Raritan PMC-1000 User manual

Power Meter Quick Setup Guide
1
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
PM Series Power Meter
Safety Information
DANGER!
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Any covers that may be displaced during the installation must be reinstalled before powering the unit.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
NOTICE
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
CAUTION
RISK OF EQUIPMENT DAMAGE
This product is designed only for use with 0.33V output current transducers (CTs).
DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
Failure to follow these instructions can result in overheating and permanent equipment damage.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control conductive pollution and
the possibility of condensation or high humidity. Consider the enclosure, the correct use of ventilation, thermal properties of the
equipment, and the relationship with the environment. Installation category: CAT II or CAT III
Provide a disconnect device to disconnect the meter from the supply source. Place this device in close proximity to the equipment and
within easy reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant
requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. Disconnecting fuse holders can be used in the
USA and Canada. Provide overcurrent protection and disconnecting device for supply conductors with approved current limiting
devices suitable for protecting the wiring.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the device may be impaired.
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on the product.
Equipment Maintenance and Service
WARNING! This equipment must only be installed by qualified electrical personnel. This product contains no user serviceable parts.
Do not open, alter or disassemble this product. All repairs and servicing must be performed by Raritan authorized service personnel.
Failure to comply with this warning may result in electric shock, personal injury and death.
Raritan
400 Cottontail Lane, Somerset, NJ 08873 USA
QUICK SETUP GUIDE
PMC-1000, PMC-1001, PMM-1000, PMB-1960

Power Meter Quick Setup Guid
e
2
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Product Overview - PM Series Power Meters
Raritan PM series power meters is a modular power metering solution comprising three components.
PMM: a 3-phase power meter with neutral and
earth current monitoring.
PMB: a 96 channel branch circuit monitor that
plugs into PMM. A PMM+PMB monitors a panel
board mains and branch circuit.
PMC: power meter controller. One PMC controls
up to 70 PMM or 8 PMM+PMB. Interconnection
uses standard shielded CAT-5 cable. All modules
receive redundant power and continue to function
as long as one or more PMM remain powered.
Raritan PM series power meters are designed for
ease of use:
CTs are available in various ratings and contain
built-in burden resistors so they can be snapped
onto live wires without damage.
CT orientation is not critical because meter
auto-corrects polarity for any CT installed
backwards.
CT connections are made close to branch circuits
using multi-conductor wiring harnesses with
individual CT wire-pairs labeled and terminated
with a keyed connector.
PMM
PMB

Power Meter Quick Setup Guid
e
3
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
PMC
Product Specification
Voltage Measurement Inputs:
Input Range* 90-277VLN, 156-480VLL
Phase to Ground* 277V
Measurement
Category
CAT III, Pollution Level 2
Frequency 47-63 Hz
Input Impedance 10MΩ
*Ratings for models with field wiring terminals. For models with factory
installed line-cords, rating is limited by plug and ratings are labeled on
back on unit.
Current Measurement Inputs:
Input Range 0-400mV
Input Impedance 10k
CT Type Voltage Output = 333mV at rated current
CT Rated Current 1-1200A
Meter Measurement Accuracy:
Active Power &
Energy
0.5%: IEC 62053 Class .5, EN 50470-3 Class C
Reactive Power &
Energy
2%

Power Meter Quick Setup Guid
e
4
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
RMS Voltage &
Current
0.2%
Frequency 0.1%
Sample Rate 64x AC frequency (phase locked)
Measurement
Update Rate
3 seconds: IEC 61000-4-30 Class S
Power Requirements:
Voltage 90-240V
Current 0.2A
Overvoltage
Category
CAT III, Pollution Level 2
Frequency 47-63 Hz
Mechanical:
Terminal Block Screw
Torque
0.37 ft-lb (0.5Nm) to 0.44 ft-lb (0.6Nm)
Terminal Block Wire
Size
14-24AWG (.5-1.6mm)
Terminal Wire
Temperature Rating
> 75 degree C
DIN Rail T35 (35mm)
Environmental:
Operating Temperature 0-60°C
Operating Humidity 5-85%RH
Operating Elevation 0-3000m
Conformance:
Safety UL/EN 61010-1
EMC/EMI EN61326-1, FCC Part 15 Class A

Power Meter Quick Setup Guid
e
5
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Power Meter (PMM) Connectors and Controls
TOP
A
Voltage measurement.
B
Power
C
Factory use (do not connect)
D
Meter Bus Terminator Switch.
E
Meter Bus Connectors. Connects PMM to
controller.
F
Factory use (do not connect)
G
Multi-conductor cable CT ABCNE connector.
H
Meter ID configuration switch.
BOTTOM
I
Expansion port. Connects PMM to PMB

Power Meter Quick Setup Guid
e
6
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Power Meter Branch Monitor (PMB) Connectors
TOP
1
Multi-conductor cable CT 1 connector.
2
Multi-conductor cable CT 2 connector.
3
Multi-conductor cable CT 3 connector.
4
Multi-conductor cable CT 4 connector.
5
Multi-conductor cable CT 5 connector.
6
Multi-conductor cable CT 6 connector.
7
Multi-conductor cable CT 7 connector.
8
Multi-conductor cable CT 8 connector.
BOTTOM
A
Expansion port. Connects PMB to PMM.

Power Meter Quick Setup Guid
e
7
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Power Meter Controller (PMC) iX6
A
MODBUS RTU isolated RS-485
B
Meter bus connector (to PMM)
C
Meter bus terminator switch
D
10/100 base-t Ethernet.
E
Feature port (Raritan asset
strip)
F
Sensor port (temperature,
humidity, etc.)
G
USB A & B (flash drives, WIFI,
serial port)
H
RS-232 (terminal CLI, modem)
I
Pin-hole access reset button
J
LCD (meter readings, settings,
configuration)
K
Keypad

Power Meter Quick Setup Guid
e
8
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
DIN Rail Mounting PMM + PMB
BOTTOM
A
Expansion Connector
supplied with PMB.
Do not hot-plug the
Expansion Port! PMM and
PMB must be
disconnected from all
power source before
plugging Expansion Port.
Snap Expansion Connector
to Expansion Ports on
bottoms of PMM and PMB.
TOP
B
35mm DIN rail
C
PMM
D
PMB
E
Modules snap into rail. Pull
white tab here to remove.

Power Meter Quick Setup Guid
e
9
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Voltage and Current Measurement Wiring
A
Protect phase lines with fused disconnects rated
for available short circuit current at connection
point.
B
All wiring: 14-22 AWG, 75°C, solid or stranded.
Do not solder tin wire ends.
C
All CT: 333mV output at rated current. Do not
use current output CT.CTs can be connected to
live circuits. Connect CT in either direction.
Circuit Type
Circuit Description
Wiring Connections
Voltage
CT
A B C N A B C
Single-Phase L-N (120V,230V,240V) X X X
L-L (208V, 400V) X X X
Split-Phase North American 120/240V Panel, 2L+N circuit X X X X X
Three-Phase 3L, 3-phase without neutral X X X X X X
3L+N, 3-phase with neutral X X X X X X X

Power Meter Quick Setup Guid
e
10
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
PMB Branch Circuit Wiring
A
CT plugs into 2-pin locking connector
(Molex 43640-0201)
B
Branch Circuits have two labels: Red
labels for odd/even numbered panels.
White labels for sequentially numbered
panels.
C
Multi-conductor CT cable. Available
lengths: 3m, 10m.
D
Connect labeled end into matching labeled
connector
All CTs 333mV output. DO NOT use current
output CT.
CT can be connected to live circuit in either
direction. Meter auto corrects polarity.
Branch Circuit
Description
Current Transformers
How Many
Connect To
Line-Neutral (LN) 120V/230V circuit wired to 1-pole circuit breaker 1 phase line
Line-Line (LL) 208/240/400V circuit wired to 2-pole circuit breaker 1 either phase line
Line-Line-Neutral (LLN) 120V+208/240V circuit wired to 2-pole circuit breaker 2 each phase line
Three-Phase (LLL, LLLN) 3-phase circuit wired to 3-pole circuit breaker 3 each phase line

Power Meter Quick Setup Guid
e
11
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
PMM Power Wiring
PMM can be powered from the voltage measurement inputs or from an auxiliary AC power source. Powering from the voltage
measurement inputs minimizes circuitry, but the meter may stop functioning if the voltage turns off.
Powering from an auxiliary single phase circuit is required when the voltage measurement circuit exceeds 240V, or when continued
operation is required if the voltage measurement inputs turn off.

Power Meter Quick Setup Guid
e
12
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Controller Wiring to Meters
Up to seventy 3-phase power meters (PMM) and eight branch circuit meters (PMM+PMB) are daisy-chain wired to a single controller
(PMC) using shielded cat 5 Ethernet cable. The wiring order of the modules and controller is not important.
A
All cables shielded Cat-5, each cable:100m max.
length.
B
Switch MBT (terminator) ON for devices at ends of
daisy chain.
C
Switch MBT OFF for devices in middle of daisy chain.
D
Assign each meter unique ID:
01-70: PMM without PMB
01-08: PMM with PMB

Power Meter Quick Setup Guid
e
13
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Panel Layout

Power Meter Quick Setup Guid
e
14
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Login and Configuration
Connect your PC directly to the PMM to complete the initial configuration.
To access the web interface at the rack:
1. Disable the wireless interface of the PC.
2. Connect a cat 5 cable between the PC and PMM network ports.
3. Open a browser. Enter the URL "https://pdu.local". The login page appears.
If the URL does not resolve, use the IP address of the PMC. Retrieve the direct IP address using the LCD display: Menu > Device
Information, scroll to the IPV4 settings. Enter the IP address in the web browser:"https://IP address/"
4. Login with the default username and password. Allow 30 seconds for first connection.
Username: admin
Password: raritan
Configuring Power Meters and Branch Circuit Monitors
You can configure your product with a spreadsheet, or in the product's web interface.
To configure with a spreadsheet:
Go to Raritan.com and download the configuration spreadsheet from the BCM2 Support page. Follow the instructions in the
spreadsheet.
To configure with the product web interface:
Make a network connection to the product. See
Login and Configuration
(on page 13). Follow the instructions in this guide, starting
with: Scan Power Meters.
Configure Using the Web Interface
Scan Power Meters
1
Click Power
Meters.
2
If nothing is
configured, scan
begins
immediately in
the
Unconfigured
Meters section.
Click Rescan to
refresh the list.
3
Click the power
meter or panel
in the
discovered list
to configure it.
Types:
PM: 3-phase
Panel: BCM

Power Meter Quick Setup Guid
e
15
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Configure Power Meter (PMM without PMB)
1
Enter a name.
2
Select the circuit type:
Single Phase
Split Phase
3-phase
3
Enter the mains circuit breaker
rating.
4
Select the checkbox for each CT
installed.
Enter the CT rating. Ratings are
marked on the CT.
5
Click OK.
The configured power meter
displays in the dashboard and
Power Meters page.

Power Meter Quick Setup Guid
e
16
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Configure Panel Mains Circuit
1
Enter a name.
2
Select the circuit type:
Single Phase
Split Phase
3-phase
3
Enter the number of circuit
positions in the panel.
Select the panel layout: one or
two columns.
Select the circuit position
numbering style: sequential or
odd/even.
4
Enter the current rating (circuit
breaker rating) of the circuit.
5
Select the checkbox for each CT
installed.
Enter the CT rating. Ratings are
marked on the CT.
6
Click OK.

Power Meter Quick Setup Guid
e
17
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Configure Panel Branch Circuits
1
In the Power Meters
page, click the panel.
The Panel details page
opens.
2
In the Panel Branch
Circuits section, click the
circuit position to open
the pop-up menu.
3
Click Create Circuit. The
Create Circuit dialog
opens.
5
Enter a name for the
circuit.
6
Select the circuit type:
One-Phase LN,
One-Phase LL,
One-Phase LLN, or
Three-Phase. Circuit
type cannot be changed
later.
7
Enter the current rating
of the circuit in Amps.
8
Enter the rating of the CT
connected at this circuit
position in Amps.
9
Click the Phase or CT# to
edit the automatic labels.
10
Click Create.

Power Meter Quick Setup Guid
e
18
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Circuits appear in the list
with a black bracket
around the circuit
positions.
Configure Thresholds
1
In the Power Meters page, click
the panel or power meter.
The details page opens.
2
In the details page, click
the actions icon, then
choose Edit Thresholds.
3
The sensor list displays.
Click a sensor to open the
Edit Threshold dialog.

Power Meter Quick Setup Guid
e
19
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
4
Select the checkbox for
the level, and enter the
threshold current in amps.
Click OK.
This example shows RMS
Current thresholds set for
upper warning and critical
levels for the circuit max
current rating, and a lower
warning set for 1 amp.

Power Meter Quick Setup Guid
e
20
QSG
-PMM-1A-v3.3.10-E 255-64-0004-00
Using the PMM's Display
Automatic Mode:
The PMM has a display with automatic and
manual modes. In automatic mode, the display
scrolls through readings.
Manual Mode:
In manual mode, you can select readings and
settings to view.
Press or to view the Main Menu.
To return to automatic mode, press once
or several times.
Press to choose a menu item. Press
to select.
Power Meters list
Power Meter details
Other manuals for PMC-1000
1
This manual suits for next models
3
Table of contents
Other Raritan Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Wylie
Wylie W2245 Installation and Calibration

Bosch
Bosch AdvancedLevel 360 Original instructions

E. DOLD & SOHNE
E. DOLD & SOHNE IK 8839 Installation / monitoring technique

CESVA
CESVA SC250 user manual

Konica Minolta
Konica Minolta T-10A instruction manual

Micromeritics
Micromeritics AccuPyc II 1340 Operator's manual