Settings Heating circuit menu 5
The following settings (5.4 – 5.6) can be used for parallel shift of the characteristic for certain time
periods – day, night or comfort temperature.
5.4 - Day correction = parallel shift of the curve
The day correction means a parallel shift of the heating curve during the daytime operating hours, since
depending on the outdoor temperature it is possible that the building may not be optimally heated with the set
characteristic. If the characteristic is not optimized, the following situation may occur:
in hot weather - the rooms are too cold
in cold weather - the rooms are too hot
In this case, one should gradually reduce the characteristic slope in steps of 0.2, each time raising the day
correction by 2-4 °C.
This procedure can be repeated several times as needed.
5.5 - Night correction = parallel shift of the curve
The night correction produces a parallel shift of the weather compensated heating curve during the nighttime
operating hours. If a negative value is set for the night correction, the reference ow temperature is lowered
accordingly during the nighttime operating hours. In this manner, primarily at night, but also during the day
when no-one is at home, energy can be saved
Example: A day correction of +5 °C and a night correction of -2 °C produces a reference ow temperature in
nighttime operation that is by 7 °C below that of daytime operation.
5.6 - Comfort temperature boost = parallel shift of the curve
The comfort temperature boost is added to the set day correction. In this manner it is possible to carry out
quick heating and/or a higher temperature in the living spaces at a certain time each day.
5.8 - Min. Flow
The minimum ow temperature is the lower limit of the heating curve.
5.9 - Max. Flow
If the temperature exceeds this value, the heating circuit is switched off until the temperature drops below again.
For safe operation, a safety thermostat shall be wired in series to a pump.
5.10. Heat Request
This function requests a burner after 1 minute if the ow temperature stays below the target ow temperature
minus the Reference/Actual value (see 5.12) for this time period. If the target ow temperature is reached, the
heat request is immediately switched off again.
Off: Heat request is deactivated
Switching: Switch exit V1 at heat request to 10 V
Modulating: The desired temperature controls the signal voltage at V1 (V1 = desired temperature/10).
CAN bus: The desired ow temperature is sent via CAN bus by the controller when heat request is received.
Conditions:
1. Controllers shall be mutually interconnected by a CAN connection cable (page 27).
2. Only one controller requests the heat source directly, either modulating or by switching contact. This contro-
ller has to be connected to the requested heat source by V1 or by V1 with additional relay (Section 5.10).
3. For all other controllers, CAN bus shall be selected in Section 5.10. If one or more controllers request a heat
source according to the conditions described above, this request is transmitted via CAN bus together with the
required ow set temperature. The controller connected to the heat source passes this requirement promptly
to the heat source. If more than one controller sends a heat request via CAN bus, the request with the highest
required ow set temperature has priority.
5.11. Energy Saving Mode
The Energy saving mode switches the heating on when T eco is undershot und heats up to Teco + hysteresis
when solar charge or solid fuel boiler is active.
5.13. Reference/Actual
Switch on hysteresis for additional heating
This setting determines the allowed undershoot of the heating circuit temperature below the ow temperature
calculated from the heating curve. If the HC ow temperature and the storage temperature drop below the
desired ow temperature by hysteresis, the additional heat source will start after a 1 minute delay.
5.14. Threshold
When Energy saving mode is active, this value is used instead of TH set. When the temperature drops below T
eco at thermostat sensor S1, the boiler relay is switched on that switches off at the value of Threshold + hysteresis.
Caution