Red Dragon PF-16 LPS User manual

RED DRAGON ELECTRONIC PROPANE FLARE
Assembly and Operating Instructions
Read this manual and any other
safety-related information before
assembling, operating or maintaining
your RED DRAGON PROPANE FLARE:
Save this manual for future reference.
The RED DRAGON
PROPANE FLARE is
designed for the
evacuation of LP liquid
or vapor only. Its use for
the evacuation of any
other gases or
flammable liquids is
strongly discouraged
and cancels any
warranties or perceived
responsibility of FLAME
ENGINEERING, INC.
Failure to follow these instructions, local, state, national codes
and other instructions provided with this flare equipment may
result in serious injury or death.
TORCHES & EQUIP.
®
PFLPS Instruction Manual 7-2012
For Models:
PF-16 LPS – 1/2" Flare – 48,300,000 BTU/hr Max

PLEASE READ BEFORE GETTING STARTED:
The purpose of the Red Dragon Electronic Propane Flare is to provide an efficient process for the evacuation of
propane liquid and or vapors from an LP container. It is important to remember a Red Dragon Propane Flare
will not completely empty the container. All safety rules, local ordinances, state and federal regulations are to
be reviewed and permission granted by the appropriate authority before the flaring of LP cylinders in or near to
a populated area.
All gas components used in the construction of the Red Dragon Propane Flare are either UL or CSA listed
components.
NOTE: The Red Dragon Propane Flare is designed for the evacuation of LP gas liquids or gases only.
The use of the flare for the evacuation of any other gases or flammable liquids is prohibited and voids
any warranties expressed or implied.
Qualifications, Codes, Etc.
The testing, firing, and the service of this flare equipment requires training and knowledge of LP-Gas and
LP-Gas appliances and should not be attempted by anyone who is not qualified. You must completely
familiarize yourself with the flare, and its operation by reading and complying with the safety instructions,
labels, owner's manual, etc. that is provided with each flare.
IMPORTANT SAFETY NOTE: The manual flare is not designed to be operated unattended.
OTHER REQUIRED EQUIPMENT NOT INCLUDED WITH THIS FLARE:
3,/27)8(/6285&(
A filled LP cylinder with a minimum of 5 gallon capacity (20lb cylinder) is required to provide the pilot torch fuel. A
larger cylinder or several 5 gallon cylinders may be required for the complete flaring of a larger propane container.
$'-867$%/(:5(1&+
Required for attaching the evacuation hoses to valve box, the flare head to the tower and the P.O.L. fitting to
the pilot cylinder.
*/29(6$1'(<(3527(&7,21
Required for safe assembly & operation of the flare.
&HPHQW%ORFNVRU6DQG%DJV
Required for weighting down tripod if the flare is to be operated on pavement or soft soil where stakes are not
sufficient.
TABLE OF CONTENTS:
FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com 1
Important Information and Safety Information ........................ 1
Other Required Equipment ......................................................... 1
Component Photos and Descriptions......................................... 2
Assembly Instructions ................................................................. 3
Lighting Instructions....................................................................5
Shut Down Procedures................................................................ 5
Trouble Shooting Tips & Other Flaring Rules ............................6
Parts List .......................................................................................8

Flare Head/Flare Hose Assembly
Pilot Torch
1/4” Pilot Torch Hose
w/ Female Swivel
Connection
Flare Tube Hose
w/ Female Swivel
Connection
Solenoid
Control Box
Pilot Cylinder
Hose Assembly
Evacuation Tank
Hose Assembly
Tripod Leg
Leg Guide
w/Handle
Tower Base
Plate
Flare
Tower
Pin
Circle Eyelet
For Ground Stakes
Ground
Stakes
Evacuation Flare Tube
(Attached to
Pilot Torch Hose)
Safety
P.O.L.
Cylinder
Fitting
Female
Fitting
10’ – 1/4”
Pilot Cylinder
Hose Assembly
Adjustable Regulator
Pilot
Cylinder
(not included)
Electrode Box
Heat Sensor &
Ignition Wire
Electronics
Control Box
Master On/Off
Switch
Master On Light
110 Volt
Power Cord
Lower Tower
Flare Tower Pin
(Behind Control Box)
Upper Tower
Flare Head/Hose
Assembly
Upper Tower
Handle
Control Box
Receiver
Plate
Caribiner Clip
FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com
COMPONENT PHOTOS & DESCRIPTIONS:
2
25’ – Evacuation
Tank Hose Assembly
Evacuation
Tank Fitting
Acme Thread LP Fitting For 1/2”
Flare Tower Shown Here
Female Swivel
Connection
Pressure
Gauge
Pressure Relief Valve
Ball
Valve

Flare Head
Receiver Bracket
Evacuation
Flare Tube
Pilot Torch
DIAGRAM 1
ASSEMBLY INSTRUCTIONS:
FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com 3
B.
1. Stand the tower in an upright position on the tower base
plate. Remove the three Leg Pins that are securing the
Tripod Legs and pull the legs free of the storage brackets.
(see photos A & B)
2. Pull the tee handle lock of the tripod leg guide. The leg
guide will slide down until the tripod legs are at maximum
extension. (see photos A ,B & C)
3. Pull upward on the lower tower square tubing until the
tee handle locks the tripod legs securely. (Test the flare
tower position and confirm that the tripod legs cannot be
folded. (see photos A & C)
IMPORTANT NOTE: The Eyelets at the end of each tripod
leg are to hold the Ground Stakes if the tower is set up on
dirt or grass. If using the flare tower on pavement, weight
the tripod legs with sandbags or cement blocks before
operating.
4. Assemble the electrode box, pilot torch and
evacuation flare tube to the receiver bracket on the top of
the upper tower using a lock-washer and hex nut. (See
Photo D and Diagram 1)
5. Attach the control box to the control box receiver plate
at the top of the lower tower section using the provided
wing nuts. (See Photo E)
6. Run the pilot hose and evacuation fuel hose from the
torch through the hose secure ring on the upper tower
collar and attach them to the appropriate fittings on the left
side of the solenoid (bottom) control box. The main
evacuation line will connect to the top fitting and the pilot
torch line will connect to the bottom fitting. These are flared
fittings – no need for thread sealant. (See Photo F)
7. Grasp the upper tower square tubing or handle and
extend the upper tower to full height and secure with the
flare tower pin which is conveniently attached to the pilot
torch hose. Check that all hoses remain in their proper hose
brackets on the tower.
BEFORE OPERATING THE RED DRAGON
PROPANE FLARE:
Make sure you have selected a safe area for
placement and operation with
approximately 40 foot radius and a
minimum 50 feet of vertical clearance.
Tee
Handle
Spring
Lock
Leg
Guide
Leg
Pins
Circle
Eyelets
A.
C.
D.
E.
Electrode Box
F.

FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com 4
8. Arrange the tower so that the tripod leg with the hose
bracket is pointing toward the tank being evacuated. Weight
the tripod legs with cinder blocks or sand bags if the unit is
to be operated on pavement. If the unit is to be operated on
dirt or grass, stake each tripod leg down using the leg
stakes included with the unit.
9. Attach the Female Swivel Connection on the Pilot Cylinder
Hose to the Male Connection on the bottom left male fitting
on the bottom of the solenoid control box. Attach the other
end of the Pilot Cylinder Hose to the pilot cylinder using the
P.O.L. fitting. NOTE: Always use a separate pilot cylinder.
Never use the tank being evacuated as the pilot source.
Wrench tighten but do not over tighten (remember this is a
left hand thread fitting).(see photo G)
10. Attach the Female Swivel Connection on the Evacuation
Tank Hose to the Male Flared Connection on the bottom right
of the Solenoid Control Box. As mentioned before, Teflon® or
pipe thread sealant is NOT required. (see photo G)
Note: Use the caribiner clip to keep the evacuation hose in
an orderly manner. (See Photo H)
ASSEMBLY INSTRUCTIONS:
G.
H.

FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com 5
RED DRAGON PROPANE FLARE OPERATING INSTRUCTIONS
BEFORE OPERATING THE RED DRAGON PROPANE FLARE:
Make sure you have selected a safe area for placement and operation with
approximately 40 foot radius and a minimum 50 feet of vertical clearance.
1. Attach pilot hose to an LPG fuel supply with at least
five gallon capacity.
2. Attach the main evacuation line to the tank being
evacuated. This connection will be either a P.O.L
fitting or a commercial tank connection, depending on
the model.
3. Slightly open each tank, one at a time, and test for
leaks at all connections to the Solenoid Control Box
using soapy water or commercial leak testing fluid.
Turn off tanks and correct any leaks before continuing.
Repeat this step if you have to correct leaks until none
are found.
4. Make certain that the main and remote switches are
in the "OFF" position. Slowly open each tank valve
fully. Connect electrical power cord to a 110 volt A.C.
power source.
NOTE: The pilot hose is equipped with a safety P.O.L. fitting.
If the valve on the pilot fuel container is turned on too
quickly, the P.O.L. fitting will check (you may hear a click)
just as it would if the hose ruptured. This check valve
restricts flow and will result in failure of the pilot to light or
result in an insufficient pilot flame. REMEMBER, ALWAYS
TURN THE TANK ON SLOWLY!
5. After making certain the remote switch is in the
"OFF" position, move the main switch to the "ON"
position. The RED indicator light will come on. The
pilot torch should now automatically light.
NOTE: It is possible you will hear the buzzing sound of
the electrical spark attempting to light the pilot burner.
The ignition system will cycle in seven seconds. The
ignition system will attempt to re-light after a 7 second
delay. A third ignition will be attempted. Failure to
establish a pilot results in the unit locking out.
Should the pilot not achieve ignition, turn the main
switch "OFF", wait 30 seconds and start again. It
may be necessary to repeat this procedure several
times to purge sufficient fuel through the pilot fuel
lines.
Once the pilot is burning, the system will continue
to monitor itself. If the pilot torch goes out, an
automatic relight is attempted. If reignition does
not occur within 10 seconds, the system will
automatically shut down and the operator should
start again at step 4 in these instructions.
6. After pilot is ignited, move the remote switch to
the "ON" position to start evacuation of the main
tank.Leak test hose connections from torch and
flare tube to the solenoid control box using soapy
water or commercial leak detector.
LIGHTING PROCEDURES
SHUT DOWN PROCEDURES
1. Turn the valve off on the tank being evacuated and allow all LP-Gas to escape from the fuel line.
2. Turn the remote switch to "OFF".
3. Close the pilot tank valve.
4. After pilot has burned out, turn main switch to "OFF".
5. Disconnect the unit from the power supply and disconnect hoses from both tanks.
Before Starting, Make sure the "Main" switch and the "Remote" switch are in the "OFF" position.

FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com 6
CARE AND MAINTENANCE
1. Check all screws on the terminal strips in the electronic control box for tightness before and after each use.
Tighten if needed.
2. Store the unit in a dry place to protect the burners and ignition system components.
3. Always leak check all connections before each use and correct as necessary before lighting. DO NOT operate
the unit if any leaks are present.
RED DRAGON PROPANE FLARE OPERATING INSTRUCTIONS
TROUBLE SHOOTING TIPS
Ignition and Heat Sensor:
The ignition and heat sensor electrodes can be sensitive. If unit is not lighting or staying lit, make sure the electrodes
have a 90° angle and that the gap between the ignitor and the ground is 1/4". The ignitor and ignitor ground wire
should be over the pilot torch bell an 1/8" - 1/4" and the heat sensor wire should just barely cross the edge as
shown below.
The flare solenoid will only activate when pilot flame is sensed. If flare solenoid fails to activate double check the
position of the heat sensor wire and make sure it is positioned as shown below.
Electrode Box
Electrode Box
Electrode Electrode
Approx. 1"
Pilot Torch
Ignitor
Heat
Sensor
Ignitor
Ground
Heat
Sensor
Ignitor
Ground Ignitor
Evacuation
Flare Tube
1/4"
Gap
Make Sure The Electrodes are
Positioned as Shown Here.
To test the ignition:
Make sure both fuel source valves are "CLOSED" (Pilot Tank and Main Fuel
Source to be flared). Turn the main switch to "ON" and then turn the remote
switch to "ON" and watch for a strong spark between ignitor and ground. If a
stong spark is not noticed turn switches off and adjust electrodes as shown in
these diagrams. Keep hands and head a safe distance away from the flare
head as there may be a small amount of fuel left in the lines.
Flaring in the Wind:
The Red Dragon Flare can operate in winds up to 25 mph. It may be necessary to
rotate the flare so the electrodes and heat sensor are situated in the pilot flame but
not exposed to the fuel coming from the evacuation flare tube.
Wind Direction
Flaring in the Rain:
Flaring may not be possible in rainy conditions. Rain may extinquish the pilot
or cool the heat sensor enough to where it will shut-down the flare solenoid.
WARNING:
Keep all parts of the body away from the
electrodes. This system creates a high
voltage spark and can cause injury or death.
DO NOT service this unit if you have a
pacemaker.

FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com 7
Lengthy Flare Jobs and the Pilot Fuel Source:
Always use a separate cylinder for the pilot source and have more than one pilot cylinder available for lengthy
flaring situations. The pilot fuel source may become empty or drop below 18 P.S.I. and have to be replaced
before the tank being evacuated is completely empty. When the pilot tank empties or drops below 18 P.S.I.
the pilot will/may quit burning and raw LP gas could be released into the atmosphere. Follow the shut-down
procedures and replace the pilot cylinder. Repeat lighting instructions to continue.
IMPORTANT NOTE: YOU SHOULD NOT USE THE SAME TANK YOU ARE EVACUATING FOR YOUR
PILOT SOURCE.
Tank Freeze-Up and the Refrigeration Effect:
Tank freeze-up or pressure loss may occur when evacuating vapor withdrawl containers, especially while
operating at outside temperatures below 50° F. Pilot containers may also be effected. Frost build up on the
outside of the tanks, fittings and hoses are indicators of excessive refrigeration.
If the tank being evacuated is losing pressure, yet still contains fuel, you may be required to cease the flaring
procedure for a few minutes to let the tank defrost. This effect can and will happen to the fuel tank being
evacuated. Other side effects are the flare tube may accumulate frost (the frost in this case contains
propane). In the right conditions this frost is flammable.
If the pilot tank is losing pressure or freezing up, replace it with a larger cylinder.
As the evacuation tank pressure drops, the speed of the process is reduced.
The fuel in the LP cylinder is being evacuated and burned at tank pressure. As the fuel is being consumed the
pressure in the cylinder will drop. Outside temperature also has a direct effect on tank pressure.
Therefore, the flare will not produce 529 gallons per hour consumption up to the very last second. A fuel
cylinder being evacuated on an 85 degree Fahrenheit day will flare faster than a fuel cylinder being evacuated
on a 40 degree Fahrenheit day.
Flaring In Extreme Conditions:
Certain components of the Ignition and Solenoid Control Box are not designed to be operated in temperatures
exceeding 125° F (54° C) or below -20° F (-32° C).
TROUBLE SHOOTING TIPS AND OTHER FLARING RULES TO REMEMBER:
NOTES
RED DRAGON PROPANE FLARE OPERATION INSTRUCTIONS

FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com 8
RED DRAGON PROPANE FLARE OPERATING INSTRUCTIONS
REPLACEMENT PARTS LIST
DESCRIPTION.....................................................................Part No.
FLARE HEAD:
Pilot torch/flare tube assembly:
For Model PF-16 LPS 1/2" Flare .................................. VT 3-12 PF-16
Electrode assembly:
Electrode (Ignitor and Heat Sensor)...............................................26
Electrode Box and Cover...............................................................36
Hi Temp Wire Insulator...............................................................26-2
HOSES:
1/4" Pilot Hoses:
65" Hose – Solenoid Control Box to Pilot Torch ...................... HP65T
10' Hose – Pilot fuel source to Solenoid Control Box ............ HP10C
Flare Hoses:
Hose From Solenoid Control Box to Flare Tube
For Model PF-16 LPS 1/2" Flare ............................... 60" – HP1/2-5TS
25' Hose From Main Tank to Solenoid Control Box
For Model PF-16 LPS 1/2" Flare ..............................25' – HP1/2X25S
REGULATOR:
25 lb. Preset Regulator For Pilot Tank....................................567 RC
TANK CONNECTIONS:
Safety P.O.L. For Pilot Tank Connection ............................P-3200 W
Commercial Tank Connector for 1/2" Flare Line......................F-3175
PRESSURE GAUGE AND PRESSURE RELIEF VALVE:
300 lb. Pressure Gauge for Main Tank....................................... G-25
400 P.S.I. Pressure Relief Valve For Evacuation Hose .............. H400
CONTROL BOXES AND INDIVIDUAL COMPONENTS:
Complete Controls: Electronics Control Box, Solenoid
Control Box, Electrode and Remote Switch
For PF-16 LPS 1/2" Flare .................................................... CS603
Electronic Control Box (Top Box) & Electrode Components:
Main ON/OFF Toggle Switch ............................................... M 3008
Main ON Indicator Light...............................................................330
Ignition Control Box ........................................................... Model 24
Wiring Harness For Ignition Control Box ........................Model 24W
Transformer (output is 24 V / 60 VA)..............................................28
Terminal Connection Strips................................................ 29 & 29-8
Remote Switch with 20' connection wire ................................PFRS
10' 110 Volt A.C. Power Cord..................................................PFPW
10' Sensor Cable......................................................................PFSW
10' Ignition wire ........................................................................ PFIW
Electrode (Ignitor and Heat Sensor)...............................................26
Electrode Box ................................................................................36
Hi Temp Wire Insulator...............................................................26-2
Solendoid Control Box Components (Bottom Box):
24 Volt A.C. normally closed solenoid valves:
1/4" Solenoid for pilot on all Solenoid Control Boxes............... S-124
1/2" Solenoid for PF-16 LPS 1/2" Flare ..................................... S-126 Pilot
Solenoid
Flare
Solenoid
Transformer
Ignition
Control Box
Terminal
Strip
Remote
Switch Plug
Main
Switch
Main Indicator
Light
Pilot Torch/Flare
Tube Assembly
Electrode Box
(Part # 36)
Heat
sensor
Ground
Ignitor
Electrode
(Part # 26)
Hi Temp Wire
Insulator (Part # 26-2)
Miscellaneous Parts:
Flare Tower Retaining Pin ..................................G-21
Tripod Leg Retaining Pins ...........................G-21-2 (3)
Control Box Receiver Plate..............................PF-TA

FLAME ENGINEERING, INC. • P.O. Box 577 • West Highway 4 • LaCrosse, KS 67548
800-255-2469 • 785-222-2873 • Fax 785-222-3619 • www.FlameEngineering.com
PFLPS Instruction Manual 7-2012
Table of contents
Other Red Dragon Flashlight manuals