Renke RS-MG41-1 User manual

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
1
RS-MG41-1
Composite multi-gas
detector
User manual
Document version:V1.0

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
2
Table of Contents
1.Product introduction.........................................................................................................................3
1.1product description.................................................................................................................3
1.2Features.................................................................................................................................. 3
1.3Technical index...................................................................................................................... 5
2.product model...................................................................................................................................5
3.Equipment List................................................................................................................................. 6
4.Way of carrying................................................................................................................................6
5.Function and operation instructions.................................................................................................7
5.1Key Description..................................................................................................................... 7
5.2Main interface introduction....................................................................................................8
5.3Instructions.............................................................................................................................9
5.3.1System setup instructions............................................................................................9
5.3.2Channel setting instructions......................................................................................11
5.3.3Store data...................................................................................................................10
5.3.4Restore factory value................................................................................................ 13
6.Configuration software instructions...............................................................................................13
7.Gas calibration............................................................................................................................... 16
8.Charging function description........................................................................................................17
9.Precautions..................................................................................................................................... 17
10.Common faults and solutions.......................................................................................................18
11.Contact information..................................................................................................................... 19
Document history..............................................................................................................................19
Appendix Sensor Selection Table.....................................................................错误!未定义书签。

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
3
1.Product introduction
1.1product description
Potentially toxic or explosive gases may be used in the production process of many industries.
RS-MG41-1 is an intrinsically safe composite detector developed by our company for
environments containing explosive or toxic gases. The instrument uses a natural diffusion method
to detect the gas and an electrochemical combustion gas sensor. It has excellent sensitivity and
excellent repeatability. The product can detect four gases: oxygen, flammable gas, carbon
monoxide, and hydrogen sulfide. The product can store up to 130,000 pieces of test data, and the
historical data can be viewed at any time with the software.
The product is easy to use and maintain, and meets the requirements of industrial site safety
monitoring for high reliability of the equipment. The housing is made of high-strength engineering
plastics and composite non-slip rubber, which has high strength and good feel, and is waterproof,
dustproof and explosion-proof.
This detector is widely used in petroleum, chemical, environmental protection, metallurgy,
refining and chemical, gas transmission and distribution, biochemical medicine, agriculture and
other industries.
The design, manufacture and verification of this product comply with the following national
standards:
GB3836.1- -2010 "Explosive environment Part 1: General requirements for equipment"
GB3836.4--2010 "Explosive environment Part 4: Equipment protected by intrinsically safe" i ""
GB15322.3- -2003 "Portable combustible gas detectors Part 3: Portable combustible gas
detectors with a measuring range of (0-100)% LEL"
JJG693- -2011 "Verification Regulations for Combustible Gas Detection Alarm"
JJG 365--2008 Verification Regulations of Electrochemical Oxygen Analyzer
JJG695- 2003 Verification Regulations of Hydrogen Sulfide Gas Detector

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
4
JJG915- 2008 Verification Regulations for Carbon Monoxide Detection Alarm
1.2Features
1. The product uses electrochemical and catalytic combustion sensors with excellent sensitivity
and repeatability
2. The product shell has high strength and belongs to intrinsically safe explosion-proof products.
3. High-definition color screen design, easy to check the gas status
4.The product can detect four gases: oxygen, flammable gas, carbon monoxide and hydrogen
sulfide
5.Can set high and low limit alarm value
6. Full-featured self-test, product adopts sound-light vibration three-level alarm
7. Shortcut key to quickly turn on and off audible alarm and storage mode
8. Up to 130,000 stored data, with the software to view historical data at any time
9. Large-capacity battery, the device can be used continuously for at least 8 hours in the constant
light mode

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
5
1.3Technical index
Detection gas
Carbon monoxide
(CO)
Hydrogen
sulfide(H2S)
Combustible gas
(CH4)
oxygen(O2)
Detection
range
0-1000 ppm
0-100ppm
0-100% LEL
0.0-30.0%VOL
Test content
70/300/700 ppm
20/50/80ppm
10%/40%/60%
LEL
5.0%/15.0%/25.0%
VOL
Indication
error
Absolute error:±
5ppm
±5 ppm
±5%FS
±3%FS
Relative error:±
10%
Duplicate
value
≤2%
≤2%
≤2%
≤1%
Zero drift
±3ppm
±5ppm
±2%FS
±1%
Span drift
±5%
±5ppm
±3%FS
±1%
Alarm action
value
50/150ppm
10/35ppm
20/50%LEL
19.5/23.5%VOL
Response time
Diffuse≤60S
Insulation
resistance
≥20MΩ
Alarm function
Sound, light, vibration
working
environment:
Temperature -10 ℃-50 ℃; humidity <95% RH without condensation
Operating
Voltage:
DC3.7V (3000mAh lithium battery capacity)
Explosion-proo
f mark:
Ex ib IIB T3 Gb
Charging time:
6h-8h
Standby time:
More than 8h continuous
2.product model

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
6
RS-MG 4 1-1
□ Handheld housing
□Multi-gas combination form
□Gas detector can measure the number of gas
types □Composite multi-gas detector
□Company code
3.Equipment List
One suitcase (contains tester equipment, USB plug, USB data cable, standard gas hood,
certification, warranty card, factory inspection report)
4.Way of carrying
Open the device with the surface buckle, snap the device to the place where you need to carry
it, and then close the buckle
RS-MG41-1 conventional gas detection range
RS-MG41-1
conventional
gas detection
range
Range
Low alarm
point
High alarm
point
Resolution
EX
(0-100) %LEL
20%LEL
50%LEL
1%LEL
H2S
(0-100) ppm
10ppm
35ppm
1ppm
CO
(0-1000) ppm
50ppm
150ppm
1ppm
O2
(0-30) %vol
19.5%vol
23.5%vol
0.1%vol

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
7
5.Function and operation instructions
5.1Key Description
image
name
Explanation
Increase build
Main interface: long press to turn on the buzzer
alarm;
Menu bar interface: short press, the cursor moves
to the previous icon;
Input value interface: short press to increase
current value; long press to increase current value
quickly.
Decrease key
Main interface: long press to turn off the buzzer
alarm;
Menu bar interface: short press, the cursor moves
to the next icon;
Input value interface: short press to decrease
current value; long press to decrease current value
quickly.
Cycle key
Password and time setting interface: the cursor
moves to the next number;
Menu interface: short press, the cursor moves to
the next icon,
Main interface: Long press to quickly turn on or
off the function of storing data.

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
8
Any interface: Long press to return to the main
interface.
Enter
Power off state: long press 2S, the device enters
power on state;
Main interface status: long press 4S, the device is
turned off, short press to enter the password
interface
Menu, input value interface: After the cursor
confirms the option, short press to confirm the
current option.
5.2Main interface introduction
Serial
number
name
Description
1
Real-time value
Display the current actual gas concentration value
2
Gas name
Show gas name
3
time
Display the current time (manual adjustment)
4
Call the police
As shown in the figure, the total alarm sound, light, and vibration
are turned on (the buzzer alarm can be turned off separately). When
displayed, it indicates that the total alarm is turned off
5
USB socket
This symbol is displayed when the USB is inserted
6
shock
This symbol appears when the device is in a vibration
7
Alarm occurred
This symbol appears to indicate that the equipment inspection is in

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
9
an alarm state
8
Storage status
The display ■indicates that the device is in the state of stopping
data storage. When it displays ▶, the device is in the state of
storing data
9
buzzer
As shown in the figure, the buzzer is normally enabled and
displayed when the buzzer is disabled:
10
Battery
When the alarm is off, the buzzer cannot be enabled
11
Proportion
Display the current remaining battery level
5.3Instructions
1. In the shutdown state, press and hold the 2S confirmation key, the device detects whether the
buzzer, flash, and vibration are used normally, and the device enters the main interface
2. On the main page, press cyclically to enter the password interface. The default password is
0000. Press the cycle to move the cursor to confirm, and click the confirm button to enter the
menu interface. As shown in Figure 1:
figure 1
5.3.1System setup instructions
Move the cursor to the corresponding icon and click the confirmation key to enter the setting
interface

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
10
Time setup: With increase button and reduce button to change the time, the cycle button moves
the cursor to the next position. The cursor moves to the confirmation position at the end.Click the
OK button.
Tip setup: Move the cursor to the corresponding option and click the confirmation to select it.
Note: when the alarm is off. The sound can not be turn on. Turn off the alarm doesn’t affect the
low battery alarm function.
Standby screen: Select the corresponding time, click the OK button.
Password setup: With increase button and reduce button to confirm the present value, the cycle
button moves the cursor to the next position. The cursor moves to the confirmation position at the
end.Click the OK button. Click return button to cancel modify the password.
Storage setup: Start storage: start to save the data
Stop storage: stop to save the present data
Delete storage: delete all the storage data
Storage interval:setup the save interval
Manual
Setup
Channel setup
Device info
Storage
Restore factory
Time setup
Tip setup
Standby screen
Password setup
Storage setup

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
11
5.3.2Channel setting instructions
Alarm value: Via the increase button and reduce button to change the upper and lower limit.
Move the cursor to confirm button, click Confirm or Ok button. Alarm value setup finished.
O2: Measuring the concentration more or less than the limit value, the device will has alarm
signal.
Other gas:Measuring the concentration more than the L Alarm value, it will has Alarm I.
Measuring the concentration more than H Alarm value, it will has has Alarm II.
(Zero) standard concentration: Note:this operation must be operated in the clear air or N2. Enter
in the operation screen, please move the cursor to Confirm or OK button. Return to the main
screen, the gas reads 0(O2 reads 20.9).
(Mid)standard concentration: Note: Non-prefessional personnel are strictly prohibited to
operate. This operation must be operated in the clear air or N2.
(Hight)standard concentration: Note: Non-prefessional personnel are strictly prohibited to
operate. This operation must be operated in the clear air or N2.
Manual
Setup
Channel setup
Device info
Storage
Restore factory
Alarm value
(Zero) standard concentration
(Mid)standard concentration
(Hight)standard concentration
One type gas

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
12
5.3.3 Store data
Device View
Note: The storage settings need to be turned on in the system settings. The device cannot view the
specific historical data. You need to use the configuration soft armor to read the data. Can be
viewed in the device: gas type, current value, range, maximum value, minimum value, start
storage time, end Storage time and number of storages.

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
13
5.3.4 Restore factory value
6.Configuration software instructions
After the software installation is complete, it will be generated on the
desktop“ ”Icon, double-click to open the software.
6.1 Set detection parameters
Connect the device to the computer through the USB data cable, click “Read Device
Information”in the toolbar, and click “Write Device Information”after editing the device
parameters to write the parameters to the device.
It should be noted that after the modified parameters are checked, modify the parameters, and
then click Write Device Information, the parameter will be written to the device. This function is
to facilitate the modification of other parameters by mistake when modifying individual
parameters. Set。

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
14
Device name: Factory default, you can view it and cannot modify it.
Equipment type: Refers to the gas combination type of the detector.
Battery level: The remaining power of the detector.
Number of items stored: The number of records currently stored by the detector (total number of
records for four gases).
Equipment time: You can check the clock time indicated by the tester to determine whether you
need to adjust the time.
Allow button to stop reporting: If you select Allow, you can press and hold the decrease key to
quickly turn off the alarm sound when an alarm occurs on the detector. If you do not allow it, you
cannot turn off the alarm sound quickly.
Sound on: Set the alarm sound of the detector on or off.
Alarm on: Set the detector's sound, light and vibration alarms on or off.
Allow recording: Set the storage function of the detector on or off.
Recording interval: Set the recording interval time of the detector (default 5 seconds).
Upper limit of oxygen alarm, lower limit of oxygen alarm: Set the upper and lower oxygen alarm
values.
Upper limit of flammable gas alarm and upper limit of flammable gas alarm: Set the low and
high values of flammable gas alarm.
Upper limit of carbon monoxide alarm, upper limit of carbon monoxide alarm: set the low
and high alarm values of carbon monoxide.
Upper limit of hydrogen sulfide alarm, upper limit of hydrogen sulfide alarm: Set low and
high alarm values for hydrogen sulfide.

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
15
6.2 Import Data
Open the multi-gas detector configuration software, and then connect the recorder to the computer
via a USB cable. Click “Read Data”to import the data stored in the tester into the configuration
software.
Click on the data to view the stored historical data in time.
6.3 export data
Select the export format (TXT / XLS / PDF) on the toolbar to save the data to the specified path
(take PDF as an example), and it prompts that the export is successful.

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
16
6.4 Clear device data
Click "Device" in the toolbar, and click "Delete device storage data" in the drop-down menu to
clear the device data. After clearing, the software prompts "Delete cleared successfully".
7.Gas calibration
Due to the normal loss and aging of the sensor during use, the instrument needs to be
calibrated after a long period of use.
To calibrate the equipment, a special calibration hood is required for calibration, as shown in

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
17
the figure below.:
* Please contact the manufacturer for specific calibration methods
8.Charging function description
When the power is less than 10%, the device issues an alarm (acoustic and visual vibration)
every two minutes until the device is turned off.
When the device is off, connect the charger to the portable detector and the other end to the
AC220V AC power supply. When the detector is fully charged, the battery capacity will be full
and it can be used normally.
9.Precautions
1. Prevent the machine from falling from high places or receiving severe vibration
2. In high-concentration gas environment, the machine may not work properly
3. Please use the detector strictly in accordance with the instructions, otherwise it may cause
inaccurate test results or damage the product
4. This product cannot be used or stored in the environment containing corrosive gas
5. If the device has not been used for a long time, please warm up and aging for 10 minutes before
using it again.
6. To ensure the accuracy of the test, the machine should be calibrated regularly, and the test
period should not exceed one year.
7. In an explosive gas environment, do not remove or replace the battery pack, and do not charge
the battery pack.

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
18
10.Common faults and solutions
Failure phenomenon
Possible failure cause
Processing method
Can not boot
Voltage is too low
Please charge in time
Crash
Contact your dealer or
manufacturer for repairs
circuit failure
Contact your dealer or
manufacturer for repairs
No response from detection
gas
circuit failure
Contact your dealer or
manufacturer for repairs
Inaccurate display
Sensor expired
Contact your dealer or
manufacturer
Long uncalibrated
Replace the sensor
Time display error
Battery is completely drained
Please calibrate in time
Strong electromagnetic
interference
Replace the RTC battery and
reset the time
Zero calibration function is
not available
Excessive sensor drift
Reset time
Instrument normal detection
interface
Sensor drift
Calibrate or replace sensors in a
timely manner
Non-return to zero (except
oxygen)
Sensor failure
Performing a zero calibration

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
19
11.Contact information
Shandong Renke Measurement & Control Technology Co., Ltd.
Address: 2 / F, East Block, Building 8, Shun Tai Plaza, High-tech Zone, Jinan City, Shandong
Province
Postcode: 250101
Phone: 400-085-5807
Fax: (86) 0531-67805165
Website: www.rkckth.com
Cloud platform address: www.0531yun.cn
Document history
V1.0 document creation

RS-MG41-1 Composite Multi-Gas Detector User Manual V1.0
Shandong Renke Control Technology Co., Ltd. www.renkeer.com
20
Appendix Sensor Selection Table
Tested gas
Measuring
range
Selectable range
Resolution
Alarm point
Combustible EX
0-100%lel
0-100%vol(Infrared)
1%lel/1%vol
low:20high:50
O2
0-30%vol
0-30%vol
0.1%vol
low:19.5%high:
23.5%vol
H2S
0-100ppm
0-50/200/1000ppm
0.1ppm
low:10 high:20 ppm
Carbon monoxide
CO
0- 1000ppm
0-500/2000/5000ppm
1ppm
low:50 high:150 ppm
CO2
0-5000ppm
0-1%/5%/10%vol
(Infrared)
1ppm/0.1%vol
low:1000 high 2000
Nitric oxide NO
0-250ppm
0-500/1000ppm
1ppm
low:50 high:150 ppm
NO2
0-20ppm
0-50/1000ppm
0.1ppm
Low: 5 High: 10 ppm
SO2
0-20ppm
0-50/1000ppm
0.1/1ppm
Low: 5 High: 10 ppm
CL2
0-20ppm
0-100/1000ppm
0.1ppm
Low: 5 High: 10 ppm
Hydrogen H2
0-1000ppm
0-5000ppm
1ppm
Low: 50 High: 150 ppm
Ammonia
0-100ppm
0-50/500/1000ppm
0.1/1ppm
Low: 20 High: 50 ppm
Phosphine PH3
0-20ppm
0-20/1000ppm
0.1ppm
Low: 5 High: 10 ppm
Hydrogen
chloride HCI
0-20ppm
0-20/500/1000ppm
0.001/0.1ppm
Low: 5 High: 10 ppm
Chlorine dioxide
CLO2
0-50ppm
0-10/100ppm
0.1ppm
Low: 5 High: 10 ppm
HCN
0-50ppm
0-100ppm
0.1/0.01ppm
Low: 10 High: 20 ppm
Ethylene oxide
C2H4O
0-100ppm
0-100ppm
1/0.1ppm
Low: 20 High: 50 ppm
O3
0-10ppm
0-20/100ppm
0.1ppm
Low: 2 High: 5 ppm
Formaldehyde
CH2O
0-20ppm
0-50/100ppm
1/0.1ppm
Low: 5 High: 10 ppm
Hydrogen fluoride
HF
0-100ppm
0-1/10/50/100ppm
0.01/0.1ppm
Low: 2 High: 5 ppm
Xylene / toluene
0-20ppm
0-1/10/50/100ppm
0.01/0.1ppm
Low: 5 High: 10 ppm
Table of contents
Popular Security Sensor manuals by other brands

MSS Professional
MSS Professional SmokeCloak VALI Series Installation and operating instruction

Nice
Nice Flood-Control Instructions and warnings for installation and use

Synergys
Synergys LeakShooter LKS1000-V3 user manual

THORLABS
THORLABS PSDM2 operating manual

Autronica
Autronica AutroFlame X33AF Addendum

IKEA
IKEA TRÅDFRI E1745 manual