does the following:
a) if the photocell is triggered during opening, the control unit continues the opening, and when the photocell is
cleared effects a STOP followed, after one second, by the re-closure.
b) if the photocell is triggered during standby with the gate open, when the photocell is cleared, after one
second, automatic re-closure occurs.
c) if the photocell is triggered during closure, the control unit effects an inversion and, when the photocell is
cleared, it effects a STOP followed, after one second, by the re-closure.
If, during the opening cycle or during standby, the photocell is not triggered, the pause time is that which is set
with the “PAU” trimmer.
5.5.5 OPEN-CLOSE-OPEN mode
Switch the dip-switch 6 to OFF and the dip-switch 7 to OFF.
If, when the automation is closed, a radio command is given, either through the “STR” input command or the
START pushbutton on the board, the control unit:
- commands a one second fixed pre-flash
- drives the two motors without 2nd motor delay if the DEL trimmer is turned fully counter-clockwise, with a 2nd
motor delay of 3 seconds for all the other positions of the DEL trimmer.
- the opening terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed. If other commands are given during opening, they will not have any effect.
When the automation is completely open, to start the closing manoeuvre give a radio or manual command and
the control unit:

11
E
N
G
L
I
S
H
QK-CE220BATRL ENGLISH
www.quiko.biz 11
- carries out a fixed one second pre-flash
- drives the two motors with a 2nd motor delay as set on the DEL trimmer
- if a command is issued during closure, the control unit carries out a complete re-opening.
- the closure terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed.
5.6 “PEDESTRIAN OPENING” FUNCTION
The pedestrian function can be assigned with the professional learning to channel 2/3/4 of the remote control.
With a “PEDESTRIAN OPENING” (“EDG” terminal) command on the input, the control unit commands an
opening for the first leaf for a time of:
- 5 seconds if no learning has been carried out,
- half of the course if a simplified learning has been carried out
- that set by the installer if a professional learning has been carried out.
Closing is triggered by a manual command, or automatically if the automatic closing function is enabled. The complete
opening command has always priority over the pedestrian opening, therefore if, during a pedestrian manoeuvre a
complete opening command is received, the control unit will command a complete opening of the automation.
5.7 TRIMMER “OBS” - “OBSTACLE SENSITIVITY” DETECTION
The “OBS” TRIMMER is used to adjust at the same time the delay time of intervention after an obstacle has
been detected and the threshold of the counter-force against the operator necessary to trigger the intervention.
Both the counter-force and the delay time increase when the trimmer is turned clockwise. The delay time
can be adjusted between 0.1 and 3 seconds. This function is useful to overcome any critical points of the
operator which cause a higher power absorption by the motor for a short time.
EXAMPLE
delay time about 0,1 sec.
EXAMPLE
delay time about 1,5 sec.
EXAMPLE
delay time about 3 sec.
If the OBS trimmer is in the MAX position, the obstacle detection is disabled.
If electric limit switches are present, the obstacle detector will provoke an inversion of the motion in closing
and a 2 second inversion in opening.
If there are no electric limit switches the obstacle detector provokes:
- in closing an inversion of the motion unless it is in the last five seconds of the manoeuvre, where does a STOP
- in opening an inversion of the motion for 2 seconds unless it is in the last five seconds of the manoeuvre,
where does a STOP.
5.8 FLASHING LIGHT
The control unit has two output terminals (LAMP) to command a low voltage flashing light. The light start flashing 1
second before each opening manoeuvre and 1 second before each closing manoeuvre.
If the dip-switch 5 is in the OFF position the power supply to the flashing light is continuous. Therefore the terminals
must be connected to a low voltage flashing light with a built-in oscillating circuit.
If the dip-switch 5 is in the ON position the power supply is intermittent and therefore a normal lamp without
oscillating circuit can be connected (230VDC, Max 10W). During the closing manoeuvre, the flashing frequency
is twice as fast as that during opening.
The flashing light is only activated during movement.
5.9 GATE OPEN WARNING LIGHT
If the safety device self-test is not used (DIP 8 “PTST” is OFF), the output +TX (terminal 10) acts as a GATE
OPEN WARNING LIGHT. You can connect a 24V lamp (max. 3W) to terminals 10 (“+TX”) and 9 (“COMMON”)
of the control unit. The status of the lamp is as follows:
- If the access is closed the light is switched off
- If the access is open or opening the lamp is alight with a fixed light
- If the access is closing the lamp flashes
5.10 SLOW-DOWN
The slow-down function allows the gate to apply a reduced force before reaching the limit stop. The speed is
reduced to about one third of the normal working speed.
The slow-down function can be enabled or not during the Professional Learning procedure. The moment in
which the slow-down starts can be differentiated between the opening and the closure.
QK-CE220BATRL ENGLISH
www.quiko.biz 10
drives the two motors without 2nd motor delay if the DEL trimmer is turned fully counter-clockwise, with a 2nd
motor delay of 3 seconds for all the other positions of the DEL trimmer.
- activates the operator for one second at maximum speed and then at the speed set with the “FOR” trimmer.
- the opening terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed. If other commands are given during opening, they will have no effect.
- with the automation stopped and in automatic standby each time the timer restarts from zero.
When the standby time has elapsed, the closing manoeuvre occurs and the control unit:
- carries out a fixed one second pre-flash
- drives the two motors with a 2nd motor delay as set on the DEL trimmer
- if other commands are issued during closure, the control unit carries out a complete re-opening.
- the closure terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed.
ATTENTION: Maintaining the opening contact (“STR” terminal) closed, with a temporised relay for
example, the control unit will command opening and the automation will remain open with automatic
closing disabled until the contact is re-opened again (Company Function).
5.5.2 Step by step mode without automatic closing
Switch the dip-switch 6 to ON and the dip-switch 7 to OFF.
The step by step command sequence is OPEN-STOP-CLOSE-STOP
The opening and closing manoeuvres take place as described in the previous paragraph.
5.5.3 Step by step mode with automatic closing
Switch the dip-switch 6 to ON and the dip-switch 7 to ON.
The step-step logic is OPEN/STOP/CLOSE/STOP.
When the opening manoeuvre has been completed and the pause time set on the PAU trimmer has elapsed the
control unit effects automatic closing.
If, when the automation is closed, a radio command is given, either through the “STR” input command or the
START pushbutton on the board, the control unit:
- commands a one second fixed pre-flash
drives the two motors without 2nd motor delay if the DEL trimmer is turned fully counter-clockwise, with a 2nd
motor delay of 3 seconds for all the other positions of the DEL trimmer.- the opening terminates when the limit
switch or the obstacle detection device are triggered, the manoeuvre time has elapsed or there is a radio or
manual command. In the latter case, the control unit disables the automatic closing and to restart the
manoeuvre, a further command is required.
If the automation is completely open, once the standby time has elapsed the closing manoeuvre occurs and the
control unit:
- carries out a fixed one second pre-flash.
- drives the two motors with a 2nd motor delay as set on the DEL trimmer
- the closing terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed.
5.5.4 Automatic closing and rapid re-closing mode
Switch the dip-switch 6 to OFF and the dip-switch 7 to ON.
Switch the dip-switch 3 to ON.
The control unit does the following:
a) if the photocell is triggered during opening, the control unit continues the opening, and when the photocell is
cleared effects a STOP followed, after one second, by the re-closure.
b) if the photocell is triggered during standby with the gate open, when the photocell is cleared, after one
second, automatic re-closure occurs.
c) if the photocell is triggered during closure, the control unit effects an inversion and, when the photocell is
cleared, it effects a STOP followed, after one second, by the re-closure.
If, during the opening cycle or during standby, the photocell is not triggered, the pause time is that which is set
with the “PAU” trimmer.
5.5.5 OPEN-CLOSE-OPEN mode
Switch the dip-switch 6 to OFF and the dip-switch 7 to OFF.
If, when the automation is closed, a radio command is given, either through the “STR” input command or the
START pushbutton on the board, the control unit:
- commands a one second fixed pre-flash
- drives the two motors without 2nd motor delay if the DEL trimmer is turned fully counter-clockwise, with a 2nd
motor delay of 3 seconds for all the other positions of the DEL trimmer.
- the opening terminates when the limit switch or the obstacle detection device are triggered or the manoeuvre
time has elapsed. If other commands are given during opening, they will not have any effect.
When the automation is completely open, to start the closing manoeuvre give a radio or manual command and
the control unit:

12
QK-CE220BATRL ENGLISH
www.quiko.biz 12
5.11 ELECTRIC LOCK
There is an output (EL) for the electric lock 12V max 15VA. The command is given before every opening
manoeuvre for 2 seconds, and before every re-opening caused by the triggering of a photocell or safety device.
Using dip-switch 4 on the card, the kick-back and the final stroke at the end of the closing manoeuvre can be
enabled or not.
Dip-switch 4 in ON position: kick-back and final stroke enabled
Dip-switch 4 in OFF position: kick-back and final stroke disabled.
5.12 COURTESY LIGHT
Using the QK-ELC expansion card a courtesy light can be managed. The contact given by the LCU card is
clean and allows a 230VAC max.500W lamp to be managed. The command to switch on the courtesy light is
given before every manoeuvre and the contact remains activated for about 120 seconds from opening.
5.13 LOGICAL STOP (STP INPUT)
The activation of the STOP input stops all the functions.
To resume the cycle the STOP must be deactivated and another command given.
5.14 CONTROL UNIT MEMORY FAULT
The EEPROM memory contains the control unit operating parameters, the codes, the logic and the memory of
the radio receiver. When the control unit is turned on, should there be a fault in the EEPROM memory, the red
LED flashes and all manoeuvres are blocked.
The Reset function must be executed (press and hold the programming button P1/SET for 2 seconds, until the
yellow LED flashes).
If the red LED turns of, the EEPROM is good, but all programming of parameters and learning of transmitters
must be done again.
If the red LED still flashes, an authorised service centre should be contacted.
6. SIGNALLING LED
Yellow led SET:
- flashes for 5 seconds when turned on to indicate that it is possible to enter the Professional or Simplified
Learning modes.
- lights up with a fixed light while Professional or Simplified Learning are carried out.
- is turned off when the control unit functions normally.
Red led ER:
- is turned off during normal control unit operations
- is alight (fixed light) when the control unit is blocked because it has failed the safety test or there is a TRIAC in
short circuit or a motor is disconnected
Red led RAD:
- flashes briefly when a 433 MHz Multipass radio code is received
- is alight (fixed light) when radio codes are being memorised
- flashes rapidly when the control unit is switched on and the radio code memory is defective
- flashes rapidly during the cancellation of radio codes
- flashes slowly when there is an attempt to memorise new radio codes and the memory is full
- is switched off when the control unit is functioning normally and waiting to receive a command via radio.
Green led GC:
- is alight (fixed light) when the automation is completely closed
- flashes during the closing manoeuvre
- otherwise it is switched off
Red led GO:
- is alight (fixed light) when the automation is open.
- flashes during the opening manoeuvre
- otherwise it is switched off
Red led PH:
- is alight when the photocell (PHO input) is aligned
- is switched off when the photocell (PHO input) is not aligned
Red led ST:
- is alight when the STOP (STP) input is closed
- is switched off when the STOP (STP) input is open.
Green led START:
- is alight when the OPEN/STEP/STEP (STR) input is closed.
- is switched off when the OPEN/STEP/STEP (STR) input is open.

13
E
N
G
L
I
S
H
QK-CE220BATRL ENGLISH
www.quiko.biz 13
7. ACCESSORIES ABSORPTION CHECK INFORMATION
(Transformer dimensioning)
The current available for the accessories is given by the power available for the accessories divided by the
voltage of the accessories 24VDC.
Iacc = Pacc / 24
The power available for the accessories is given by the transformer power, less the power absorbed by the
control unit (8W).
Pacc = Ptras – 8
On board the control unit, there is a 20VA transformer for which the available power is 12W and the available
current is 500mA as described in the technical characteristics.
Below un example of calculation of the current available for the accessories.
QK-
CE220BATRL
20VA 6.4W 13.6W 24V 560mA
Ptras = transformer power
Pmot = motor power
Iacc = current available for accessories
Pacc = power available for accessories

14
14
8. TROUBLESHOOTING
PROBLEM PROBABLE CAUSE REMEDY
230 volt mains voltage absent Check master switch
Emergency STOP present Check for any STOP commands
connected to the STP input.
There is no jumper between the STP
input and the common.
If not used, check if there is a
jumper on the STP input.
One of the fuses is burnt out. Replace the fuse with one of the
same value.
On giving a command with the
remote control or with the key-
switch, the gate does not open.
Motor power cable not connected or
faulty.
Check the connection of the cable
in the terminal board or replace it.
The photocell, if present, is
obstructed or not functioning.
Check, clean the photocell or
remove the obstacle.
The photocell is missing and there
is no jumper between the PHO input
and the common.
Check the accessory connections
and the presence of the “jumper”.
The gate opens but does not close.
A key selector NC contact has been
used instead of an NO contact to
connect to the STR input
Check the connections.
The operator functions by wire but
not with the remote control.
The remote control has not been
memorised or is broken or the
battery is flat.
Check/change the battery.
Carry out the remote control
acknowledgement procedure.
The electrical limit switch activates
but the motor does not stop.
The opening and closing limit
switches have been exchanged.
An NO contact has been used
instead of an NC.
Check the connections.
Check if the leaves are in axis,
lubricate if necessary.
Increase the trigger threshold by
turning the OBS trimmer clockwise.
The gate moves then stops, both in
opening and closing.
The motor force is insufficient
and/or the trigger threshold of the
OBS is too low.
If it is not sufficient, increase the
FOR trimmer clockwise and
reprogram from RESET
Remove any obstacles from the
gate; restore the hinges, replace or
lubricate them.
When commanded, the motor starts
but the gate does not move.
There is an obstacle in front of the
gate; the hinges are blocked; a
motor fixing bracket has detached. Fix the motor fixing bracket.
N.B.: If the problem persists, contact your Retailer or the nearest Service Centre.
ATTENTION: Before sending a remote control to be repaired, check that the batteries are not flat.
50% of all remote controls that return for servicing only have flat batteries.

15
E
N
G
L
I
S
H
15
SAFETY WARNINGS FOR INSTALLATION AND USE
These warnings are an essential, integral part of the product and must be given to the user. They provide
important indications on the installation, use and maintenance and must be read carefully. This form must be
preserved and passed on to subsequent users of the system. The incorrect installation or improper use of
the product may be dangerous.
INSTALLATION INSTRUCTIONS
• The installation must be performed by professionally skilled personnel and in compliance with current
local, state, national and European legislation.
• Before beginning the installation, check the integrity of the product.
• The laying of cables, electrical connections and adjustments must be workmanlike performed.
• The packing materials (cardboard, plastic, polystyrene, etc.) are a potential hazard and should be
disposed of correctly and not left within reach of children.
• Do not install the product in potentially explosive environments or environments disturbed by
electromagnetic fields. The presence of inflammable gases or fumes is a grave danger to safety.
• Set up a safety device for overvoltage, a disconnecting and/or differential switch suitable for the product
and conforming to current standards.
• The manufacturer declines any and all responsibility for product integrity, safety and operation in the
event incompatible devices and/or components are installed.
• Solely original spare parts should be used for repairs and replacements.
• The installer must provide all the information relative to the operating, maintenance and use of the
individual components and the complete system as specified in the MACHINE LEGISLATION (see
regulations EN 12635, EN 12453 and EN 12445).
MAINTENANCE
• To ensure product efficiency, it is essential that professionally skilled personnel carry out maintenance
within the times established by the installer, the manufacturer and by current legislation.
• All installation, maintenance, repairs and cleaning operations must be documented. This documentation
must be preserved by the user, and made available to the personnel responsible for the control.
WARNINGS FOR THE USER
• Read the instructions and enclosed documentation carefully.
• The product must be used for the express purpose for which it was designed. Any other use is
considered improper and therefore hazardous. In addition, the information given in this document and in
the enclosed documentation may be subject to modifications without prior notice. It is given as an
indication only for product application. QUIKO declines any responsibility for the above.
• Keep products, devices, documentation and anything else provided out of reach of children.
• In the event of maintenance, cleaning, breakdown or faulty operation of the product cut off the power
and do not attempt to operate on the product except when indicated. Contact professional personnel,
competent and suitable for the task. Failure to adhere to the above indications may be dangerous.
WARRANTY LIMITS
The warrantee is valid for 24 months from the date indicated in the sales document and its validity is limited
to the original purchaser. It does not cover the following eventualities: negligence, incorrect or improper use
of the product, use of accessories not conforming to the manufacturer's specifications, tampering by the
customer or third parties, natural causes (lightning, floods, fire, etc.), riots, vandalism, modifications to the
environmental conditions of the installation site. Nor does the warranty cover parts subject to wear (batteries,
oil etc.). Products returned to QUIKO for repair shall only be accepted carriage paid. QUIKO shall return the
repaired product to the sender carriage forward. Otherwise the goods will be refused on receipt. The
purchase of the product implies the full acceptance of all the general terms of sale. Any dispute shall be
submitted for judgement to the Court of Vicenza.

m
a
n
u
a
l
e
d
’
u
s
o

I
T
A
L
I
A
N
O
m
a
n
u
a
l
e
d
’
u
s
o
QK-CE220BATRL
QUADRO ELETTRONICO DI COMANDO PER DUE MOTORI 230VAC
MANUALE TECNICO DI INSTALLAZIONE
ATTENZIONE!
Prima di effettuare l’installazione, leggere attentamente questo manuale.
La QUIKO declina ogni responsabilità in caso di non osservanza delle
normative vigenti nel Paese dove viene effettuata l’installazione
Il marchio CE è conforme alla direttiva europea R&TTE 99/05CE
QUADRO ELETTRONICO DI COMANDO
PER DUE MOTORI 230VAC

1
Stabilimento 2
Via Seccalegno, 19
36040 Sossano (VI) - Italia
Tel: +39 0444 785513 Fax: +39 0444 782371
Quiko
®
è un marchio:
Borinato F.lli Snc
E-mail: info@quiko.biz
Web: www.quiko.biz
Sede legale e stabilimento 1
Via Chiesa, 59
36040 San Germano D.B. (VI) - Italia
Tel: +39 0444 868126 Fax: +39 0444 868126
SOMMARIO
INTRODUZIONE 2
CARATTERISTICHE PRINCIPALI DELLA SCHEDA 2
CARATTERISTICHE TECNICHE 2
INSTALLAZIONE 2
COLLEGAMENTI E SETTAGGI 3
SETTAGGIVARI 4
PROGRAMMAZIONE RADIORICEVENTE 4
PROGRAMMAZIONE 5
COLLAUDO 6
POSSIBILI ANOMALIE E SOLUZIONI 6
DICHIARAZIONE DI CONFORMITA’ 7
GARANZIA QUIKO
®
: CONDIZIONI GENERALI 8
QK-CE220BATRL ITALIANO
www.quiko.biz 2
1. INFORMAZIONI GENERALI........................................................................ 3
2. CARATTERISTICHE PRINCIPALI............................................................... 3
3. CARATTERISTICHE TECNICHE................................................................. 3
4. COLLEGAMENTO E MESSA IN FUNZIONE DELLA CENTRALE..............4
4.1 SCHEMA GENERALE SETTAGGI E COLLEGAMENTI..........................................5
4.2 PROCEDURA DI APPRENDIMENTO SEMPLIFICATA (vedi anche pagg. 8-10) ........6
4.3 PROCEDURA DI APPRENDIMENTO PROFESSIONALE (vedi anche pagg. 8-10) .... 7
5. LOGICA DI FUNZIONAMENTO DELLA CENTRALE (esame analitico) ....8
5.1 PROGRAMMAZIONE E CANCELLAZIONE DEI RADIOCOMANDI........................8
5.2 FUNZIONAMENTO DELLE SICUREZZE .................................................................8
5.3 TRIMMER “FOR”- FORZA/VELOCITA’ MOTORI....................................................9
5.4 TRIMMER “DEL”- SFASATURA MOTORI...............................................................9
5.5 TRIMMER “PAU”- MODALITÀ DI FUNZIONAMENTO “APERTURA E CHIUSURA”..9
5.6 FUNZIONE “APERTURA PEDONALE”.................................................................10
5.7 TRIMMER “OBS”- RILEVAMENTO “SENSIBILITÀ OSTACOLO” .......................11
5.8 LAMPEGGIATORE.................................................................................................11
5.9 SPIA CANCELLO APERTO ...................................................................................11
5.10 RALLENTAMENTO ................................................................................................11
5.11 ELETTROSERRATURA .........................................................................................11
5.12 LUCE DI CORTESIA...............................................................................................11
5.13 STOP LOGICO (INGRESSO STP) .........................................................................12
5.14 ANOMALIA MEMORIA DELLA CENTRALE..........................................................12
6. LED DI SEGNALAZIONE .......................................................................... 12
7. INFORMAZIONI VERIFICA ASSORBIMENTO ACCESSORI.................... 13
8. INCONVENIENTI – CAUSE E RIMEDI ...................................................... 14
AVVERTENZE SICUREZZA PER INSTALLAZIONE ED USO.........................................15

3
I
T
A
L
I
A
N
O
QK-CE220BATRL ITALIANO
www.quiko.biz 3
1. INFORMAZIONI GENERALI
La centrale universale autoapprendente QK-CE220BATRL è stata ideata per l’automazione di un accesso ad 1
o 2 motori 230VAC con o senza finecorsa elettrici. E’ dotata di un’innovativa procedura di autoapprendimento
per una rapida installazione e di quattro trimmer per la regolazione fine dei parametri principali; forza,
tempo di pausa, sensibilità del controllo ostacolo e sfasatura tra i due motori.
Sono disponibili:
- una programmazione autoapprendente rapida, in cui la centrale esegue automaticamente la manovra di
apprendimento dei tempi di manovra e fissa l’inizio del rallentamento sia in apertura che in chiusura al 85%
della manovra.
- una programmazione professionale in cui l’installatore può determinare l’istante di inizio del
rallentamento delle ante, l’abilitazione dell’apertura pedonale via radio, la modalità di intervento dei
dispositivi di sicurezza.
2. CARATTERISTICHE PRINCIPALI
• Comando e controllo di accessi automatizzati ad 1 o 2 motori 230VAC (max 400W)
• Sfasatura motori in chiusura regolabile tramite trimmer tra 0 e 15 secondi
• Sfasatura motori in apertura impostabile a 0 o 3 secondi
• Doppio ingresso finecorsa apre chiude
• Velocità motore regolabile tramite trimmer da 50-100%.
• Apertura parziale (pedonale) personalizzabile
• Tempo di sosta regolabile tramite trimmer da 0 a 60 secondi.
• Tempo di intervento del controllo ostacolo regolabile tramite trimmer tra 0,1 e 3,0 secondi.
• Settaggi iniziali tramite dip-switch
• LED di segnalazione (8)
• Gestione diretta elettroserratura 12V 15W con relè dedicato
• Espansione per luce di cortesia (accessorio opzionale QK-ELC)
• Ricevitore rolling-code a 433MHz incorporato con 180 codici radio memorizzabili
• Gestione logica lampeggiante incorporata
• Conforme alle Direttive Europee di riferimento:R&TTE 99/05/CE
DICHIARAZIONE DI CONFORMITA'
La QUIKO dichiara che QK-CE220BATRL E' CONFORME ai requisiti essenziali della direttiva 99/05/EC
(R&TTE)
3. CARATTERISTICHE TECNICHE
Alimentazione trasformatore: primario 230 / secondario 18V 20VA / secondario12V 20VA
Alimentazione centrale: 230VAC
Uscita motore: 2 x 400W
Assorbimento max motore e accessori: Max 8 Ampere
Alim. accessori: 24 VDC - 500 mA (vedi info pag. 13)
Temperatura ambiente di funzionamento: -20°C / + 5 5 °C
Parametri di programmazione: memorizzati in EEPROM
Gestore delle funzioni: microprocessore con watch-dog
Grado IP del box IP54

4
QK-CE220BATRL ITALIANO
www.quiko.biz 4
4. COLLEGAMENTO E MESSA IN FUNZIONE DELLA CENTRALE
a) Prima di eseguire l’installazione della centrale QK-CE220BATRL leggere le “Avvertenze
generali per la sicurezza e note” (pag. 15).
b) Prevedere sulla rete di alimentazione un interruttore magnetotermico differenziale da 6A
(IC=30mA) come previsto dalle vigenti normative di riferimento (IC=corrente
differenziale).
c) * Fissare il box tramite gli appositi fori di fissaggio.
d) * Innestare i passacavi in dotazione e fare passare i cavi tenendo separati quelli di
potenza da quelli di comando.
e) Collegare i motori ai morsetti “MOT1” e “MOT2”, se si impiega un solo motore va
collegato ai morsetti “MOT1”.
f) Collegare gli accessori esterni facendo attenzione che la somma degli assorbimenti
medi di tutti gli accessori collegati non superi la massima corrente disponibile (vedi info
pag. 13).
g) ATTENZIONE!: Collegare i finecorsa se presenti, altrimenti non ponticellare gli
ingressi FC1, FC2, FO1 ed FO2 in morsettiera.
h) ATTENZIONE!: Se la centrale viene utilizzata con motori oleodinamici per evitare
funzionamenti rumorosi e irregolari si consiglia:
• di porre la Forza al 100% (Trimmer “FOR” tutto in senso orario)
• di non utilizzare il rallentamento (eseguire procedura di apprendimento
professionale)
• di non utilizzare il controllo ostacolo (trimmer OBS al MAX),
i) Durante l’apprendimento in mancanza di finecorsa elettrici e con il rilevamento
ostacolo escluso (ad esempio con motori oleodinamici), oppure in assenza di
STOP meccanico (battuta), per definire i tempi di manovra:
• Premere il pulsante 1 del telecomando o il pulsante P1/SET per fermare la prima anta
dove richiesto.
• Premere il pulsante 2 del telecomando o il pulsante P2/RAD per fermare la seconda
anta dove richiesto.
j) Verificare il corretto collegamento e funzionamento di tutti gli accessori collegati in
morsettiera.
SETTAGGI INIZIALI PREIMPOSTATI
Se non vengono eseguite programmazioni, la centrale si comporta nel seguente modo:
• Modalità passo-passo con chiusura automatica esclusa
• Nessun rallentamento
• Presenza sicurezza in chiusura
• No sicurezza in apertura
• Tempo intervento rilevamento ostacolo (OBS) 1 secondo
• Sfasamento dei motori pari a 3 secondi sia in apertura che in chiusura
• Canale 1 dei radiocomandi abilitato per l’apertura totale
• Test sicurezze disabilitato
• Colpo d’ariete disabilitato
Table of contents
Languages:
Other quiko Controllers manuals
Popular Controllers manuals by other brands

Chamberlain
Chamberlain LA400UL Wiring diagram

Honeywell
Honeywell ComfortPoint Open CPO-VAV2A installation instructions

Siemens
Siemens GCA 1 Series Mounting instructions

hanshow
hanshow HS C09978 product manual

Truma
Truma DuoControl vertical operating instructions

HB-THERM
HB-THERM M8155-EN Assembly instructions

Resol
Resol DeltaSol MX Manual for the specialised craftsman

Eaton
Eaton SONIX 2Mx Technical manual

Staubli
Staubli CS8C instruction manual

Deep Sea Electronics Plc
Deep Sea Electronics Plc 5320 Installation instructions and instructions for use

Vita Spa
Vita Spa L700C Series owner's manual

artisan
artisan cFP-2200 Operating instructions and specifications