RDM PR0029L-ACF User manual

Brooklands Case Controller
Commissioning/User Guide
Revision 2.2c
PR0029L-ACF

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
2
Contents
Description........................................................................................................... 3
Addressing ........................................................................................................ 3
Id .................................................................................................................. 3
Parameter Settings ............................................................................................. 3
Valve Type Selection........................................................................................... 3
Case Lights........................................................................................................ 4
On Line Status ................................................................................................... 4
Connections....................................................................................................... 4
Case Clean Switch .............................................................................................. 4
Default Parameter settings .................................................................................. 4
Parameter Descriptions ....................................................................................... 7
Probe allocations ................................................................................................ 9
Fan Speed ......................................................................................................... 9
CO2 App............................................................................................................ 9
Probe Type * ..................................................................................................... 9
When used in conjunction with a Mercury switch (PR0018-PHI) ................................ 9
EEV Control using Pressure .................................................................................. 9
Maximum Operating Pressure (MOP)..................................................................... 9
Servicing ......................................................................................................... 10
Inputs and Outputs........................................................................................... 10
Hardware Options............................................................................................. 11
External Tray Features ...................................................................................... 11
Wiring Loom (PR0024) ...................................................................................... 12
Specification .................................................................................................... 12

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
3
Description
The RDM Brooklands control tray PR0029L-ACF is a control system. The tray is used in conjunction with
the Brooklands wiring loom which connects to the tray using a 19 pole multiway connector. This loom
connects to all the low voltage components in the cabinet, these being the temperature probes,
refrigeration solenoid valve (24vdc), evaporator fans (24vdc) and a fan fail signal (volt free). There is a
separate mains voltage connector which connects to the cabinet lights. Two versions of the Brooklands
tray (PR0029-ACF & PR0037) have an additional mains connector for use with mains voltage evaporator
fans.
The tray is designed to be used on sites utilising a standard refrigerant or CO2.The unit has a Solid State
Relay (SSR) and through the in-built software the user can set the valve type for Mechanical Liquid Line
Valve (LLV) or Electronic Expansion Valve (EEV) control. The PR0029L provides a varying low voltage
output supply to control the evaporator fans. The PR0029L ACF and PR0037 provides a mains feed to
control the evaporator fans, the PR0037 has the addition of a higher specification relay to drive LED lights.
The RJ45 connector found at the rear of the tray is a serial RS232 port and must be connected to an
appropriate communications module such as an IP Futura Module (PR0016) or Mercury switch (PR0018 or
PR0018-PHI) or RS485 Legacy Module (PR0026). This allows communication with compatible front ends
such as the RDM Data Manager or Data Director.
The RDM Brooklands tray PR0033 is fitted with an electro-mechanical relay to drive a LLV and the PR0033E
has an SSR to operate an EEV. The PR0033/E series control tray is designed to be used only on IP networks
only and must be connected to an appropriate IP communications module or Mercury Switch. The tray has
the addition of a PWM (Pulse width modulated) output for controlling intelligent evaporator fans. The
controller has a “CO2 App parameter” to allow them to be used in conjunction with an RDM Data Manager,
Plant Pack Controller and CO2 Pump Station for load shedding on CO2 sites.
Addressing
The controller will log onto the network when it is first powered up. You must set the address using the front
accessed rotary switches prior to power up. If you change the location of a tray from one case section to
another, you should change the rotary switches to the new address before powering up the tray in the new
location.
NOTE: V1.3 software does not support Genus RS485
networking.
Id
To set the network id, use the front accessed rotary switches and set the address of your choice. Each device
on the network must have a unique address number.
(Normally set to Bay/case number such as 103 = Bay10 case 3)
Parameter Settings
All parameter settings are modified using the RDM Data Manager front-end alarm panel, a service or install
level password is required to alter any settings. Default settings are shown below
Valve Type Selection
The PR0029L & PR0037 Brooklands control tray has a parameter to set the valve type (EEV or TEV) via the
front end if the controller software is version V2.0 or higher or V7.5 or higher. On earlier software versions,
V6.9 or above, the valve type can only be changed using a PC connected to the controller. If the tray has V1.4
software then the valve type cannot be changed and is fixed as EEV only. The default factory setting is EEV.
The PR0033 Brooklands control tray can only be used with a thermostatic expansion valve (TEV).
The PR0033E Brooklands control tray can only be used with an electronic expansion valve (EEV).
On the PR0033/E range there is no user settable parameter to set valve type, this is fixed to the hardware type
PR0033 or PR0033E.
See RDM Data Manager user guides for more information on CO2 Load Shedding

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
4
Case Lights
Timers either locally in the tray or remotely at the front end normally control the case lights automatically. If
there are no timers set up from the front end or if there is no network connection, the lights default to on.
On Line Status
The case status indicator is used to display the network status: -
Alternate Red/Green: - logging on
Alternate Red/Green/Amber: - has address but not on-line
Fixed temperature band colour (Red, Green or Yelllow): - online
Connections
There is No status indicator on this version of the Brooklands Tray. The RS232 serial port of the
communications module plugs into the rear of the tray (RJ45 connector). All case wiring connects to the two
flying leads at the back of the tray. (19 way and 3 way)
The power lead plugs into the rear of the case and is the ONLY method of isolation. The power lead must be
removed before the lid is removed.
Case Clean Switch
THIS IS NOT AN ISOLATOR. The case clean switch will turn power off to all outgoing circuits and send
signals to the front-end indicating the case has been manually switched to case clean mode. The controller will
remain powered and will continue to communicate with the front end panel which will only generate an offline
alarm if there is a genuine power failure or communications failure.
Default Parameter settings
Parameter
Range
Step
Units
Default
PR0029L
LLV
PR0029L
EEV
PR0029L/37
LLV
230V ACF
PR0029L/37
EEV
230V ACF
PR0033
LLV
PR0033E
EEV
Yellow Cycle
temp.
-49.0 to 30.0
0.1
Deg C
2.0
Red Cycle temp.
-49.0 to 30.0
0.1
Deg C
4.0
Green Cycle
temp.
-49.0 to 30.0
0.1
Deg C
8.0
Cut-in diff.
0.0 to 10.0
0.1
Deg C
1.0
Control weight
0 to 100
1
%
40
Superheat Ref.
4.0 to 12.0
0.1
Deg C
6.0
EEV Prop. Gain
0.0 to 100.0
0.1
-
2.2
EEV Integ. Gain
0.0 to 100.0
0.1
-
1.8
EEV Integ. Time
00:00 to 23:59
00:01
mm:ss
03:00
Fan Speed
0 to 5
1
-
3
Temp. Band
Yellow/Red/Green
/ Ambient
-
-
Yellow
Probe Type
PT1000/ NTC 3K
-
-
PT1000

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
5
Parameter
Range
Step
Units
Default
PR0029L
LLV
PR0029L
EEV
PR0029L/37
LLV
230V ACF
PR0029L/37
EEV
230V ACF
PR0033
LLV
PR0033E
EEV
Evap Select
Local/ Remote
-
-
Local
Div Value
0 to 100
1
%
50
Ctrl Probe Type
Air Probe/
Logging
-
-
Air Probe
PWM
0 to 100
1
%
80
Valve Type
EEV/LLV
1
-
EEV
Co2 App
Off
Mode 1
Mode 2
1
-
Off
Alarm delay
00:00 to 99:00
01:00
mm:ss
20:00
Yellow UT Alarm
-49.0 to 60.0
0.1
Deg C
-3.0
Yellow OT Alarm
-49.0 to 60.0
0.1
Deg C
5.0
Red UT Alarm
-49.0 to 60.0
0.1
Deg C
-2.0
Red OT Alarm
-49.0 to 60.0
0.1
Deg C
6.0
Green UT Alarm
-49.0 to 60.0
0.1
Deg C
0.0
Green OT Alarm
-49.0 to 60.0
0.1
Deg C
12.0
Yel Prod UT Alm
-49.0 to 60.0
0.1
Deg C
-1.0
Yel Prod OT Alm
-49.0 to 60.0
0.1
Deg C
6.0
Red Prod UT Alm
-49.0 to 60.0
0.1
Deg C
0.0
Red Prod OT Alm
-49.0 to 60.0
0.1
Deg C
9.0
Grn Prod UT Alm
-49.0 to 60.0
0.1
Deg C
4.0
Grn Prod OT Alm
-49.0 to 60.0
0.1
Deg C
12.0
Defrost Start
00:00 to 23:50
00:01
hh:mm
01:00
Defrost Number
0 to 8
1
-
6
No Defrost Time
0 to 25
1
-
8
Def. term. temp.
-49.0 to 30.0
0.1
Deg C
8.0
Defrost min time
00:00 to 99:00
01:00
mm:ss
15:00
Defrost max time
00:00 to 99:00
01:00
mm:ss
45:00
Drain down time
00:00 to 24:00
00:15
mm:ss
01:30
Recovery time
00:00 to 99:00
01:00
mm:ss
30:00
Defrost Mode
Local/ Remote
-
-
Local
Fans in Def
Off/On
-
-
On
Lights Mode
Local/Remote/Ma
n Off/ Man On
-
-
Local

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
6
Parameter
Range
Step
Units
Default
PR0029L
LLV
PR0029L
EEV
PR0029L/37
LLV
230V ACF
PR0029L/37
EEV
230V ACF
PR0033
LLV
PR0033E
EEV
Sun Lights On
00:00 to 23:59
00:01
hh:mm
08:00
Sun Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
Mon Lights On
00:00 to 23:59
00:01
hh:mm
08:00
Mon Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
Tue Lights On
00:00 to 23:59
00:01
hh:mm
08:00
Tue Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
Wed Lights On
00:00 to 23:59
00:01
hh:mm
08:00
Wed Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
Thu Lights On
00:00 to 23:59
00:01
hh:mm
08:00
Thu Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
Fri Lights On
00:00 to 23:59
00:01
hh:mm
08:00
Fri Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
Sat Lights On
00:00 to 23:59
00:01
hh:mm
08:00
Sat Lights Off
00:00 to 23:59
00:01
hh:mm
20:00

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
7
Parameter Descriptions
Parameter
Description
Yellow Cycle temp.
When the temperature band is set to yellow range (see Temp. Band Parameter Below) this
will be the cut in temperature.
Red Cycle temp.
When the temperature band is set to red range (see Temp. Band Parameter Below) this will
be the cut in temperature.
Green Cycle temp.
When the temperature band is set to green range (see Temp. Band Parameter Below) this
will be the cut in temperature.
Cut-in diff.
This is the differential below cut in temperature where refrigeration will cut out.
Control weight
Percentage of the Air-On temperature that is used to calculate the control temp. The
remaining percentage will be used on the Air-Off temperature. Example;
P-03 set to 30% Control temp = 30% Air-on and 70% Air-off
Superheat Ref.
The controller will attempt to maintain this superheat value (EEV only)
EEV Prop. Gain
These are the parameters to fine tune the valve PID feedback control loop, these
parameters should be left as default and only be changed in exceptional circumstances.
EEV Integ. Gain
EEV Integ. Time
Fan Speed
The fan speed output will run the fans depending on the voltage set at fan speed parameter
(1 = 16Vdc. 2 = 18Vdc. 3 = 20Vdc. 4 = 22Vdc. 5 = 24Vdc. (PR0029 only))
The PWM output (PR0033 & PR0033E only) will run the evaporator fans at this pre-set
percentage of full speed (PWM Parameter).
PR0029L ACF and PR0037 trays have fixed speed mains fans.
Temp. Band
This selects the temperature band that the cabinet will run at, yellow, red, green or
ambient, this is set according to the type of product in the cabinet. Temperature alarm
settings will automatically change accordingly.
Probe Type
As standard the tray uses PT1000 temperature probes however NTC 3K probes can be used
by setting this parameter to 1.
Note that the log probe remains as a PT1000
Evap Select
The superheat for EEV control can be calculated using different means to suit the
application.
Local - Based on the value of the Evaporator and Suction line temperature probe inputs
connected directly to the controller.
Rem1 - The local suction line temperature probe and a local suction pressure measured by
a transducer connected to the refrigeration case island Mercury Hub (PR0018-PHI). The
pressure read from the Mercury Hub pressure transducer is converted to a temperature
based on the gas type being used by the system. This temperature is transmitted to all
controllers connected to the Mercury Hub.
Rem2/3 - Not used at present.
Div Value
This parameter is used in conjunction with a Mercury Switch pressure application (Evap.
select set to Rem1). When the Mercury Switch generates the MOP (Maximum operating
pressure) alarm the controller reduces the maximum valve opening to this percentage. For
example if this parameter is set to 50% and the MOP alarm is generated then the
maximum valve opening will be limited to 50%. Therefore as the controller pulses the valve
the maximum the valve will open is 50%.
Ctrl Probe Type
Switches between using the air-on probe(s) and the Logging probe. Note the control
temperature will still be a derivative of the weighted average of the control probe + Air-off
probe(s)
PWM
Pulse Width Modulation, this applies only to trays with PWM controlled fans (PR0033 &
PR0033E), this is the percentage of maximum speed the fans will run at.
Valve Type
Selects between mechanical liquid line valve (LLV) and electronic expansion valve (EEV)
Co2 App
When used in conjunction with a Data Manager load shedding system, this parameter
selects how the valve and fans will operate if a load shedding signal is received from the
Data Manager.
Mode 1 –Evaporator fans off, valve open 100% on Load Cycling
Mode 2 –Evaporator fans off, valve closed to 0% on Load Cycling
Alarm delay
Delay for the over and under-temperature alarms
Yellow UT Alarm
Under temperature alarm set point when set to yellow range. This alarm uses the control
temperature.
Yellow OT Alarm
Over temperature alarm set point when set to yellow range. This alarm uses the air off
temperature.
Red UT Alarm
Under temperature alarm set point when set to red range. This alarm uses the control
temperature.
Red OT Alarm
Over temperature alarm set point when set to red range. This alarm uses the air off
temperature.
Green UT Alarm
Under temperature alarm set point when set to green range. This alarm uses the control
temperature.

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
8
Parameter
Description
Green OT Alarm
Over temperature alarm set point when set to green range. This alarm uses the air off
temperature
Yellow Product UT Alarm
Logging probe under temperature alarm set point when set to yellow range.
Yellow Product OT Alarm
Logging probe over temperature alarm set point when set to yellow range.
Red Product UT Alarm
Logging probe under temperature alarm set point when set to red range.
Red Product OT Alarm
Logging probe over temperature alarm set point when set to red range.
Green Product UT Alarm
Logging probe under temperature alarm set point when set to green range.
Green Product OT Alarm
Logging probe over temperature alarm set point when set to green range.
Defrost Start
When defrost mode is set to “Local”, this is the start time for the 1st defrost
Defrost Number
When defrost mode is set to “Local”, this is the number of defrosts per day equally spaced
from the start time.
No Defrost Time
If the controller misses a defrost command for any reason, a defrost will initiate after this
time has elapsed from the last defrost. Normally set to 2 hours over the normal defrost
period.
Def. term. temp.
The defrost will terminate when the temperature of the air off probe(s) reaches this value.
Defrost min time
Minimum time that a defrost will use. Defrost can’t terminate until this time has elapsed. If
termination temperature is reached during this period the controller will not continue the
refrigeration cycle until the end of the defrost min period.
Defrost max time
Time period after defrost minimum that defrosts are allowed to terminate.
Drain down time
A period after defrost period to allow the draining of any surplus water.
Recovery time
The valve is switched on at the start of this period to allow the temperature to recover to
the normal operating point. This period also inhibits the OT alarm.
Note that if the air-off temperature is still above the OT alarm setpoint when this period
expires, an immediate OT alarm occurs; there is not a further alarm delay.
Defrost Mode
Allows the user to set the defrost mode: -
Local: Uses the internal parameters (see above)
Remote: Requires a defrost schedule in the front end.
Fans in Def
Allows the fans to run during defrost or not.
Lights Mode
Allows the user to set the lights mode: -
Always off
Always on
Use a local schedule (see below)
Use a remote schedule (Set up in the system front end)
Sun Lights On
When lights mode set to Local, Sunday On Time.
Sun Lights Off
When lights mode set to Local, Sunday Off Time.
Mon Lights On
When lights mode set to Local, Monday On Time.
Mon Lights Off
When lights mode set to Local, Monday Off Time.
Tue Lights On
When lights mode set to Local, Tuesday On Time.
Tue Lights Off
When lights mode set to Local, Tuesday Off Time
Wed Lights On
When lights mode set to Local, Wednesday On Time.
Wed Lights Off
When lights mode set to Local, Wednesday Off Time
Thu Lights On
When lights mode set to Local, Thursday On Time.
Thu Lights Off
When lights mode set to Local, Thursday Off Time.
Fri Lights On
When lights mode set to Local, Friday On Time.
Fri Lights Off
When lights mode set to Local, Friday Off Time.
Sat Lights On
When lights mode set to Local, Saturday On Time.
Sat Lights Off
When lights mode set to Local, Saturday Off Time.

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
9
Probe allocations
Probe 1 Air on left Probe 5 Product probe
Probe 2 Air off left Probe 6 Evaporator inlet
Probe 3 Air on right Probe 7 Evaporator outlet
Probe 4 Air off right
Fan Speed
The fan speed output will run the fans depending on the voltage set at fan speed parameter (1 = 16Vdc. 2 =
18Vdc. 3 = 20Vdc.4 = 22Vdc. 5 = 24Vdc. (PR0029 only))
The PWM output (PR0033 & PR0033E only) will run the evaporator fans at this pre-set percentage of full speed
(PWM Parameter).
Before Adjusting the fan speed parameters firstly determine the fan type fitted to the case.
PR0029L ACF and PR0037 trays have fixed speed mains fans.
CO2 App
Needs to be set to Mode 1 or Mode 2 when using CO2 Load Cycling
Mode 1 –Evaporator fans off, valve open 100% on Load Cycling.
Mode 2 - Evaporator fans off, valve closed 0% on Load Cycling.
Probe Type *
NTC 3K Probes can be used by setting this parameter to 1.
Note that the log probe remains as a PT1000
When used in conjunction with a Mercury switch (PR0018-PHI)
EEV Control using Pressure
The Mercury Switch (PR0018-PHI) can be used for EEV control on an island by island basis. In an EEV
application the evaporator in temperature probe reading for a case controller can be obtained from the Mercury
switch on which the controller is connected. A suction pressure transducer is connected from the case Island to
the 4-20mA input of the Mercury Switch and the pressure read from this transducer is converted to a
temperature based on the gas type being used by the system. This temperature is transmitted to each
controller (Rem Evap Temp) connected to the switch and along with the suction temperature probe local to the
controller the superheat is calculated. Please note that RDM recommended that the evaporator in temperature
probe is fitted as the controller will use this to calculate the superheat in the event of a communication loss
with the Mercury Switch. Setting parameter “Evap Select” to “Remote” allows for the use of this remote
temperature provided by the Mercury Switch. Please see the Mercury Switch user document (PR0018-PHI) for
further details.
Maximum Operating Pressure (MOP)
Maximum Operating Pressure (MOP) support added to Brooklands Controller. MOP is a remote command sent
from the Mercury switch (PR0018-PHI) to the controller to either close or reduce the EEV valve opening when a
predetermined pressure is reached. This MOP value is configured in the Mercury switch setup. When the
Mercury Switch generates a MOP alarm the controller reduces the maximum valve opening (Div Value) to this
percentage. For example if the “Div Value” parameter is set to 50% and the MOP alarm is generated then the
maximum valve opening will be limited to 50%. Therefore as the controller pulses the valve the maximum the
valve will open to is 50%. For Mechanical Valve Controllers the LLV is closed for the MOP alarm duration.

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
10
Servicing
There are no serviceable parts. The only parts that are replaceable on this tray are the front panel mounted
fuses. If replacement fuses are required they must match the original size.
Fuses: HRC conforming to IEC60127 (32 x 6.3mm)
Fans (F1) 3.15A (T)
Lights (F2) 3.15A (T)
Controller (F3) 0.25A (F)
Valve (F4) 0.25A (T)
Fuse rating may vary depending on the age of the tray so please check with the controller label for tray you
are using.
Inputs and Outputs
Inputs
Range
Step
Units
PR0029L LLV
PR0029L EEV
PR0029L/37 LLV
230V ACF
PR0029L/37 EEV
230V ACF
PR0033 LLV
PR033E EEV
Control temp.
-49.0 to 60.0
0.1
Deg C
Air on temp.
-49.0 to 60.0
0.1
Deg C
Air off temp.
-49.0 to 60.0
0.1
Deg C
Air on Left
-49.0 to 60.0
0.1
Deg C
Air off Left
-49.0 to 60.0
0.1
Deg C
Air on Right
-49.0 to 60.0
0.1
Deg C
Air off Right
-49.0 to 60.0
0.1
Deg C
Product Probe
-49.0 to 60.0
0.1
Deg C
Evaporator Probe
-49.0 to 60.0
0.1
Deg C
Suc. Line Probe
-49.0 to 60.0
0.1
Deg C
Fan Fail
Alm/Ok
-
-
Superheat
-49.0 to 60.0
0.1
Deg C
Rem Evap Temp.
-49.0 to 60.0
0.1
Deg C
MOP
Off/On
-
-
CO2
Off/On
-
-
EEV Opening
0 to 100
0.1
%
LLV
Closed/ Open
-
-
Trim Heater
Off/On
-
-
Case Fans
Off/On
Lights
Off/On
PWM
0 to 100
1
%
Last Def. Time
00:00 to 23:59
00:01
hh:mm
Last Def. Length
00:00 to 03:00
00:01
hh:mm
Last Def. Ctrl
Temp.
-49.0 to 60.0
0.1
Deg C
Last Def. Type
None/ Internal/
External/
Network/
Timed/ Forced
-
-

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
11
Hardware Options
Part Number
EEV Control
LLV Control
PWM Fans
230VAC Fans
LED Lighting
PR0029L
X
X
X
PR0029L ACF
X
X
PR0033
X
X
X
PR0033E
X
X
X
PR0037
X
External Tray Features
3
RDM
M&S
1 2
F1
F2
F3
3
3
3
F4
Case clean switch.
Note: This does not
isolate the power
supply
Network Address
Rotary Switches
Network
Status LED
Fan
Fuse
(3.15A)
Lighting
Fuse
(3.15A)
Controller
Fuse
(0.25A)
Valve
Fuse
(0.25A)
Lighting
Mains
Connector
(On flying
lead)
RS232 Socket
(Connects to
comms module
or Mercury
Switch)
19 Way
Wiring
Harness
Connector
Socket
(On Flying
Lead)
Mains Fans
Connector
(Only used on
PR0029 ACF and
PR0037 )
Tray Mains
Power
Connector
FRONT
BACK

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
12
Wiring Loom (PR0024)
Specification
PR0029L ACF Brooklands Case Controller
Supply Voltage Range
240 Vac ±10%
Supply Frequency
50Hz
Typical supply current (Excluding
relay load)
<1 Amp
General
Operating temperature range
+50C to +500C
Storage temperature range
-200C to +650C
Environmental
Indoor use at altitudes up to 2000m, pollution degree 2, installation
category II. Voltage fluctuations not to exceed ±10% of nominal voltage.
Size
188mm (W) x 78.5mm (H) x 648mm (D)
Approx. Weight
4.13kg
Safety
EN61010-1: 2010
EMC
EN61326:2013
Ventilation
There is no requirement for forced cooling ventilation
Class 2 Insulation
No protective Earth is required and none should be fitted. Earth connection
is functional only.
Connections
Relay and probe: RDM wiring harness PR0024
Power: 3 pin GST18
Lights: 3 pin M12
Product Probe
Socket
RH Air Off Probe
LH Air Off Probe
Evap. In Probe
Evap. Out Probe
+24VDC Fan Supply (Brown)
+24VDC Fan Supply (Yellow)
Fan Supply Gnd (Blue)
LH Air On Probe (Orange)
RH Air On Probe (Green)
*Fan Fail Signal (Red)
Probe & Fan Fail Signal Gnd
(Purple)
Valve Connector DIN
Socket (24VDC)
Pin 1 +24v (Brown)
Pin 2 0v (Blue)
Pin 3 Earth
(Green/Yellow)
19 Way Harness
Connector Plug
(Connects to 19 way
harness socket on
tray)
*Fan fail alarm is generated when the fan fail signal
(red) is connected to fan fail ground (purple)

Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
13
240V Fans: 2 pin M12
RS232: RJ45
Relay Specification
Relay 1, EEV, Solid State (PR0029L, 29L-ACF, 33E, 37)
Output Current Rating
3A max, 20mA min
Output Voltage Rating
24-240 VAC
Note: Valve supply and return are limited by internal 24Vac 12VA
transformer
Relay 1, Valve, Mechanical (PR0033E)
Contact Type
SPDT
Contact Rating
10A @ 250Vac (30Vdc) Resistive (CosΦ = 1)
7.5A Inductive (CosΦ = 0.4)
Note: Valve supply and return are limited by internal 24Vac 12VA
transformer
Relay 2, Lights, Standard (PR0029L, 29L-ACF, 33, 33E)
Contact Type
SPDT
Contact Rating
10A @ 250Vac (30Vdc) Resistive (CosΦ = 1)
7.5A Inductive (CosΦ = 0.4)
Peak inrush current (20ms): 20A
Fuse
3.15A, 1500V Breaking Capacity, Type T
NOTE: The lights output is protected by a 3.15A fuse so the lights cannot
draw any more than this under normal running.
Relay 2, Lights, High Inrush (PR0037)
Contact Type
N/O
Contact Rating
16A @ 250Vac Resistive (CosΦ = 1)
Peak inrush current (20ms): 80A
Fuse
3.15A, 1500V Breaking Capacity, Type T
NOTE: The lights output is protected by a 3.15A fuse so the lights cannot
draw any more than this under normal running.
Relay 3, Fans
Contact Type
SPDT
Contact Rating
10A @ 250Vac (30Vdc) Resistive (CosΦ = 1)
7.5A Inductive (CosΦ = 0.4)
Fuse
3.15A, 1500V Breaking Capacity, Type T
Inputs
Probe Input resistance
3.01K Ohms
Probe Input type
PT1000

While every effort is made to ensure the information given within this
document is accurate, Resource Data Management Ltd shall not be liable for
errors or omissions, for incidental or consequential damages, directly or
indirectly, in connection with the furnishing, performance or misuse of this
product or document. All specifications are subject to change without notice.
See www.resourcedm.com for terms and conditions of sales.
Copyright © Resource Data Management
Group Offices
RDM Group Head Office
80 Johnstone Avenue
Hillington Industrial Estate
Glasgow
G52 4NZ
United Kingdom
+44 (0)141 810 2828
support@resourcedm.com
RDM Inc
100 North Sixth Street
Suite 630B
Minneapolis, MN
55403
United States
+1 612 354 3923
usasupport@resourcedm.com
RDM Asia
Sky Park at One City
Jalan USJ 25/1
47650 Subang Jaya
Selangor
Malaysia
+60 3 5115 0061
[email protected]om.my
Visit www.resourcedm.com/support for more information on
RDM solutions, additional product documentation and software
downloads.
This manual suits for next models
10
Table of contents
Popular Control System manuals by other brands

Norac
Norac UC4 Plus Rogator 64 Series installation manual

CYBELEC
CYBELEC DNC 60 GS user guide

Weishaupt
Weishaupt WCM-FS 2.0 Installation and operating instruction

AutomationMaker
AutomationMaker SUPER X3 manual

Raven
Raven AccuBoom Parallel Installation Manual

ZF Marine
ZF Marine ClearCommand 9000 Series Installation, operation and troubleshooting manual