Redbusbar SmokeSight User manual

SmokeSight SS10MANN V0.6
Page 1
SmokeSight Residential Smoke Alarm
By Redbusbar
Part Number: SS10MANN
Description: 240 VAC Mains Power Photoelectric Smoke Alarm with 2xAA 1.5VDC Battery Backup
PLEASE LEAVE THESE INSTRUCTIONS WITH THE OCCUPANT, TO BE RETAINED FOR THE LIFE OF THE ALARM.
THIS SMOKE ALARM MUST BE INSTALLED BY A LICENSED ELECTRICIAN.
1Read all Instructions before Installation and Operation
Regular testing of this smoke alarm is necessary to ensure the unit is functional and that the battery is in good
condition. It is recommended that the smoke alarm be replaced after 10 years of normal service. The only user-
serviceable parts are the replaceable backup batteries. Refer to ‘Replacing the Backup Batteries’.
RISK OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• This product must only be installed and serviced by
appropriately qualified and/or licenced electrical
personnel.
• This product must only be used for the purpose
described in these instructions and must be installed in
accordance with the local regulations.
• Hazardous voltages may be present at wires
connected to this product.
• Before working on this product, isolate the electrical
supply.
• Ensure that the product has been correctly installed
and tested for safe operation before reconnecting the
electrical supply.
Failure to comply with these instructions may result in
death or serious injury.
EQUIPMENT INSTALLATION HAZARD
• This alarm cannot be operated from power derived
from a square wave, modified square wave or modified
sine wave inverter. These inverters are sometimes
used in off grid installations such as solar or wind
power sources. They produce high peak voltages that
will damage the alarm.
• Ensure that the mains supply, active and neutral is
wired to the correct terminals.
• Ensure that green LED is ON when mains supply is on.
• Ensure that red LED is not fast flashing.
• Smoke Test each interlinked alarm. Check to ensure
every interlinked alarm, alarms correctly. If any unit
fails to alarm, check all wiring and connections.
Failure to follow these instructions may result in
equipment damage or injury.
Smoke Alarm –Top View
Smoke Alarm –Bottom View
1. Mains (Green) LED
2. Alarm (Red) LED
3. Smoke Alarm Backup
Battery Holder
1
2
3

SmokeSight SS10MANN V0.6
Page 2
Mounting Base –Top View
Mounting Base –Bottom View
4. Locking Tab
5. Tamper Clip
6. Mains Lid
7. Mains, Loop and
Interlink Terminals
2Specifications
Application
Residential Smoke Alarm for domestic
dwellings
Environment
Altitude: 0m to 2,000m
Temperature: 0°C to 40°C
Humidity: 5% to 95%
Installation
Ceiling or wall mounted
Audible
Indication
Alarm: 85dBA at 3m, ISO 8201
Battery Low: Chirp
Primary
Power Supply
220/240VAC, 50Hz, 30mA
Visual Indication
Mains Supply: Green LED
Alarm: Red LED
Terminals
4 Screw Terminals
Voltage Rating: 300VAC
Conductor Size: 2 × 1.5 mm2, min
cable size: 1mm2
Interlink
Wired: 40 alarms over 150 metres
maximum
Secondary
Power Supply
2 x 1.5VDC AA Batteries
Compliance
AS 3786:2014, AS/NZS 60065,
AS/NZS 60950.1, IEC 62599.2
Sensing Type
Photoelectric. The smoke alarm
contains NO radioactive material
3Locations
This smoke alarm can be used in all residential homes and apartments and positioned in accordance with building
regulations and state legislation. Refer to figure below when deciding the number of and location of smoke alarms.
Avoid dead air space positions. Install smoke alarms along exit paths from bedrooms. Locate alarms in stairways as
stairways act as chimneys for smoke and heat. Locate a smoke alarm in any area where a smoker sleeps or where
electrical appliances are used in bedrooms. Smoke, heat and other combustion materials rise to the ceiling and
spread horizontally. In a residential dwelling, mount the smoke alarm in the centre of the ceiling. In mobile homes,
wall mount the smoke alarm on an inside partition to avoid the thermal barrier that may form under the ceiling.
5
4
5
6
5
5
7
4

SmokeSight SS10MANN V0.6
Page 3
4Locations to Avoid
Within 1 metre of air conditioner ducts, ceiling fans and other high air flow areas. Smoke may be blown away or
diffused in these areas.
In areas where the temperature may fall below 0°C or rise above 45°C. Failure to alarm, improper alarms or
nuisance alarms may result.
In damp or very humid areas such as bathrooms or laundries, where the normal humidity may rise above 95% or
fall below 5% relative humidity. False alarms and unstable operation may result.
In areas where particles of combustion are normally present, such as garages or kitchens, as this can cause false
alarms.
In dusty or dirty areas, as an accumulation of dust and dirt in the sensing chamber may block the openings and
prevent an alarm, or may cause false alarms.
Where bugs or insects are present as they may block the openings and prevent an alarm, or may cause false
alarms.
Within 1 metre of electrical noise sources, e.g. fluorescent lights, LED lights and fan motors. Electrical noise may
cause nuisance alarms.

SmokeSight SS10MANN V0.6
Page 4
5Wired Interlinked Smoke Alarms
Interlinking smoke alarms ensures that if one alarm
senses smoke, all of the connected alarms will operate
(alarm). While all interlinked alarms will sound, only the
alarm(s) that sensed smoke will fast flash their red LED. A
signal is applied to the interlink wire (referenced to
neutral) to connect to the other interlinked alarms.
Alternate smoke alarms (Part# SS10MAMA or SS10LNAN)
may be purchased separately if wired connection is not
possible. Refer to ‘Installation’ for the interlink
connection arrangement.
EQUIPMENT INSTALLATION HAZARD
• All interlinked smoke alarms must be supplied from the
same circuit. A common Neutral must be used
• DO NOT connect the Interlink wire to Active or Neutral.
• Maximum of 40 interlinked smoke alarms.
• Only SmokeSight alarms can be interlinked.
Failure to follow these instructions may result in
equipment damage or injury
6Installation
1. If tamper prevention is required, prevents alarm removal without the use of a tool, remove the Tamper Clip
from the mounting base by twisting it back and forth until it breaks loose.
2. Strip the Active, Neutral and Interlink (if used) wires. Use a minimum of 1mm2250VAC insulated wire for all
wiring, including the interlink wiring.
3. Connect the wires to the correct terminals on the base and ensure that the terminal screws are tight.
4. Slide the terminal cover closed to avoid contact with the live terminals.
Mains Supply
220-240VAC
Active (A) –Red
Neutral (N) –Black
InterLink (IL) - Optional
5. Screw the mounting base onto the ceiling or wall using appropriate fasteners. Screw diameter 8gauge/4mm.
6. Apply smoke alarm power by installing 2xAA batteries into the into the bottom battery bay of the smoke alarm.
7. Engage and slide the smoke alarm along the mounting base until it is fully home and it ‘clicks’. The smoke alarm
will only travel home and click if the smoke alarm batteries are installed. Note: Do not attempt to slide the alarm
onto the mounting base unless the smoke alarm batteries are installed as damage may result.

SmokeSight SS10MANN V0.6
Page 5
Ready to slide
Engages with a ‘click’
Slide
8. Turn on the mains power and check that the green and red LEDs function. The Green LED should illuminate to
show mains power present. The red LED will flash every 5mins and 45secs to indicate correct operation and that
the battery backup is functional.
9. Press the Test+Hush button to check that the alarm sounds.
10. If tamper prevention is required, slide the Tamper Clip between the ceiling and the mounting base, locking tab.
The Tamper Clip can be removed by gripping it with pliers and pulling the clip away from the smoke alarm.
Loose Tamper Clip
Tamper Clip Installation
Tamper Clip Installed
Installation is not complete until the green and red LEDs are functioning correctly and the alarm has been checked
for correct operation.
7Overview
Once the mains supply is connected or the backup batteries are installed correctly, the smoke alarm is operational. If
smoke is detected the alarm will sound and the red LED will flash rapidly. This will continue until the air is cleared of
smoke. During normal operations the red LED flashes once every 5mins and 45secs to indicate that the smoke alarm
and battery backup is functional. The green LED is illuminated when the mains power is applied.
7.1 When the Alarm Sounds
1. Alert small children in the home.
2. Leave immediately by your plan of escape. Don’t waste time getting dressed or picking up valuables.
3. When leaving, don’t open any inside door without first feeling its surface. If hot, or if you see smoke seeping
through cracks, don’t open that door! Instead, use your alternate exit. If inside the door is cool, place your
shoulder against it, open it slightly and be ready to slam it shut if heat and smoke rush in.
4. Stay close to the floor if air is smoky. Breathe shallowly through a wet cloth if possible.
5. Once outside, go to your selected meeting place and make sure everyone is there.
6. Call the Fire Brigade from your neighbour’s home - not from yours!

SmokeSight SS10MANN V0.6
Page 6
7. Don’t return to your home until officials say that it is safe to do so.
For further information on fire safety contact your local Fire Brigade.
7.2 Testing
TEST THE SMOKE ALARM ONCE PER MONTH TO ENSURE CORRECT OPERATION. Test by pushing the Test+Hush
button on the smoke alarm until the alarm sounds. The alarm will sound if all electronic circuitry, horn and battery
are functional. Any Interlinked alarms will also sound. If no alarm sounds, check that the battery is installed correctly
or replace the battery. If the battery is new and installed correctly and the alarm still doesn’t sound, replace the
smoke alarm. If the smoke alarm is installed in a mobile home, test weekly and after every journey. After the
Test+Hush button has been pressed, wait 10mins before any additional testing is conducted to avoid any false alarm
responses as the alarm is in reduced sensitivity mode during this period. Refer to ‘Hush’.
IMPORTANT: If premises are unoccupied for a period of time (more than a few days) then a battery test should be
undertaken upon return. If the low battery warning sounds, test and replace the battery if necessary.
Never use an open flame of any type to test your alarm. Check that all interlinked smoke alarms operate during
the test.
7.3 Hush
This smoke alarm has a built-in Hush feature incorporated into the Test button. If cooking or other non-hazardous
sources cause the alarm to sound, it can be temporarily silenced by pressing the Test+Hush button. The alarm then
enters a low sensitivity period for 9mins. If the smoke density increases during this period from a smoke or fire
event, the unit will go into alarm mode.
Before using the alarm HUSH feature, identify the source of smoke and be certain that a safe condition exists.
7.4 Replacing the Backup Battery
The backup power to the smoke alarm is supplied by 2xAA 1.5VDC alkaline
batteries, located in the bottom battery bay of the smoke alarm. The
batteries should last a minimum of five years under normal operating
conditions. An audible chirp once every 40 to 50 secs indicates that the
battery needs to be replaced. Pressing the Test+Hush button will silence
the low battery chirp for up to 8 hours. It is recommended to replace the
batteries on a memorable day eg 1st April, April Fool’s Day.
RECOMMENDED BATTERIES: Energizer E91, Duracell MN1500, Fujitsu LR6
TEST THE OPERATION OF THE SMOKE ALARM BY PRESSING THE
TEST+HUSH BUTTON AFTER BATTERY REPLACEMENT
8Troubleshooting
The SmokeSight smoke alarm constantly monitors its internal functions to maintain your safety. If it is alarming or
chirping, note answers to the following questions to diagnose the problem, and your solution:
1. If it’s alarming (3 loud tones repeating every 1.5 seconds), refer to smoke alarm troubleshooting below.
2. If it’s not alarming but instead chirping (1 or more beeps every 5 minutes), refer to smoke alarm
troubleshooting below.

SmokeSight SS10MANN V0.6
Page 7
8.1 Smoke alarm troubleshooting
CONDITION
CAUSE
REMEDY / ACTION
ALARMS & TEST+HUSH
Alarm sounds and the red
LED is blinking rapidly.
Smoke has activated the smoke
alarm
If the cause is unknown, vacate the
building immediately and call the Fire and
Emergency Services.
If the cause is known to be a false alarm,
see “False Alarm” section below.
Alarm sounds but the red
LED is OFF.
Smoke has activated an interlinked
alarm, located somewhere else in
the dwelling.
Smoke alarm is sounding, it
does not stop when
Test+Hush is pressed.
Smoke density is too high, even in
low sensitivity mode, for the Hush
feature to activate.
Smoke alarm is sounding, it
stops when Test+Hush is
pressed.
Low sensitivity mode has been
activated for 9mins
Make sure you are safe and have
eliminated the source of the smoke. See
“False Alarm” section below.
While the Test+Hush
button is pressed the alarm
sounds
The smoke alarm is indicating that
all electronic circuitry, siren and
battery are functional.
Normal test condition. Test regularly to
ensure proper operation
While the Test+Hush
button is pressed the alarm
does not sound
The smoke alarm may not be
operating correctly.
Check that the green LED is ON and the
red LED flashes once every 5mins. If
problem persists contact an electrician for
replacement.
CHIRP
One audible chirp every 40
to 50secs (no LED flash)
Low battery warning.
Replace the 2xAA 1.5VDC batteries. Press
the Test+Hush button to silence the low
battery chirp for up to 8 hours.
Three audible chirps every
40 to 50secs (no LED flash)
The smoke alarm may not be
operating correctly.
Clean smoke alarm according to
“Maintenance, Repairs and Service”
section. If problem persists contact an
electrician for replacement.
LED
Green LED ON.
240VAC mains supply ON.
Normal operating condition
Green LED OFF.
240VAC mains supply OFF.
Check that mains power is ON. Main
circuit breaker may have tripped. Wiring
could be incorrect.
Red LED flashes every
5mins and 45secs.
The smoke alarm is functioning
correctly.
Normal operating condition.
Red LED flashes every 8 to
12secs.
The smoke alarm is in low
sensitivity mode. Test+Hush
button has been pressed.
Wait 10mins to return to normal operating
mode.
OTHER
Smoke alarm will not slide
along the base until it
clicks.
Battery or batteries missing
Install missing battery or batteries
8.1.1 False Alarm
In the event of a false alarm (alarms are sounding without any smoke present):
1. Identify which smoke alarm/s are in alarm state –Look for the alarm/s sounding and with red LED fast flashing.
2. On each smoke alarm in alarm state press the Test+Hush button to silence the alarm
3. Disconnect all smoke alarms in the alarm state by removing them from their base.

SmokeSight SS10MANN V0.6
Page 8
4. Clean smoke alarms in accordance with the “Maintenance, Repairs and Service”section.
5. Re-install and test all the smoke alarms.
9Maintenance, Repairs and Service
It is recommended that the smoke alarm is inspected monthly to ensure it is free from dust, fibres and insects.
9.1 Cleaning
1. Remove smoke alarm power
2. Clean the sensor chamber using a vacuum or can of compressed air. Do not use an air compressor as it will
damage the smoke alarm as the air is not dry or clean. Place the nozzle near the alarm lip, adjacent to the
wording “To remove –Push rear tab <<< slide” and slanted upwards toward the cover.
3. Turn the smoke alarm over (top cover facing down) and repeat the clean
4. Tap the smoke alarm lightly on a hard surface to dislodge attached foreign bodies
5. Repeat the clean
6. Turn the smoke alarm over (top cover facing up)
7. Repeat steps 4 and 5
8. Apply smoke alarm power and wait for 1 minute
a. If the alarm starts sounding the smoke alarm has not/cannot be cleaned properly
b. If the alarm does not sound reinstall the cleaned smoke alarm
ALWAYS TEST THE SMOKE ALARM AFTER CLEANING.
If the smoke alarm is defective in any way, do not tamper with the smoke alarm. The smoke alarm does not contain
any user-serviceable parts. As the smoke alarm does not contain any radioactive material, disposal with domestic
rubbish is permitted in Australia and New Zealand.
10 Warranty
Redbusbar Pty Ltd, warrants this product to be free from defects in materials and workmanship for a period of 5
(five) years from the date of installation. Refer to the Redbusbar terms of sale for full warranty conditions
http://www.redbusbar.com/Terms-and-Conditions.html
Redbusbar reserves the right to change specifications, modify designs and discontinue items without incurring
obligation and whilst every effort is made to ensure that descriptions, specifications and other information in this
document are correct, no warranty is given in respect thereof and the company shall not be liable for any error
therein. © Redbusbar 2018. Redbusbar acknowledges that the Activfire Certified logo is a trademark of CSIRO.
This manual suits for next models
1
Table of contents
Other Redbusbar Smoke Alarm manuals
Popular Smoke Alarm manuals by other brands

Universal Security Instruments
Universal Security Instruments UNIVERSAL SS-770-LR user manual

Honeywell
Honeywell 5800COMBO-CN Quick installation guide

VESDA
VESDA VLS-XXX Product guide

Sealey
Sealey SFAL01 quick start guide

Electronics Line
Electronics Line EL-2603NA installation guide

United Technologies
United Technologies EDWARDS SIGA-HFD Installation sheet