Rain Bird IC-TFU User manual

Rain Bird® IC-TFU
Transition Field Upgrade Device
Installation Guide
CONNECT to convert

2
IC
-
TFU
Installation Guide
Reference Documents ..................................................................................................... 3
IMPORTANT NOTES: Installing the IC-TFU – Transition Field Upgrade Device ............ 4
Installation Checklist........................................................................................................ 5
Verify Compatibility with Rain Bird Central Control Software .......................................... 6
Choose Location to Install the IC-TFU ............................................................................ 7
Gather Installation Tools / Other Materials Required ...................................................... 7
Installation Step #1 – Connect IC-TFU Output wires to a DC Latching Solenoid ............ 8
Installation Step #2 – Connect to MAXI™ wire .............................................................. 10
Installation Step #3 - Complete Field Installation .......................................................... 12
Installation Step #4 - Configure Rain Bird Central Control Software ............................. 14
IC-TFU Specifications & Compliance ............................................................................ 15

IC
-
TFU
Installation Guide
3
Reference Documents
Installation guidelines to be followed when installing IC-TFU or any other Rain Bird IC System™
components can be found on the Rain Bird IC System website at:
https://www.rainbird.com/products/ic-rotors-valves
https://www.rainbird.com/golf/products/ic-system
Reference Documents:
Rain Bird IC System Wire Path Design Guide
Rain Bird IC System Design Guide
Rain Bird IC System Installation Guide
Rain Bird IC System Operation & Troubleshooting Guide

4
IC
-
TFU
Installation Guide
IMPORTANT NOTES: Installing the IC-TFU – Transition Field Upgrade
Device
NOTE: The IC-TFU device must be installed in compliance with all electrical codes.
NOTE: The installation of the IC-TFU device should be performed with the IC
SystemTM wire path power turned off.
NOTE: The IC-TFU device requires time to intialize. Always wait two minutes after
the wire path has been powered before attempting any operation with the IC-TFU
device.
WARNING: Field wire paths must be kept separate from other wire paths. Do not
connect the field wires together from different output (group) wire paths on the
Integrated Control Interface.
WARNING: This device is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning use
of the appliance by a person responsible for their safety.

D37567
Installation Checklist
The following steps are recommended in order to properly install the IC-TFU device. For your
convenience, a check-off box has been provided for each step.
Verify Compatible Rain Bird Central Control Software is Installed
Choose a location to install the IC-TFU.
Gather Installation Tools / Other Materials Required
Install IC-TFU
o Step 1: Connect IC-TFU to Solenoid
o Step 2: Connect IC-TFU to IC SystemTM field wiring
o Step 3: Complete the installation
o Step 4: Configure Rain Bird central control software

6
IC
-
TFU
Installation Guide
Verify Compatibility with Rain Bird Central Control Software
1. Verify Central Control software (Cirrus™, Nimbus™ II, Stratus™ II or
Stratus LT™) in use is version 8.1.0 or higher.
2. Open the Central Control software and click on the “Rain Bird” icon in
the front office.
3. If the software version is less than 8.1.0, (as viewed below) contact
your Rain Bird distributor for options to acquire new software. Rain
Bird distributors and / or Rain Bird GSP can assist with software
updates.

D37567
Choose Location to Install the IC-TFU
1. Choose a location minimizing wiring length between IC-TFU and the DC Latching Solenoid
you desire to connect. The recommended location is within two (2) feet (0.6m) of the
base of the connected rotor or in the same valve box as the connected valve.
2. Choose a location with easy access to the MAXI™ wire path.
3. The IC-TFU device should be housed in an accessible valve box with proper drainage
whenever possible.
4. Take caution to observe local electrical codes when installing the IC-TFU.
NOTE: This and all other devices must be
installed in compliance with local electrical
codes.
Gather Installation Tools / Other Materials Required
Wire strippers
Rain Bird WC Series Wire Connectors (4)

8
IC
-
TFU
Installation Guide
Installation Step #1 – Connect IC-TFU Output wires to a DC Latching
Solenoid
The IC-TFU device provides control output pulses in response to Rain Bird IC SystemTM commands
received from the Rain Bird central control computer. IC-TFU control output pulses are suitable
for activating and deactivating a large number of DC latching solenoids.
1. Strip approximately 1” of insulation from each DC Latching Solenoid connection wire
to be spliced with IC-TFU output control wires. Take care not to score copper
conductors.
2. Splice / join wires by wrapping IC-TFU wires around DC Latching Solenoid Wires.
(Figure 1)
a. Connect IC-TFU Output (+) (red-with-white stripe) wire to latching solenoid (+)
control input. (red wire)
b. Connect IC-TFU Output (-) (black-with-white stripe) wire to latching solenoid (-
) control input. (black wire)
c. Trim joined wires to the appropriate length for the wire nuts.
Figure 1

D37567
3. Add suitable protection to the splices using Rain Bird WC series wire connectors.
a. Secure each splice with a wire nut (Figure 2)
b. Insert the splice and wire nut completely into the grease cap (Figure 3)
i. If required; use a thin object to push the wire nut to the end of the
grease cap.
Note: grease caps are single-use; do NOT attempt to reuse them.
Figure 2
Figure 3

10
IC
-
TFU
Installation Guide
Installation Step #2 – Connect to MAXI™ wire
1. Assure the IC wire path that the IC-TFU will be connected to is
powered OFF. (Figure 4)
2. IC-TFU should arrive from the factory with wire ends stripped.
If not, strip approximately 1” of insulation from each wire.
Take care not to score the copper strands.
3. Strip approximately 1” of insulation from each MAXI™ wire (IC
SystemTM field wiring) to be spliced with IC-TFU. Take care not
to score copper conductor.
4. Splice / join wires by wrapping IC-TFU wires around MAXI
wires. (Figure 5)
a. Connect the IC-TFU (red) wire to the MAXI™ (red)
wire. The IC-TFU to MAXI™ connection should be
solid red on both sides of the splice.
b. Connect the IC-TFU (black) wire to the MAXI™
(black) wire. The IC-TFU to MAXI™ connection
should be solid black on both sides of the splice.
c. Trim joined wires to appropriate length for the wire
nuts.
Figure 4
Figure 5

D37567
5. Add suitable protection to the splices using Rain Bird WC series wire connectors.
a. Secure each splice with a wire nut (Figure 5)
b. Insert the splice and wire nut completely into the grease cap (Figure 6)
i. If required; use a thin object such as an irrigation flag to push the wire
nut to the end of the grease cap.
Note: grease caps are single-use; do NOT attempt to reuse them.
Figure 6

12
IC
-
TFU
Installation Guide
Installation Step #3 - Complete Field Installation
1. Double-check safety of all connections. Assure that all
electrical codes have been followed and that no
exposed wire ends are present.
2. Remove address barcode from the IC-TFU device by
tearing at perforated line. (keep this barcode for your
records)
3. Assure that all connections are suitably protected from
surrounding environment, placing the IC-TFU and wire
splices near the base of an exposed rotor (Figure 7) or
in a separate valve box.
*FLEX and INFINITY are registered trademarks of the Toro Corporation
Figure 7

D37567
4. Apply power to the IC SystemTM wire path.
a. Allow two (2) minutes for all IC SystemTM
devices on the wire path to power-up
before performing operations.
Figure 8

14
IC
-
TFU
Installation Guide
Installation Step #4 – Refer to IC System Installation Guide and Central
Control Manual to Complete Setup
1. Refer to the IC System Installation manual found at:
https://www.rainbird.com/products/ic-rotors-valves
2. Activate Rain Bird Central Control software (version 8.1.0 or higher) on the central control
pc and select System Settings to check the Integrated Control Interface (ICI) configuration:
3. Refer to the Rain Bird Central Control user manual supplied with the Central Control PC to
complete Station Detail and Flow Zone setup for the IC-TFU.

D37567
IC-TFU Specifications & Compliance
Operating Temperature: 14ºF to 125ºF (-10ºC to 51ºC)
Storage Temperature: -40ºF to 150ºF (-40ºC to 65.5ºC)
Operating Humidity: 75% max at 40ºF to 108ºF (4.4ºC to 42.2ºC)
Storage Humidity: 75% max at 40ºF to 108ºF (4.4ºC to 42.2ºC)
IC SystemTM Field Wiring Voltage 26-28 VAC (max)
SOLENOID
CONTROLLER
273J
This device complies with Part 15 of the FCC rules subject to the following
two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including
interference that may cause undesired operation.
This Class B digital apparatus meets all requirements of the Canadian
Interference Causing Equipment Regulations.
EN61000-6-1 (1997) Class B:
EN61000-3-2
EN61000-3-3
EN61000-6-3 (1996):
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
EN 60335-1: 2010 Safety of household and similar electrical appliances

16
IC
-
TFU
Installation Guide
Rain Bird Corporation
6991 E. Southpoint Road
Tucson, AZ, 85706, U.S.A
Phone: (520) 741-6100
Fax: (520) 741-6522
Rain Bird Technical Services
(866) GSP-XPRT (477-9778)
(U.S. and Canada only)
Specification Hotline
(800) 458-3005
(U.S. and Canada only)
Rain Bird Corporation
970 W. Sierra Madre Avenue
Azusa, CA, 91702, U.S.A
Phone: (626) 812-3400
Fax: (626) 812-3411
Rain Bird International, Inc.
100 W. Sierra Madre Avenue
Azusa, CA, 91702, U.S.A
Phone: (626) 963-9311
Fax: (626) 963-4287
® Registered Trademark of Rain
Bird Corporation
© 2019 Rain Bird Corporation
5/2019
Table of contents