REMKO SLE 45 User manual

Edition GB – N12
Operating and
installation instructions
Read the instructions prior to performing any task!
SLE 45, SLE 65, SLE 85
REMKO SLN series
Swimming pool dehumidifiers


Contents
Carefully read this Operating Manual prior to commissioning/ using the
units.
This operating manual is a translation of the German original.
These instructions are an integral part of the unit and must always be
kept in the vicinity of the installation location or on the
unit itself.
Subject to modifications; no liability accepted for errors or misprints!
Safety notes 4
Air dehumidification 5-7
Testing the water quality 8
Unit description 9
Set-up 10-13
Commissioning 14-15
Unit function 16
Wireless remote control 17-19
LED remote control 20
Care and maintenance 21
Troubleshooting 22
Fault and information messages 23
Diagram, cooling cycle 24
Electrical wiring diagram 25
Intended use 26
Customer service and guarantee 26
Environmental protection and recycling 26
Exploded view of the unit 28
Spare parts list 29
RS-485 interface 30-32
USB interface 33
Maintenance log 34
Technical data 35-37
3

Safety notes
The units have been subjected to
extensive material, functional and
quality inspections prior to delivery.
However, dangers can result
from the units if they are used
improperly or not as intended by
untrained personnel.
The following notes must be
observed in full:
■
The units may not be installed
or operated in explosive
environments
■
The units must not be installed
or operated in atmospheres
containing oil, sulphur or salt
■
The units must not be exposed
to direct jets of water
■
An unobstructed air inlet and
air outlet must be guaranteed
at all times
■
The air-inlet grill must always
be kept free of dirt and loose
objects
■
The units must not be covered
during operation
■
Never stick foreign objects into
the units
■
All electrical cables on the
outside of the units must be
protected against damage (e.g.
by animals etc.)
■
The units are only permitted
to be set up or installed in the
intended position (upright)
■
Unobstructed and frost-proof
condensate drainage must be
ensured at all times
■
The unit connections must
always be established
according to the applicable
installation regulations
CAUTION
The units must be set up and
installed in such a way that
they are easily accessible for
monitoring, repair and
maintenance work.
!
4
REMKO SLE series

It is evident that the corrosion
rate below 50 % relative humidity
(RH) is low, and below 40 % is
negligible.
The corrosion rate increases
significantly above 60% RH.
This threshold for damage as the
result of humidity also applies to
other materials, such as powdery
substances, packaging, wood and
electronic units.
Buildings may be dried in a variety
of ways:
1. By heating and air exchange:
The air in the room is heated
in order for moisture to be
removed and then this air is fed
outside. All of the energy that
is involved is lost together with
the moist air that is released.
2. By air dehumidification:
The moist air that is present
within an enclosed space is
continuously dehumidified
according to the condensation
principle.
The correlations occurring when
air is dehumidified are based on
physical laws.
These are depicted here in
graphical form in order to provide
you with a brief overview of the
principles of air dehumidification.
The use of
REMKO air dehumidifiers
– Even if windows and doors
are well insulated, water and
moisture are still capable of
penetrating thick concrete walls.
– The water required for setting
in the production of concrete,
mortar and plaster etc. may only
be diffused after 1-2 months.
– Even moisture trapped in the
masonry after high-water or
a flood is released very slowly.
– The same is also true of
moisture contained in stored
materials for example.
The moisture (water vapour)
released from parts of a building
or materials is absorbed by the
surrounding air. As a result, the
moisture content increases, which
ultimately gives rise to corrosion,
mould, rot, peeling of paint and
other unwanted damage.
By way of example, the diagram
shows the corrosion rate of metal
in different levels of humidity.
Air dehumidification
Relative humidity %
Corrosion rate
With regard to energy
consumption, air dehumidification
has one distinct advantage:
Energy expenditure is limited
exclusively to the air volumes
present. The mechanical heat that
is released by the dehumidification
process is fed back into the room.
Under normal use, the
air
dehumidifier
uses approximately
25 % of the energy that is
required for the
“heating and
ventilating” principle.
Relative air humidity
Our ambient air is a gaseous
mixture which always contains
a certain volume of water in the
form of water vapour. This volume
of water is specified in g per kg of
dry air (absolute moisture content).
1 m3of air weighs approx. 1.2 kg
at 20 °C
Depending on the temperature,
each kg of air is only capable of
absorbing a certain volume of
water vapour. Once this capacity
has been reached, the air is
referred to as “saturated” and has
a relative humidity (RH) of 100 %.
Relative humidity is understood
to mean the ratio between the
current quantity of water vapour in
the air and the maximum possible
quantity of water vapour at the
same temperature.
The ability of the air to absorb
water vapour increases as
the temperature rises. I.e. the
maximum possible (absolute)
water content becomes greater as
the temperature rises.
5

Water vapour
condensation
Because the capacity for the
maximum possible volume of
water vapour increases as the air
is heated, the volume of water
vapour contained remains constant
and so relative humidity falls.
In contrast, because the capacity
for the maximum possible volume
of water vapour decreases as the
air is cooled, the volume of water
vapour contained remains constant
and so relative humidity increases.
If the temperature continues to
fall, the capacity for the maximum
possible volume of water vapour
is reduced so much so that it is
ultimately equal to the volume of
water vapour contained in the air.
This temperature is referred to
as the dew point. If the air is
cooled to below the dew point,
the volume of water vapour in
the air will become greater than
the maximum possible volume of
water vapour.
At this point, the water vapour
begins to precipitate.
It then condenses to water.
Humidity is then removed from the
air.
Examples of condensation include
steamed-up window panes in
winter, or the moisture on the
outside of a cold drinks bottle.
As the relative humidity of the air
increases, so too does the dew
point, making it easier for the
temperature to fall below it.
Building materials and structures
are capable of absorbing
considerable volumes of water,
such as brick 90-190 l/m³, heavy
concrete 140-190 l/m³ and
limestone 180-270 l/m³.
The drying of moist materials such
as masonry is effected as follows:
■
The moisture
moves from the
inside of the
material to its
surface
■
Evaporation occurs on the
surface = transfer of water
vapour to the ambient air
Temp. Water vapour content in g/m3at humidity of
°C 40% 60% 80% 100%
-5 1.3 1.9 2.6 3.3
+10 3.8 5.6 7.5 9.4
+15 5.1 7.7 10.2 12.8
+20 6.9 10.4 13.8 17.3
+25 9.2 13.8 18.4 23.0
+30 12.9 18.2 24.3 30.3
■
The air containing water vapour
is constantly circulated through
the REMKO air dehumidifier.
The air is dehumidified and,
slightly heated, leaves the unit
in order to re-absorb water
vapour
■
In this way, the moisture
contained in the material is
reduced gradually
The material is dried!
The accumulated condensate is
collected in the unit and drained
off from there.
Verdampfer Kondensator
°C
30
25
20
15
% r.F.
100
90
80
70
60
50
40
30
20
10
+
+
-
Lufttemperatur
Luftfeuchte
Verlauf
Luftrichtung
Evaporator Condenser
Air temperature
Air humidity
Progression
Air direction
As it flows through or over the evaporator, the air stream is cooled
to dew point. The water vapour condenses, and is collected in
a condensate trap from where it is drained off.
Drying materials
6
REMKO SLE series

Condensation heat
The Energy transferred to the air
from the condenser consists of:
1. The amount of heat derived
beforehand in the evaporator.
2. The electrical drive energy.
3. The condensation heat released
by liquefying the water vapour.
Energy must be supplied when
liquid is converted into a gas.
This energy is designated as
evaporation heat.
It does not cause any increase in
temperature, but is required to
convert a liquid into a gas.
Conversely,
energy is released
when gas is liquefied, this is
designated as condensation heat.
The amount of energy from
evaporation heat and condensation
heat is the same.
For water, this is:
2250 kJ/kg (4.18 kJ = 1kcal)
From this it is evident that the
condensation of water vapour
causes a large quantity of energy
to be released.
If the moisture that it is to be
condensed is not introduced by
evaporation in the room itself,
but from outside, e.g. through
ventilation, the condensation heat
released contributes to the heating
of the room.
When dehumidifying, a heat
cycle is created, whereby heat is
consumed for evaporation and
released for condensation.
When dehumidifying fed air,
a larger contribution of heat is
created, which manifests itself as
a temperature increase.
Generally speaking, the time
required for the drying process
is not only dependent on
the output of the unit, but is
determined to a greater extent by
the speed at which the material
or building section loses its
moisture.
7

Testing the water quality
Water quality
The correct combination of chemicals in swimming pools in indoor areas is of major importance to the health of
the users and for systems in the vicinity of the swimming pool and its plant room.
Inadequately treated water leads to poor hygiene, whilst water that has been excessively treated gives off
chlorine into the air, which can irritate the eyes and lead to respiratory problems. At the same time, an incorrect
combination of chemicals in the water can lead within a very short time to the destruction of all systems -
including the dehumidifier and other systems that have been installed for air treatment.
The following tables contain the limit values for swimming pools in indoor areas in accordance with
EN/ISO 12944-2, corrosivity category C4.
These limit values must be observed, otherwise the guarantee is voided
When adding chemicals
The following guideline values apply to swimming pools when adding chemicals:
Chemical values ppm
Free chlorine content 1,0 - 2,0
Combined chlorine content max. 1/3 of the free chlorine content
pH value 7,2 - 7,6
Total alkalinity 80 - 150
Calcium hardness 250 - 450
Total dissolved solids < 2000
Sulphates < 360
With own production of chlorine
The following guideline values apply to swimming pools with own production of chlorine:
Chemical values ppm
Salt (NaCl) < 30000
Total dissolved solids < 5 500
pH value 7,2 - 7,6
Total alkalinity 80 - 150
Calcium hardness 250 - 450
Sulphates < 360
Langelier saturation index
To make sure the various water quality parameters remain within an acceptable range, the Langelier saturation
index should be applied.
8
REMKO SLE series

Unit description
Schematic depiction of the workings of the SLE 45-85 air dehumidifier
Moist room air
Warmed and
dehumidified air
The units may be used
to dehumidify areas such as:
■
Private swimming pools
■
Spa areas
■
Fitness centres
■
Storage rooms
■
Archives
■
Museums
The units have been designed for
universal and straightforward air
dehumidification.
Their compact dimensions allow
the units to be transported and
installed with ease in the adjacent
room.
The units operate in accordance
with the condensation principle
and are equipped with a
hermetically sealed refrigerant
system and low-noise and low-
maintenance fan(s).
The fully-automated electronic
controller, an integrated hygrostat
and connection ports for
condensate drainage provided by
the customer ensure continuous
fault-free operation.
The units are reliable, easy to use
and conform to the fundamental
health and safety requirements of
the appropriate EU stipulations.
The units are used in all locations
where dry air is a must and where
economic consequential damage
(such as that caused by mould)
must be prevented.
Operating sequence
The unit is switched on and off
using the integrated hygrostat.
The hygrostat is set to
60 % RH in the factory.
The respective unit function is
indicated by a multi-colour LED
display on the front of the unit.
The fan extracts the moist room
air via the lower part of the front
panel.
Heat is removed from the room air
on the cold evaporator. The air is
then cooled to below dew point.
The water vapour contained in
the room air is then deposited
as condensate or rime on the
evaporator fins.
On the condenser, the cold and
dehumidified air is warmed up
again and discharged back into the
room via the top part of the front
panel with a temperature increase
of around 5 K above the room
temperature.
The processed, dry air therefore
continuously mixes with the room
air.
Continuous circulation of the room
air through the unit gradually
reduces the relative humidity
(% RH) in the room to the desired
humidity level.
LED light function
If the unit was delivered with the
LED light function, the light can
be switched on and off using an
operating switch at the top right
corner of the panel. If designed as
an RGB-LED, a remote control is
also supplied.
LED light function
LED operating switch
9

Set-up
For optimum and safe use of the
units, the following notes must be
followed in full:
Access to the controller
The unit panel must first be
removed from the unit in order to
access the controller. To do this,
remove the bottom lock. Angle the
front panel downwards and then
lift up and off vertically.
The controller is located behind the
top cover of the internal housing
parts above the compressor.
Once the top two screws on the
inner housing parts are removed,
the top panel can be removed and
access is free.
Once work is completed, re-
install or lock the housing parts
accordingly.
■
The unit must be mounted or
set up upright to ensure that air
can be taken in and blown out
freely
■
Observe the illustrated minimum
gaps between the unit and
the ceiling and floor in the
installation room to ensure safe
operation
■
The unit must never be
mounted in the immediate
vicinity of heaters or other
sources of heat
■
The room being dehumidified
must be closed to the
neighbouring atmosphere
■
Avoid having opened windows
and doors etc., and avoid
frequent entry to or exit from
the room as much as possible
■
In order to achieve optimum
room air circulation using the
dehumidifier, the supply and
exhaust air openings must
remain clear
■
Secure the wall spacers provided
with the unit to the bottom
corners of the unit using
adhesive
341 341 341
437 437
450 450 450
Wall-mounted bracket for the units
SLE 45
SLE 65
SLE 85
■
Comply with all regulations
governing structural, electrical
and other building requirements
and conditions with regard to
the installation site
■
Mount the wall console
provided securely to the wall
using suitable fastening fixtures
(not included)
■
The unit must be mounted or
set up upright to ensure that the
condensate can drain freely
■
The unit’s alignment must be
adhered to exactly in order to
prevent warpage on the housing
and to ensure that the unit
panel can be put on without
hindrances
CAUTION
The units are set up in
areas with a high potential
for hazards. In addition to
the local regulations, the
VDE regulations relating to
safety zones, local potential
equalisation, equipment,
safety measures and protection
classes must be adhered to.
Mounting the units on the wall
min.
403
min.
730
700
325
335
Wall spacer
10
REMKO SLE series

Condensate water drain
The condensate water drain is
located on the unit's base.
The condensate drain is connected
to the discharge nozzle supplied.
A solid or flexible 3/4” discharge
connector can be installed on this.
■
The discharge hose must always
be laid at an incline of at least
2 % so that the water can flow
unhindered from the drip tray.
■
Alternatively, a condensate
pump can be fitted to the unit in
order to pump the condensate
water to a drainage point
located at a higher level.
■
If drainage is to be carried out
through the wall, the relevant
measures such as holes for
correct condensate drainage
must be taken before installing
the unit.
■
See the diagram at the side for
information on the location of
the drainage connection.
All measurements in mm
Location of the condensate drain
56
430
Putting the panel on
The unit is supplied from the
factory with a separate panel.
This must therefore be put on
properly before starting the unit.
Follow one of the following two
instructions depending on the unit
equipment.
Installing the SLE panel
without LED light function
To equip the unit with the panel,
follow these instructions.
1. Open the connection flap on
the bottom.
2. Guide the power cable through
the cable gland and then onwards
to the terminal block.
3. Then attach the cable for the
power supply. Connect the L1
phase accordingly to the first
grey terminal (L1) from the left.
Connect the zero phase N to the
first blue terminal (N) from the left
and connect the earth conductor
PE to the earth conductor terminal
(PE) (also see the electrical wiring
diagram).
4. Re-close and fasten the
connection flap.
5. Connect the unit to the power
supply.
6. Remove the control board cover.
7. Set the room humidity on the
control board (see commissioning).
8. Re-attach the control board
cover using the two screws.
9. Hang the SLE panel into the top
edge, use the top guide pins to
centre it and then let it rest gently.
10. Push the panel using the
bottom guide pins.
11. Tighten the two locks
clockwise so that the bottom of
the panel can no longer be lifted.
11

Installing the SLE panel with
LED light function
To equip the unit with a panel
for the LED light function, follow
these instructions.
1. Open the connection flap on
the bottom.
2. Connect the supplied cable
section (0.5 m) with plug contact.
Connect the brown cable to the
second grey terminal (L1) from the
left. Connect the blue cable to the
second blue terminal (N) from the
left.
3. Push the strain relief onto the
rail and push the two cable ties
through the eyes.
4. Guide the cable end with the
plug contact through the bottom
gap. Attach the cable with the
cable ties to the strain relief and
shorten the ends of the cable ties
accordingly.
5. Guide the power cable through
the cable gland and then onwards
to the terminal block.
6. Then attach the cable for the
power supply. Connect the L1
phase accordingly to the first
grey terminal (L1) from the left.
Connect the zero phase N to the
first blue terminal (N) from the left
and connect the earth conductor
PE to the earth conductor terminal
(PE) (also see the electrical wiring
diagram).
1. Opening the connection flap
2. Connecting the cable section
3.-6. Strain relief and power supply
12
REMKO SLE series

7. Re-close and fasten the
connection flap.
8. Connect the unit to the power
supply.
9. Remove the control board cover.
10. Set the room humidity on the
control board (see commissioning).
11. Re-attach the control board
cover using the two screws.
12. Disconnect the unit from the
power supply.
13. Hang the SLE panel with LED
function into the top edge, use
the top guide pins to centre it and
then let it rest gently.
14. Angle the panel slightly
downwards and connect the plug
contact on the terminal block to
the plug contact on the panel.
15. Stow the cable in the
connection box.
16. Push the panel using the
bottom guide pins.
17. Tighten the two locks
clockwise so that the bottom of
the panel can no longer be lifted.
7. Closing the connection flap
13.-17. Putting the unit panel on
Plug contacts Lock
8.-12. Control board
13

Before commissioning the unit or if
local requirements dictate, the air-
inlet grill and air-outlet grill must
be checked for contamination.
The units are operated using an
integrated hygrostat that is set to
60 % RH (default value for spas
and indoor swimming pools).
If the room humidity is below
60 % RH, the unit does not start.
If the relative humidity is
above 60 %, the unit starts
the dehumidification process
automatically.
If you would like to make changes
to the hygrostat settings, remove
the front panel and the control
board cover located in the upper
section in order to access the
control board.
Commissioning
NOTE
When the unit is switched on
or off using the main switch,
a signal is issued upon startup
and the operation LED display
illuminates blue as soon as
the unit is ready for operation.
Once all conditions have
been met, the dehumidifying
process begins.
Display and operator panel
The display is a four-digit seven
segment display. The first two
digits are used to display the
respective “code”, e.g. rHXX, for
setting the room humidity and the
last two digits correspond to the
value set.
In the standard view, no code is
shown on the display. It is only the
value of the humidity currently
measured that is displayed.
The operator panel with the
buttons “Up”, “Down” and
“OK” can be found on the right-
hand side of the front of the
control board. These can be used
to navigate around the menu
structure of the control board and
to couple the control board with
a wireless remote control.
NOTE
If the air humidity is lower
that the set value, the unit will
not start up, even if the mains
voltage is connected.
Control board, front
Control board
The units are equipped with an
electronic controller. This features
various interfaces and a display.
The following section describes
these features in detail.
Code Value
NOTE
Interrupting the operation of
the unit before the compressor
has run for 6 minutes will
activate a restart lock lasting
approx. 4 minutes.
EXT RH/T
These terminals allow you to
connect up an external electronic
humidity and temperature probe.
The temperature probe must be
an NTC probe with 10 kΩat 25
°C and a B25/85 of 3969 K. The
humidity probe must be designed
for a voltage supply of 12 V DC and
feature an analogue voltage output
of 0-10_V with max. 10 mA.
ALARM
The alarm contacts are two
potential-free contacts that are
open in an unswitched state.
The RUN contact is closed when the
compressor is in operation.
The FAIL contact is closed when
there is a malfunction in the unit.
12VDC
Relays can be controlled via the
HEAT contacts in order to switch
the external heating on and
off. They are active when the
°C option in the menu is set to
a value.
USB interface
The information on the USB
interface can be found further on
in this manual.
RS-485 interface
The information on the RS-485
interface can be found further on
in this manual.
14
REMKO SLE series

1. Level 2. Level 3. Level
°CXX
External heating
EFXX
External fan
SIXX
Service interval
tESt
Self-test
rHXX
“Value”
"Value confirmed"
“Value confirmed”
“Value confirmed”
OK
“Value confirmed”
“Test confirmed”
“Value”
“Value”
“Value”
OK
OK
OK
OK
OK OK
OK OK
Menu structure of the SLE air dehumidifier
Menu items
Code: RH
The code “RH” stands for the
relative air humidity that the unit
should reach. The value can be set
between 40 and 99 % RH. The
default value is 60.
Code: EF
The code “EF” stands for external
heating control with the aim of
reaching the specified air humidity
more quickly. The set value may
differ from the setpoint humidity
so that the external heating can
either operate permanently or
merely provide a support function.
The value can be set between
40 and 99 % RH. The default
value is set to “OF”.
Code: SI
The code “SI” stands for the
maintenance interval that the
operator or fitter requires. This
value is indicated in weeks and can
be set from 01 to 99. The default
value is “OF.”
Code: tE
The code “tE” stands for testing
and the value “St” for self-test.
To start the self-test, press “OK”
and to cancel it, hold the down
key down for 5 seconds.
Menu structure
To define the setpoints using the
integrated operator panel, hold
down the “OK” key for 5 seconds
so that the display switches from
the humidity currently measured to
the menu item rHXX.
If you would like to exit the menu,
do not press any keys on the
operator panel for 10 seconds.
NOTE
The corresponding terminals
for these options are located
on the control board of the
unit.
Code: °C
The code “°C” stands for external
heating control with the aim of
reaching a defined setpoint. The
value can be set to between 05
and 34. This value is set to “OF”
by default.
OK
5 seconds
15

Fan control
When the control board puts the
dehumidifier into operation, the
fan(s) switch on together with the
compressor.
Defrosting
The units feature an intelligent and
active defrosting function. If the
room temperature is below 20 °C,
the evaporator will start to ice up
after a short time.
If the evaporator probe registers
a temperature of less than 5 °C
on the evaporator surface,
the unit only continues to run
in dehumidification mode for
a further 30 minutes.
Once this time has expired, the
fans stop and the solenoid valve
for hot-gas defrosting opens.
When the evaporator probe
registers a temperature higher
than 5 ºC again, the solenoid
valve closes and the unit resumes
dehumidification.
Safety circuit
If the temperature exceeds 55 °C
on the condenser (e.g. due to a fan
failure or an overly high room
temperature (higher than 36 °C)),
the compressor stops automatically
to prevent an overload.
As soon as the temperature on the
condenser permits dehumidification
again, the unit starts up
automatically.
Unit function
Compressor control
The compressor has a 6 minute
restart delay. The delay period
must elapse before it is possible to
restart the compressor.
This safety function protects the
compressor against an overload
caused by overly high pressure
in the cooling cycle.
In order to prevent damage to the
condenser, the units are equipped
with a mechanism that prevents
the compressor being immediately
switched back on after it is
switched off via the mains power
supply.
The compressor does not switch
back on until after a waiting time
of approx. 30 seconds!
Operating LED
The multi-colour LED display is in
the background of the top grille
on the front panel. It indicates the
current operating state of the unit.
Legend of the operation LED colours
The LED illuminates “blue” and
stays that way when the unit is
connected to the mains power
supply (standby).
The LED illuminates “green”
and stays that way when the
compressor is in operation and
the unit is in dehumidifying or
defrosting mode.
The LED lights up “yellow” and
stays that way when the unit
is operating in wireless remote
control mode.
The LED lights up “red” when
a fault has occurred. Please refer
to the Troubleshooting chapter to
rectify the fault.
LED light function
If the unit was delivered with the
LED light function, the light can
be switched on and off using an
operating switch at the top right
corner of the panel. If designed as
an RGB-LED, a remote control is
also supplied.
LED light function
LED operating switch
16
REMKO SLE series

Wireless remote control
The wireless remote control
allows an SLE unit to be operated
and adjusted in a simple and
convenient manner. The current
humidity and temperature can be
viewed on the wireless remote
control and the setpoint humidity
can be adjusted.
The wireless remote control is
intended for use with the SLE 45-
65-85 dehumidifier models.
The wireless remote control has
a coverage distance of up to
50 metres from the installation
location of the unit.
Design of the wireless remote
control
The wireless remote control is
equipped with a large, clear display
and has operating buttons for the
different options Up, Down, Left,
Right and Enter.
The display values and the air
humidity scale have a value range
of 0 to 99 % RH.
The display values and the air
temperature scale have a value
range of 0 °C to 40 °C.
Information display
The information display shows the
setpoint values for the unit. Fault
messages together with the fault
symbols are also displayed here.
Power supply
The wireless remote control can
be powered using 2 AAA batteries
with 1.5 V each or can be powered
externally using the USB cable
provided. Enter
(Change menu item)
Right
(Increase value)
Up
Down
Left
(Decrease value)
Operating button control options
Humidity indicator and
scale Dehumidification External heating
External fan
Fault symbol Information display
Service Temperature
indicator and scale
Wireless symbol
Remote control lock Battery indicator
Overview of the display
Wireless remote control
17

3. If coupling was successful, the
unit sends a serial number to the
wireless remote control and the
wireless symbol is displayed.
4. The swimming pool
dehumidifier confirms the
connection by displaying the code
“Conn” for a period of 3 seconds.
This procedure can also be carried
out using several remote controls
so that an air dehumidifier can
be controller by several remote
controls.
Connecting the antenna
The antenna is located on the
control board inside the unit or
can be fitted there. This will be
pre-installed if the unit is delivered
together with the remote control.
Before fitting the antenna,
disconnect the unit from the
power supply. Then loosen the two
locks on the bottom of the unit by
turning them anticlockwise, tilt the
front cover of the unit and lift it
up. In the upper right area, remove
the two screws on the board cover
and remove the cover. Pull the
control board forwards, screw
the antenna into place and bend
it forwards. Once the antenna is
screwed in place and the board
has been returned to the previous
position, the unit can now be
provided with power in order to
couple it with the wireless remote
control. Then screw the housing
parts back into place.
Switching on and coupling the
remote control
The wireless remote control must
be coupled with the unit before it
can be used. To do so, carry out
the following steps.
1. Insert the batteries provided into
the battery compartment on the
rear of the wireless remote control.
2a. The remote control will search
for the unit for two minutes.
During this time, the remote
control display flashes every
2 seconds.
2b. During the search phase, hold
down the Up and Down keys on
the operator panel of the control
board at the same time for 5
seconds.
Coupling
Connecting the antenna
Location of the control board
Coupling failure
If the wireless remote control fails
to couple with the unit, the fault
symbol becomes visible, “Conn” is
shown permanently on the display
and the wireless symbol flashes.
The wireless remote control
needs to be reset before a new
coupling attempt can be made.
To do so, hold the Left key on the
wireless remote control down for
10 seconds.
18
REMKO SLE series

Maintenance message
Unlike the other fault messages,
the maintenance message can
be acknowledged or reset via the
wireless remote control. This is
due to the fact that it is a purely
informative message.
Proceed as follows to set up the
new maintenance interval.
1. Hold down the Right key for
5 seconds to open the fitter menu.
2. Use the Up and Down keys
to navigate to the maintenance
symbol.
3. Use the Right and Left keys to
change the 0 value to the required
maintenance interval.
4. Confirm the new maintenance
interval by pressing the Enter key.
Fault messages
The fault messages correspond
to the alarm messages which can
also be shown on the unit’s control
board display. To make the alarm
message recognizable, the fault
symbol is also displayed on the
wireless remote control.
Generally speaking, the fault
messages can only be reset on the
display panel of the control board.
The unit must be thoroughly
inspected and the fault reset
following rectification each and
every time.
No changes can be made to the
setpoints in the setup menus while
there is an active fault.
User setup menu
Hold down the Enter key for
3 seconds to open the user setup
menu.
In this menu it is possible to switch
between the wireless remote
control symbols using the Up
and Down keys provided the
corresponding option of “OF” has
been set to a value on the control
board itself. Please read pages 12
and 13 to set these values.
The Left and Right keys can be
used to set these parameter values.
The parameter is confirmed as
a new setpoint using the Enter
key. When this is confirmed, the
remote control switches back to
the symbol and exits the menu.
If you would like to exit the user
setup menu, do not press any
keys on the remote control for
10 seconds.
External heating
Dehumidification
User setup menu symbols
External heating
Dehumidification
External fan
Maintenance interval
Fitter setup menu symbols
Examples of fault messages
Sensor fault
Overly high
pressure level
detected
Maintenance message
NOTE
Do not simply reset the fault
messages without establishing
the cause first.
HP High priority
LP
SEnS
Abt
AbrH Low priority
Fault priority
General
The wireless remote control
displays the values for humidity
and temperature at all times.
The values only disappear when
a malfunction arises.
Depending on which function is
currently active, one or more of
the symbols appear in the centre
of the display.
Fault priority
In the event that several faults
occur at the same time, only the
fault with the highest priority is
displayed.
Fitter setup menu
Hold down the Right key for
5 seconds to open the fitter setup
menu. At this point it is possible
to access all four menu items. It is
also necessary to set the respective
“OF” option on the control board
to a specific value to enable access.
19

LED wireless remote control
The LED wireless remote control is
used to set the colour modes.
The LED wireless remote control is
intended for use with SLE 45-65-
85 dehumidifier models that are
equipped with the RGB LED light
function.
The LED wireless remote control
has a coverage distance of up to
50 metres from the installation
location of the unit.
Sleep mode
If the LED wireless remote
control is not used for more
than 30 seconds, it switches
to sleep mode in order to save
battery power. Pressing any key
deactivates sleep mode and the
LED wireless remote control can be
used for setting again.
ON/OFF
(delayed)
Speed
Brightness -
Speed
Brightness +
Touch colour
wheel
Change mode
LED wireless remote control (RGB)
Using the LED remote control to
change modes
You can use the “Change mode”
key to select from 11 different
programs.
1. Solid colour, red
2. Solid colour, green
3. Solid colour, blue
4. Solid colour, yellow
5. Solid colour, violet
6. Solid colour, turquoise
7. Solid colour, white
8. RGB alternating
(jumping)
9. Seven alternating colours
(jumping)
10. RGB alternating
(cross-fading)
11. All colour alternating
(cross-fading)
Changing the battery
The battery compartment is
located on the bottom of the
remote control. 1x CR2032
is inserted here. The battery
compartment must be closed
completely.
NOTE
Pay attention to the polarity
when inserting the battery.
CAUTION
If damage results in the LEDs
being directly visible, avoid
looking into the LEDs. The
high light intensity can cause
damage to the retina.
CAUTION
The fast light changes and light
intensity changes can affect
cognition, cause complaints
and trigger epileptic fits in
people prone to them.
20
REMKO SLE series
This manual suits for next models
3
Table of contents
Other REMKO Dehumidifier manuals

REMKO
REMKO ETF 220 User manual

REMKO
REMKO ETF-S Series User manual

REMKO
REMKO ASF 100 User manual

REMKO
REMKO ETF 240 User manual

REMKO
REMKO AMT Series User manual

REMKO
REMKO ETF 360 User manual

REMKO
REMKO ETF 360 User manual

REMKO
REMKO SLE Series User manual

REMKO
REMKO AMT 45-E User manual

REMKO
REMKO LTE 120 User manual

REMKO
REMKO LTE 50 User manual

REMKO
REMKO LTE 50 Eco User manual

REMKO
REMKO AMT 60-E User manual

REMKO
REMKO SLE 20 User manual

REMKO
REMKO SLN 40 User manual

REMKO
REMKO HITLINE TK Series User manual

REMKO
REMKO ETF 320 Eco User manual

REMKO
REMKO SLE 65 User manual

REMKO
REMKO ETF 320 User manual

REMKO
REMKO LTE Eco Series User manual