
RF WIRELESS INTERCONNECTION
PLANNING
MAINTENANCE, REPAIRS, AND SERVICE
Developing and implementing an escape plan is crucial for ensuring the safety of your
household in the event of a fire. To do so, it is recommended that you follow the steps
outlined below:
• Create a floor plan that identifies all doors and windows, as well as at least two escape
routes from each room. Note that for second-storey houses, rope or chain ladders may
be necessary.
• Hold a family meeting to discuss and review your escape plan, ensuring that each
member understands what to do in case of a fire.
• Designate a predetermined location outside of your home where all family members
can meet in the event of a fire.
• Ensure that everyone is familiar with the sound of the smoke alarm and conduct regular
practice drills of leaving the home when it goes off.
• Conduct fire drills at least every six months, including night-time drills.
• Practicing your escape plan allows you to test its effectiveness before an actual
emergency. It is crucial that every member of the household is aware of the plan, as
they may need to act quickly and independently in the event of an emergency.
IN CASE OF FIRE
• Leave the building immediately using your pre-determined plan of escape. Time is of
the essence, so do not waste time getting dressed or retrieving valuables.
• When exiting, do not open any internal doors without first feeling the surface. If the
door is hot or smoke is seeping through cracks, do not open it. Instead, use your
alternative exit. If the door is cool, place your shoulder against it, open it slightly, and
be prepared to shut it quickly if heat or smoke rush in.
• Stay close to the floor if the air is smoky and breathe shallowly through a wet cloth if
possible.
• Once outside, proceed to your designated meeting place and ensure that all family
members are present.
• Call the Fire Brigade from a neighbor's home, not from your own.
• Do not re-enter your home until officials confirm that it is safe to do so.
For additional information on fire safety, please contact your local Fire Brigade.
Developing and practicing a plan of escape is essential for ensuring the safety of your
household in the event of a fire. When the smoke alarm sounds, it is crucial that you
follow the steps outlined below:
If you observe any indication from the smoke alarm
and are uncertain about its condition, please refer to
the table below for the "LED Indicator" and "Siren" of
your smoke alarm. The table will help you determine
the current status of the alarm and the appropriate
action to be taken.
If you require further assistance, we recommend
reaching out to our technical support for inquiries.
You can find the contact details in this manual.
When it comes to maintaining, repairing, and servicing your smoke alarm, it is important
to follow proper guidelines. Please refer to the information below:
Maintenance:
To ensure optimal performance, it is recommended that the smoke alarm be inspected
monthly to check for dirt, dust, and insects. The alarm can be vacuumed or brushed with
a soft brush to remove accumulated dust, dirt, or kitchen grease. Additionally, applying a
small amount of surface spray to a cloth and wiping around and over the alarm which will
should deter insect ingress. After cleaning, always test the smoke alarm to ensure that it
is functioning correctly.
Repairs / Service:
In the event that the smoke alarm is defective, refrain from tampering with the unit. The
unit does not contain any user-serviceable parts. Seek professional assistance for
repairs or servicing.
LIMITATION OF SMOKE ALARMS
• When discussing the limitations of smoke alarms, it's important to keep the following
points in mind:
• Smoke alarms can only detect smoke if it reaches the device. This means that fires that
start in areas far away from the alarm, such as chimneys, walls, roofs, or another floor
of the building, may not be detected.
• If the smoke alarm is located outside of the bedrooms or on a different floor, it may not
be able to wake up individuals who are sound sleepers. For this reason, it is
recommended that a smoke alarm be installed in each bedroom to provide additional
protection.
• While smoke alarms can provide early warning of a fire and help save lives, they should
not be considered as an alternative to an insurance policy.
• Standard smoke alarms will not alert individuals who are hearing impaired. Special
purpose devices such as the Red Strobe Light and Vibrating Pad for Hearing Impaired
should be used in these cases to ensure that everyone in the building is alerted in the
event of a fire.
• By keeping these limitations in mind, individuals can take steps to maximize the
effectiveness of their smoke alarms and ensure that they are taking all necessary
precautions to protect themselves and their property from the dangers of fire.
•
This smoke alarm has a built-in Hush or Silence feature incorporated into the
Test/Hush button. If cooking or other non-hazardous sources cause the alarm to sound,
it can be temporarily Hush by depressing the Test/Hush button for 1 second.
The alarm
will then enter a dormant period for 10 minutes.
After the 10 minute dormant period, the smoke alarm will resume normal operation.
Note: After the Test/Hush button has been pressed, wait 10 minutes before any
additional testing is conducted to avoid any abnormal responses as the smoke alarm is
not sensitive to smoke during this period. See Fig.12 for details.
•
This smoke alarm has a self-diagnosis. If the smoke alarm detects the battery is low
and/or an internal fault, it will chirp. This alarm could be temporarily silenced by holding
the Test/Hush button for 1 second. The alarm will not chirp for 10 hours but the LED will
remain functioning. It is recommanded to replace the smoke alarm as soon as possible
after this period of time.
Note: Silence will not affect the basic fire warning functions of a smoke alarm. During
the silenced period, if the smoke alarm detects any smoke, it will still operate fire
warning (Rapid flashing red LED and chirping). See Fig.12 for details.
HUSH OR SILENCE FUNCTION
This smoke alarm has a built-in feature to detect the power source.
If the A (Active) connection is present and the alarm is activated, it operates as a
220-240V mains-powered smoke alarm. In this case, the battery acts as a backup and
lasts for 10 years from installation. See Fig. 7 for instructions on activating the
smoke alarm.
If the A (Active) connection is not present and the alarm is activated, it relies solely on
battery power. The battery, under normal conditions, lasts for 10 years from installation.
Instructions for activating the smoke alarm can be found in Fig.7.
OPERATION
TESTING
TESTING
• Before testing, please ensure that the smoke alarm has been activated, either through
its battery or AC power supply.
• Regularly testing the smoke alarm is crucial to ensure its proper functioning and early
detection of fires, regardless of whether it is powered by a battery or AC power.
1) To perform the test, press and hold the "HUSH/TEST" button for 1 second. This will
activate the alarm, indicating that the electronic circuitry and horn are functioning
correctly.
Note: If the alarm does not sound during the test, please check the battery or AC
power supply and ensure that the smoke alarm is connected to a continuous final
sub-circuit.
Note: At the same time, any alarm that is RF paired to the RF network or hardwire
interconnected to the smoke alarm will also be triggered within 30 seconds.
2) To deactivate the smoke alarm from the test mode, briefly press the test button once
again.
Note: Continuous chirping, erratic noise, or a low sound from the alarm may indicate a
defective alarm. In such cases, please return the unit to the place of purchase.
WARNING: Never use an open flame of any type to test your alarm. Check that all
interconnected smoke alarms operate during the test.
WARNING: Do not apply excessive force on the “HUSH/TEST” button this may
damage the smoke alarm and may void the warranty.
CAUTION: Smoke alarm should be tested on a monthly basis. To accurately test
the integrity of the sensing chamber use a smoke detector (aerosol) tester.
• Adjust the angle of the RF Module to be parallel
with the alarm unit and gently push the RF Module.
Please refrain from applying excessive force to
avoid damaging the RF Module. If the RF Module
does not fit into the alarm immediately, readjust the
angle of the RF Module and reinsert it.
• The alarm unit will have click sound to indicate the
RF module has been installed into the alarm unit.
INSTALL THE RF MODULE INTO THE ALARM
UNIT:
REMOVE THE MODULE CHIPS
FROM THE ALARM UNIT:
RF WIRELESS PAIRING INSTRUCTION
• To detach the alarm unit from the flush
mount base, utilise an insulated
screwdriver to press the button located
at the two arrow points. See fig.10.1
• Grasp the alarm unit firmly and utilise an
insulated screwdriver to push the head of
the RF Module, thereby removing the RF
module from the alarm unit. See fig.10.2.
PAIRING
• RFMDUAL as Master
– Press and hold the test button for 10
seconds until the alarms red LED turns
solid.
• RFMDUAL as Slave
– Press the test button 2 times quickly,
Alarm LED will flash for 5 times to
indicate successfully connection.
TESTING
• Follow steps in Section - “Testing” Press
and hold the test button 1 second, then
release.
• Smoke alarm will go off, paired smoke
alarms will also go off within 60 seconds.
Alarm red LED will flash for 60 seconds.
Clear Pairing Memory
– Press the test button 5 times, Alarm red
LED will flash for 10 times.
Fig.9
Fig. 10.2
Fig. 10.1
TEST/HUSH
& RF-PAIRING
BUTTON
Fig. 11
Memory Function
If one of the alarm indicators (RED LED) is flashing every 4
seconds, it indicates that a smoke alarm has previously been
activated.
Every
4 sec
Red
Standby
The red LED flashes once every 48 seconds to indicate the smoke
alarm and battery are functioning correctly.
Every
Red
40-60 sec
Low Battery
The smoke alarm signals low battery by flashing the red LED once
and emitting a chirp every 48 seconds.
Every
Red
40-60 sec
85dB
Fire Alarm
The smoke alarm will sound a loud alarm (85 dB) and the red LED
will flash rapidly. This will continue until the air is cleared.
85dB Red
Green LED
The green LED is illuminated when the mains power (220-240V) is
on. If the smoke alarm is powered only by battery. The Green LED
will not illuminated.
AC
Powered
Green
Featured LED and Alarm Signal
Green LED
Fig.12
HUSH
10 Minutes
SILENCE
10 Hours
False alarm
(Nuisance Alarm)
Low Battery
and/or
Fault Alarm
Red Smoke Alarms PTY. LTD. reserves the right to change specifications,modify designs
and discontinue items without incurring obligation and whilst every effort is made to ensure
that descriptions, specifications and other information in this catalogue are correct, no
warranty is given in respect of these of and the company shall not be liable for any error
therein.
© Red Smoke Alarms 2023
This material copyright under Australian and international laws. Except as permitted under
the relevant law, no part of this work may be reproduced by any process without prior
written permission of and acknowledgment to Red Smoke Alarm PTY. LTD..
WARRANTY
WARNING: DO NOT ATTEMPT TO OPEN THE HOUSING.
Red Smoke Alarms warrants the RFMDUAL to be free from defects in materials and
workmanships under normal use and service for a period of ten years from manufacture
date. The company will not be obligated to repair or replace parts which are found to be in
need of repair because of misuse, damage or alterations that occur after the date of
purchase. Return the RFMDUAL smoke alarm with proof of purchase to your local
distributor. The liability of the company arising from the sale of this RFMDUAL Smoke
Alarm shall not in any case exceed the cost of replacement and in no case shall the
company be liable for consequential loss or damages resulting from the failure of the
RFMDUAL Smoke Alarm.
RED SMOKE ALARMS PTY. SHALL HAVE NO LIABILITY FOR ANY PERSONAL
INJURY OR PROPERTY DAMAGE, OR ANY SPECIAL INCIDENTAL, CONTINGENT OR
CONSEQUENTIAL DAMAGE OF ANY KIND RESULTING FROM A FIRE. THE EXCLU-
SIVE REMEDY FOR BREACH OF THE LIMITED WARRANTY CONTAINED HEREIN IS
THE REPAIR OR REPLACEMENT OF THE DEFECTIVE PRODUCT AT RED SMOKE
ALARMS PTY. LTD. OPTION. IN NO CASE SHALL RED SMOKE ALARMS PTY. LTD.’S
LIABILITY UNDER ANY OTHER REMEDY PRESCRIBED BY LAW EXCEED THE
PURCHASE PRICE. YOUR RFMDUAL SMOKE ALARM IS NOT A SUBSTITUTE FOR
PROPERTY, DISABILITY, LIFE OR OTHER INSURANCE OF ANY KIND. APPROPRI-
ATE COVERAGE IS YOUR RESPONSIBILITY. CONSULT YOUR INSURANCE AGENT.
This does not affect your statutory rights.
This device is only suitable for single occupancy private dwellings only and not intended for
multi occupancy private dwellings or commercial or industrial dwellings.
Waste electrical products should not be disposed of with normal household waste. Please
recycle where facilities exist. Check with your Local Authority or retailer for recycling
advice. New regulation will encourage the recycling of Waste from Electrical and Electronic
Equipment (European "WEEE Directive" effective August 2005).
INDICATION AND ACTION
LED SIRENSTATUS ACTION NEEDED
INDICATOR
Green LED
illuminated
Red LED 1
flash every
48 seconds
None
Standby
Mode
(240v AC
mains
powered)
Red LED
flashing
rapidly until
smoke is clear
chirping
rapidly until
smoke is
clear
Fire Alarm
Mode
Smoke alarm in
standby condition,
powered by 240v AC
mains and backup
battery. No action
required.
Smoke Alarm detects
fire. See Section - “In
case of fire”
Red LED
flashing
rapidly for 3
seconds and
remain
illuminated for
60 seconds (if
without
deactivation)
chirping
rapidly for 3
seconds only
Fire Warning
Mode
Activate the test mode
by holding the test
button for 1 seconds.
Deactivate the test
mode by pressing the
test button 1 time.
See Section -
“TESTING”
Red LED 1
flashes every
48 seconds
1 short chirp
every 48
seconds
(Chirp pattern
sync with the
Red LED)
Low Battery
Warning The battery is low.
Check Section -
“Maintenance, Repairs,
and Service” for further
instruction.
Red LED 1
flashes every
4 seconds,
lasting 72
hours
None
Memory
Function
This indication will last
for 72 hours. Then, it will
automatically resume to
standby mode. No
action required.
Red LED 2
short flashes
every 48
seconds
2 short chirps
every 48
seconds
(Chirp pattern
sync with the
Red LED)
Unit Fault The alarm unit is faulty.
Check Section -
“Maintenance, Repairs,
and Service” for further
instruction.
Green LED
not illuminat-
ed
Red LED 1
flash every
48 seconds
None
Standby
Mode
(Powered by
Battery only)
Smoke alarm in
standby condition,
powered by internal
sealed battery power.
No action required.
Smoke Alarm Indication:
Red LED will flash rapidly for 3 seconds, then stay
solid
Red LED will turn off
Activation / Deactivation
Activate test mode: hold the test button for 1
second. (test mode will last for 60 seconds)
Deactivate the test mode: press the test
button for 1 time.
Contact Details
RED SMOKE ALARMS PTY. LTD.
35 Hitech Drive, Kunda Park QLD 4556
www.redsmokealarms.com.au
1300 316 552