Regulus PG 1000 User manual

www.regulus.eu
PG 1000
PG 1000
EN
Installation and Operation Manual
PG 1000 Backup Power Supply

│2
REGULUS - Zdroj PG 1000 - www.regulus.cz
CONTENTS
SAFETY INFORMATION ........................................................................................................................ 3
TAKING CARE OF YOUR BATTERY ..................................................................................................... 3
1 Essential information - use, features, description ........................................................................ 4
1.1 General description ............................................................................................................ 5
1.2 Front panel .......................................................................................................................... 6
1.3 Rear panel ........................................................................................................................... 6
2 Inallation ........................................................................................................................................ 7
2.1 Recommended wiring ........................................................................................................ 7
2.2 Turning PG 1000 on with no grid power ........................................................................... 13
2.3 Turning PG 1000 off ........................................................................................................... 13
3 Alarm indication ............................................................................................................................... 13
4 Troubleshooting ............................................................................................................................... 14
5 Technical data ................................................................................................................................... 15

3 │
REGULUS - Zdroj PG 1000 - www.regulus.cz
SAFETY INFORMATION
The appliance shall be installed by a trained person. The Manual is intended for an informed person. The
contents of this Manual may change over time.
THE APPLIANCE OPERATES WITH VOLTAGE DANGEROUS TO HUMAN LIFE. PLEASE STICK
TO SAFETY INSTRUCTIONS GIVEN IN THIS GUIDE, PREVENTING THUS RISK OF ELECTRIC
SHOCK.
IMPORTANT
Wrong wiring or handling may cause damage to the appliance itself or connected machines!
Prior to beginning with installation and start of the appliance, please read the Manual carefully and follow the instruction
meticulously!
These electrical appliances shall be grounded in compliance with the valid standards. The cross-sections of the power
supply cables and their current ratings shall conform to the nominal values on the label and to the specication of the
appliance as required by a respective rule valid for low-voltage electric appliances. Prior to installation of this electric
appliance please make sure all circuit breakers and fuses are o.
Batteries may only be handled by trained, informed and experienced persons sticking to all applicable safety measures.
Before touching the battery clamps, all safety and switch-o elements at the appliance itself, batteries and their outlets
shall be switched o!
Do not put any tools, instruments or other, esp. metal items on batteries!
Avoid touching the terminal block or battery clamps with bare hands or conductive items held in hands!
Do not push any objects into the appliance through the ventilation or other openings!
Use a damp cloth to clean the casing. Take care not to let moisture or water into the appliance through the ventilation
or other openings!
The appliance shall be installed in a suciently spacious and ventilated room enabling good access. It shall never be
exposed to weather!
PLEASE RESPECT THE FOLLOWING INSTRUCTIONS
The appliance may be installed by authorized sta only!
When switching o the electric appliance fed by PG 1000 do not forget to switch o the PG 1000 itself as well. Otherwise
the PG 1000’s inverter continues to supply electricity from its battery and does not switch o until the battery voltage
drops below the set min. value.
Do not leave the appliance turned o for more than 6 months unless its batteries had been fully charged (charging
shall continue for at least 2 hours after the oating voltage had been reached).
The appliance should be completely cleaned by a serviceperson at least twice a year. Cooling is hindered by dust
inside and the appliance might suer damage from overheating.
TAKING CARE OF YOUR BATTERY
The appliance is equipped with maintenance-free lead acid battery. The following rules shall be respected when using it:
Avoid any mechanical stress, especially by a hit.
Avoid any damage to the battery casing and do not attempt to open it. The acid inside is toxic, dangerous to skin and
eyes!
Do not short-circuit the battery cables, it is highly risky, causing damage to the battery!
In no case shall the battery be exposed to high temperatures or ames. There is a risk of explosion!
When the battery is to be replaced and a new one installed, its number, model, wiring manner and capacity set by the
manufacturer shall be maintained. Only an authorized serviceperson may do that.
In a room where the battery is placed the temperature shall be kept at 20 °C ± 5 °C. At temperatures above 20 °C the
battery lifetime deteriorates, at temperatures below 20 °C the battery capacity deteriorates.
SAFETY INSTRUCTIONS REGARDING THE BATTERY
A battery represents a serious threat to human health and the environment. It shall be disposed of in compliance
with a valid legislation. The appliance shall be stored in a dry, ventilated room, protected from moisture and eects of
chemicals.
When working with the appliance, refrain from smoking and using open ame!
Do not use water to extinguish eventual re, danger of explosion!
Gases develop in all lead acid batteries during charging. In traditional unsealed batteries these gases escape into the
air. In batteries with pressure valves most of these gases recombine inside the battery and just a very small portion
escapes into the air.
Hydrogen gas may explode and cause serious injuries and re.
Always ensure good ventilation for battery cabinets or rooms (at least 1 l of air per hour).

│4
REGULUS - Zdroj PG 1000 - www.regulus.cz
ACID BURN INJURY
CALL A DOCTOR OR AMBULANCE IMMEDIATELY
This battery is sealed, valve-controlled, with acid in a gel
form or soaked in microscopic-porous vitreous substance in a
sealed case.
If a battery case suers damage, the acid may leak out. In such
a case internal short circuit may occur or a person may get
splashed with sulphur acid!
Should the acid get in contact with skin, take o immediately
all contaminated clothing, and wash immediately with plenty
of water, use sterile gauze bandage and special medical aids.
In case of contact of acid with eyes, rinse immediately with
plenty of water and call emergency and ambulance. In all
emergency, life-threatening situations contact a doctor asap.
KEEP IN MIND THAT EVEN IF THE APPLIANCE IS TURNED OFF, THE BATTERY VOLTAGE IS STILL PRESENT IN
THE WIRING AND AT THE CLAMPS.
HOW TO ENSURE LONG LIFE FOR YOUR BATTERY:
Always store the battery fully charged. When it is not connected to an operational charger, always disconnect also the
battery poles. Even a small discharge current for a longer time will cause irreversible damage to the battery.
Never store a discharged battery. Always charge it prior to storing and disconnect all leads from the battery poles. The
battery may be stored for a longer time in this manner only. At the same time, it is recommended to charge it every
recommended 3 months. Older batteries shall be checked more frequently.
Battery poles shall never get connected to each other. That means a short circuit that can cause a
battery explosion with subsequent re.
1 ESSENTIAL INFORMATION - USE, FEATURES, DESCRIPTION
- PG 1000 line UPS is intended preferably for circulation pumps in heating systems.
- The PG 1000 load shall not exceed the value shown on the label placed on its rear panel.
- In order to avoid a risk of injury, use rechargeable lead acid batteries only, preferably models designed for UPS’s.
- The appliance is designed for indoor use. Do not expose it to rain, snow or any other moisture.
- Never wire and charge very cold batteries (exposed to freezing temperatures).
- In- and outgoing cables shall comply with the PG 1000 output.
- Be extremely careful when using metal items and tools near the battery. Short-circuiting might cause even a battery
explosion.
- The ON/OFF button does not disconnect electrically the internal circuitry. In order to de-energize the PG 1000, it is
necessary to disconnect the power supply at the respective terminals - by disconnecting the battery and pulling out the
power cord.
- Do not open the cover of PG 1000 when any of its internal circuits are energized; this may apply even if the power
supply at the input terminal is disconnected. In no case any repair on internal parts of PG 1000 may be performed by
a user.
- The front panel is designed for manual control; do not use sharp or pointed items..
- PG 1000 is not designed for outdoor operation, nor for operation in explosive environment.
- PG 1000 shall be placed in a suciently ventilated space. Ventilation openings shall not be covered and air intake shall
not be obstructed.
- When PG 1000 is in operation, its fan is running. Its switching is controlled (see Installation description, switching on
and o).
DANGER

5 │
REGULUS - Zdroj PG 1000 - www.regulus.cz
1.1 GENERAL DESCRIPTION
When PG 1000 is power-supplied from the grid, the electricity runs via its internal bypass directly to its outlet socket.
At the same time, the battery is being charged. In case of a power failure, the inverter turns on and the load is fed from
the battery.
A battery connects to PG 1000 using cables tted with cable lugs.
Max. battery capacity for UPS PG 1000 is 100 Ah.
During charging, the temperature of PG 1000 may rise to circa 45 °C (normal operation state).
WARNING! The battery shall be connected for standard operation, otherwise the appliance cannot be turned on.
WARNING! The battery shall be connected to the terminals marked with the same polarity (+ red / - blue or black). The
poles between a battery and PG 1000 must not get swapped, there is a risk of damage to PG 1000.
NOTE! MORE APPLIANCES MAY BE CONNECTED BUT ONLY WITH RESPECT TO THE POWER OUTPUT OF
THE PUMP AND PG 1000.
OF COURSE, WITH A HIGHER LOAD CONNECTED, THE BACKUP TIME GETS SHORTER.
The appliance connects to the power supply with a standard power cord with wall plug. The load is power supplied via
the 230 V socket.
WARNING! WHEN TESTING A PUMP BACKUP, NEVER UNPLUG THE PG 1000 FROM ELECTRICAL SOCKET.
DOING SO WOULD INTERRUPT THE PE LINE. DE-ENERGIZING SHALL BE DONE BY A CIRCUIT BREAKER OR
A FUSE. MAKE SURE THE PUMP IS CONNECTED IN TN-S SYSTEM, i.e. three-wire system (L, N and PE).
When running from the battery, BACKUP MODE is shown on the display. If the battery voltage falls to a low level, an
acoustic alarm sounds prior to disconnecting PG 1000, and a low battery symbol appears.
WARNING – Whenever handling a battery and PG 1000, the PG 1000 shall be turned o and disconnected from the
power supply.
FEATURES
Fast automatic line-to-battery switching
Selectable input voltage ranges
High ecient DC-to-AC conversion (12 V to 230 V)
Flexible placement - lying at or standing
Built-in enhanced charger
Intelligent 2-stage charger control for ecient charging and preventing overcharge
Overload protection
Auto-restart while AC recovery
Backlit LCD screen, sound signals
BATTERY CONNECTION
The battery terminal on PG 1000 is tted with M6 sized PLUS and MINUS contacts. A battery is to be wired using a pair
of cables with lugs at the PG 1000 end, and cable lugs or other terminals at the battery end (depends on the battery
model).
Since a battery features extra low tension (12 V), it is important that its connection to the PG 1000 is as good as possible.
This way contact resistance will be avoided that would compromise both the backup and battery charge time. For longer
leads, a larger cross section shall be selected for the cables in order to prevent higher voltage drops.
Important:
Check annually that the battery terminals are properly tightened.
COMMENTS ON UPS PG 1000 OPERATION
As new batteries are not cheap, eorts may emerge to save money by using old automotive batteries. However, these
batteries are worn o internally and won’t charge to their full capacity. Such batteries are unreliable and unsuitable for
any backup use.
PG 1000 is not designed for use with an automotive battery. Please note that an automotive battery design diers from
that of a stationary battery. A starter battery is designed for a high-current, frequent and very short discharge during
start-up while a stationary battery is designed to be used only from time to time during a power failure but it shall stand
a long lasting discharge with a relatively low current. That is why using an automotive battery is unadvisable and such a
battery, although featuring the same capacity, will not reach the same backup time as a stationary battery.
Should the UPS be disconnected from the mains for a longer time, it is unconditionally necessary to disconnect
also the battery from the UPS. Despite being switched o by the mains switch, UPS keeps drawing a tiny
current from the battery that might discharge it even below the critical level. Storing a discharged battery will
cause its denite destruction!

│6
REGULUS - Zdroj PG 1000 - www.regulus.cz
1.2 FRONT PANEL
If the power supply cord is connected, press ON button and the PG 500 will work either in 230 V mode or in a battery
mode, depending on whether the power supply is available. One more pressing the button will turn o the inverter control
but the battery charging is maintained (supposed the incoming 230 V power
is available).
Power line operation
The display shows (from the left): input voltage, output voltage, LINE MODE,
momentary load in %, battery level.
Battery operation
The display shows the input voltage as 000 and the text BACKUP MODE is
displayed.
Fault
The display shows “0” and FAULT.
Bar diagrams
1.3 REAR PANEL
1. Screw terminals for wiring a battery.
2. Integrated 230 V socket to accommodate a power cord. A fuse incorporated.
3. 230 V socket (out).
4. Input voltage range selector. (Output voltage will be the same as input voltage from the el. network.) Select “Narrow”
for most applications. “Wide” should be selected only when using appliances that can stand a wider voltage range.
WIRING A BATTERY
Battery cables with the right terminals (lugs) shall be connected to the battery, respecting the right polarity.
Avoid applying excess power when tightening bolts at the battery (the recommended torque is 5-7 Nm). The battery
might get destroyed when the contacts tear off the lead plate inside the battery. For an improved contact, applying
anti-oxidant compound may be useful.
Symbol
Load: 0-25 % 25-50 % 50-75 % 75-100 %
Battery level:: < 11 V 11 - 11.5 V 11.5 - 12.5 V > 12.5 V

7 │
REGULUS - Zdroj PG 1000 - www.regulus.cz
Connecting one battery Connecting batteries in parallel
Battery voltage shall be the same as in PG 1000.
In case of connecting more batteries in parallel, all the batteries shall be of the same nominal capacity, principally the
same model from the same manufacturer, and if possible also from the same production batch. All the batteries shall
have the same tension (equally charged). The length of connecting cables should be almost identical as well as the
ambient temperature. A sucient safe distance between batteries of at least 1.5 cm shall be respected.
The batteries should be disconnected, measured separately and charged if needed at least once a year. The batteries
may be discharging unevenly (due to internal inuences) which may aect the overall capacity of their connection.
2 INSTALLATION
1. Make sure the power grid voltage corresponds to the voltage PG 1000 is designed for.
2. Connect the battery respecting the preceding information in these Instructions (MIND THE POLARITY, + red / - blue
or black).
3. Plug the power supply cord into the respective socket at the rear side of PG 1000 and into a wall socket. WARNING
- from the moment on the battery is being charged. At the same time, the internal cooling fan also starts running.
4. Connect your pump or another load by plugging its cable into the socket of PG 1000. It is necessary to stick to a
TN-S system (three-wire system, i.e. live wire is black, neutral wire is pale blue and protective earth wire is yellow-
green). No contact of the UPS outlet socket shall get connected to any lead of mains or any other electric wiring.
The UPS is designed for a closed circuit. If the UPS outlet got connected with the mains, there would be a danger of
destroying the connected appliances, the UPS itself, and even causing harm to health and property. The only lead
that may be connected outside TN-S network is the protective yellow-green lead.
5. Press ON/OFF push button to turn PG 1000 on. A signal will sound and all the LEDs will ash once. The green LED
will stay lit, indicating that PG 1000 is running (standard mode, ready for backup).
6. Now you can turn on a pump or another load and test power grid operation without the inverter. The inverter will turn
on automatically at power supply failure.
2.1 RECOMMENDED WIRING
● it is recommended to use solely an installation contactor with a 230 VAC coil, 2x NO + 2x NC
● it must be ensured that the PE lead cannot be disconnected!
● unconditional separation of the circuit fed from PG 1000 from the mains shall be respected

│8
REGULUS - Zdroj PG 1000 - www.regulus.cz
IR12 CTC controller
Backup of circulation pump of a heat pump.
PG 1000 BACKUP POWER SUPPLY
MAINS
230 V, 50 Hz
CIRCUIT WITHOUT
BACKUP
IR 12 SMART
CONTROLLER
PUMP WITHOUT
BACKUP
DETAILED PIC. SHOWING TERMINAL BOARDS MARKING AND WIRING
PUMP WITH
BACKUP
CIRCUIT WITH
BACKUP
Do respect the separation between the circuits with and without backup.
Not only for the live wire but also for the neutral one!
BATTERY

9 │
REGULUS - Zdroj PG 1000 - www.regulus.cz
IR12 CTC controller + fireplace module
Backup of circulation pump of a fireplace.
PG 1000 BACKUP POWER SUPPLY
MAINS
230 V, 50 Hz
CIRCUIT WITHOUT
BACKUP
IR 12 SMART
CONTROLLER
PUMP WITHOUT
BACKUP
DETAILED PIC. SHOWING TERMINAL BOARDS MARKING AND WIRING
PUMP WITH
BACKUP
CIRCUIT WITH
BACKUP
Do respect the separation between the circuits with and without backup.
Not only for the live wire but also for the neutral one!
BATTERY

│10
REGULUS - Zdroj PG 1000 - www.regulus.cz
IR12 CTC controller + PWM module
Backup of a PWM-controlled solar pump.
PG 1000 BACKUP POWER SUPPLY
MAINS
230 V, 50 Hz
CIRCUIT WITHOUT
BACKUP
IR 12 SMART
CONTROLLER
PUMP WITHOUT
BACKUP
DETAILED PIC. SHOWING TERMINAL BOARDS MARKING AND WIRING
PUMP WITH
BACKUP
CIRCUIT WITH
BACKUP
Do respect the separation between the circuits with and without backup.
Not only for the live wire but also for the neutral one!
BATTERY

11 │
REGULUS - Zdroj PG 1000 - www.regulus.cz
Fireplace
Backup of a fireplace circulation pump with flue thermostat.
MAINS
230 V, 50 Hz PUMP WITH
BACKUP
FLUE
THERMOSTAT
BATTERY PG 1000 BACKUP POWER SUPPLY

│12
REGULUS - Zdroj PG 1000 - www.regulus.cz
PG 1000 BACKUP POWER SUPPLY
MAINS
230 V, 50 Hz
BATTERY
STDC, TRS etc. controller
Pump backup
STDC, TRS etc. controller
Backup of a PWM-controlled pump.
PG 1000 BACKUP POWER SUPPLYBATTERY
MAINS
230 V, 50 Hz
STDC, TRS etc.
controller
MAINS
230 V, 50 Hz
STDC, TRS etc.
controller
PUMP WITH BACKUP
PUMP WITH BACKUP

13 │
REGULUS - Zdroj PG 1000 - www.regulus.cz
2.2 TURNING PG 1000 ON WITH NO GRID POWER
Point 6. Press ON/OFF push button to turn PG 1000 on. The yellow LED indicates PG 1000 running but power
supplied from a battery only (the battery must be connected). As soon as grid power supply is restored, the green LED
will light up and PG 1000 will work normally, charging the battery.
2.3 TURNING PG 1000 OFF
PG 500 can be turned o by pressing and holding the ON/OFF push button until the green LED goes o. WARNING!
The battery is still being charged. Complete turn o shall be done by disconnecting the mains.
Warning
● For safety reasons, it is strongly recommended not to modify the cables supplied. Further it is necessary to
make sure the power supply to PG 1000 is safely earthed.
● A mains socket or circuit breaker shall be located close to the appliance and shall be easily accessible.
● Never disconnect the 230 V power supply to PG 1000 when it is running - the earth protection of both
PG 1000 and the load connected would be interrupted.
● Check that when all loads are connected, the total earth leakage current does not exceed 2.7 mA
(EN 62040-1-1).
● NOTE: When plugged to power supply, the internal cooling fan with timer starts up and keeps running
constantly for up to 3 days.
● After this time that is sucient to fully charge the battery, the fan goes o and the battery is kept under oat
charging.
● In case of a power supply breakdown, the fan turns on, cooling the inverter.
● When power supply is restored, the timer turns on and the cycle is repeated.
3. ALARM INDICATION
Visual indication
Power grid operation – LINE MODE shown on display
Battery operation – BACKUP MODE shown on display
Battery charging – always when less than 4 bars of battery level
are shown.
Overload – load icon flashes
Low battery – battery icon ashes.
Fault – FAULT shown on display
Audio indication
Low battery voltage - signal each 2 s
Overload - signal each 0.5 s
Defect - uninterrupted tone

│14
REGULUS - Zdroj PG 1000 - www.regulus.cz
4 TROUBLESHOOTING
Situation Items to check Solution
No LED is lit (outlet from PG
1000 energized) ● Weak battery
● ON push button not pressed ● Charge battery
● Replace battery
● Press and hold ON push button
No LED is lit (outlet from PG
1000 de-energized) ● Defect battery
● Battery not connected
● Input fuse
● Power source defect
● Check battery condition and connection
● Check the fuse
● Contact service a
Power supply is present but
PG 1000 works in the battery
mode
● Power cord is not plugged either into
PG 1000 or into an electrical socket.
● Electrical socket is defect
Plug the power cord into PG 1000 and into
a working electrical socket
● Input fuse (4 A) located under the
mains socket on PG 1000 Replace the fuse
PG 1000 has started up but
the battery level indicator
ashes
Lower voltage in the battery If power supply is available and OK, let the
battery charge for at least 8 hours
PG 1000 does not serve the
expected backup time
Battery capacity may be reduced:
● Too long storage time
● Overload
● Battery lifetime over
● Repeated frequent power failures
when battery does not get fully
charged again
● Let the battery charge for about 8 hours
● Disconnect excess load
● Replace the battery
Sound alarm (signal) sounds
every 0.5 sec. Overload Check what is connected to PG 1000 and
disconnect excess load
Sound alarm (signal) sounds
continuously
Fault Hand over to an authorized service
provider

15 │
REGULUS - Zdroj PG 1000 - www.regulus.cz
5. TECHNICAL SPECIFICATIONS
MODEL PG 1000
Power output W600 W
Input
Line 1
Nominal voltage 230 V, 50 Hz
Smaller input voltage range (marked
NARROW) 170 - 260 VAV, 50 Hz
Wider input voltage range (for less sensitive
load), (marked WIDE) 90 - 280 V 50 Hz
Output
Line 1
Nominal voltage 230 V 50 Hz
Voltage control (backup mode) +10% / -18%
Frekvency 50 Hz
Frequency control (backup mode) +/- 0,5 Hz
Waveform (backup mode) Modified sine-wave
Power factor cos φ 0,6
Charging
Max. charging current up to 13 A (+/- 1 A)
Float charge 13. V +/- 0.2 V
Overcharge protection 16 V +/- 0,3 V charger turns off, signalling fault
Transfer time 15 - 20 ms, 30 ms max.
Účinnost AC/AC >95%
DC/AC >80%
Visual
indication
Mains operation LINE MODE displayed
Battery operation BACKUP MODE displayed
Battery charging The respective battery level bar flashes
Overload Flashing icon
Low battery voltage Flashing icon
Defect FAULT displayed
Sound alarms
Low battery voltage Signal each 2 s
Overload Signal each 0.5 s
Defect Uninterrupted tone
Protection Deep discharge protection, overcharge
protection, overload protection
Mechanical
properties
Dimensions (D x W x H) mm 260 / 224 / 80
Weight (kg) 2.1
Ambient
conditions
Operating environment 0~40 °C, 0~90%rel. humidity (noncondensing)
Noise level < 45 dB
1 m long battery cables are included in the supply.

©2018 We reserve the right to errors, changes and improvements without prior notice..
REGULUS spol. s r.o.
E-mail: sales@regulus.eu
Web: www.regulus.eu
v1.5-12/2018
Table of contents
Other Regulus Power Supply manuals
Popular Power Supply manuals by other brands

Frequency Central
Frequency Central ROUTEMASTER Build Document

Siemens
Siemens SIMATIC ET200SP PS 6EP7133-6AB00-0BN0 24 V/5... manual

SUNSLICE
SUNSLICE GRAVITY 756 instruction manual

Allen-Bradley
Allen-Bradley 1771-P7 Series C installation instructions

AWA
AWA HP-23 Upgrade instructions

RevolutionAIR
RevolutionAIR Avanty instruction manual