Resistron ROPEX RES-409 User manual

Gansäcker 21 Fax: +49/(0)7142/7776-19 Internet: www.ropex.de
D-74321-Bietigheim-Bissingen (Germany) Data subject to change
24.4.09
RESISTRON
RES-409
GB
Important features
• Microprocessor technology
• Complete control via CAN-Bus interface (CAN 2.0A according ISO 11898)
Remark: CANopen is not supported
• Automatic zero calibration (AUTOCAL)
• Automatic optimization (AUTOTUNE)
• Automatic configuration of the secondary voltage and current ranges
(AUTORANGE, as of February 2007)
• Automatic phase angle compensation (AUTOCOMP, as of February 2007)
• Automatic frequency adjustment
• Large current and voltage range
• 0…10VDC analog output for ACTUAL temperature
• Additional 24VDC control signals for START 0 (Set 0) and START 1 (Set 1)
(as of February 2007)
• Alarm function with fault diagnosis
• Heatsealing band alloy and temperature range selectable
• Booster connection as standard (as of February 2007)
Operating
instructions

Page 2 RES-409
Contents
1 Safety and warning notes . . . . . . . . . . . . . . 3
1.1 Use . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Heatsealing band . . . . . . . . . . . . . . . . 3
1.3 Impulse transformer . . . . . . . . . . . . . . 3
1.4 Current transformer PEX-W2/-W3 . . . . 3
1.5 Line filter . . . . . . . . . . . . . . . . . . . . . . . 4
1.6 Warranty provisions . . . . . . . . . . . . . . . 4
1.7 Standards / CE marking . . . . . . . . . . . 4
2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Principle of operation . . . . . . . . . . . . . . . . . 5
4 Description of the controller . . . . . . . . . . . 6
5 Accessories and modifications . . . . . . . . . 6
5.1 Accessories . . . . . . . . . . . . . . . . . . . . . 6
5.2 Modifications (MODs) . . . . . . . . . . . . . 7
6 Technical data . . . . . . . . . . . . . . . . . . . . . . . 8
7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 11
8 Montage und Installation . . . . . . . . . . . . . 11
8.1 Installation procedure . . . . . . . . . . . . 11
8.2 Installation steps . . . . . . . . . . . . . . . . 12
8.3 Power supply . . . . . . . . . . . . . . . . . . . 13
8.4 Line filter . . . . . . . . . . . . . . . . . . . . . . 14
8.5 Current transformer PEX-W3 . . . . . . 14
8.6 Wiring diagram (standard) . . . . . . . . . 15
8.7 Wiring diagram with booster
connection (MOD 26) . . . . . . . . . . . . 16
9 Startup and operation . . . . . . . . . . . . . . . . 17
9.1 View of the controller . . . . . . . . . . . . . 17
9.2 Controller configuration . . . . . . . . . . . 18
9.3 Heatsealing band . . . . . . . . . . . . . . . 23
9.4 Startup procedure . . . . . . . . . . . . . . . 23
10 Controller functions . . . . . . . . . . . . . . . . . 25
10.1 Indicators and controls . . . . . . . . . . . 25
10.2 CAN protocol . . . . . . . . . . . . . . . . . . . 26
10.3 Receiving CAN messages . . . . . . . . . 27
10.4 Sending CAN messages . . . . . . . . . . 33
10.5 Temperature meter (actual value output)
38
10.6 Hold mode . . . . . . . . . . . . . . . . . . . . . 39
10.7 Measuring impulse length
(as of February 2007) . . . . . . . . . . . . 40
10.8 Automatic phase compensation (AUTO-
COMP, as of February 2007) . . . . . . 40
10.9 Temperature monitoring /
"temperature OK" bit
(as of February 2007) . . . . . . . . . . . . 41
10.10 Temperature diagnosis
(as of February 2007) . . . . . . . . . . . . 42
10.11 Heatup timeout
(as of February 2007) . . . . . . . . . . . . 42
10.12 Diagnostic interface / visualization soft-
ware (as of February 2007) . . . . . . . . 43
10.13 Booster connection . . . . . . . . . . . . . . 43
10.14 Undervoltage detection
(as of February 2007) . . . . . . . . . . . . 44
10.15 System monitoring / fault output . . . . 44
10.16 Error messages . . . . . . . . . . . . . . . . . 45
10.17 Fault areas and causes . . . . . . . . . . . 50
11 Factory settings . . . . . . . . . . . . . . . . . . . . . 51
12 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 52
13 How to order . . . . . . . . . . . . . . . . . . . . . . . . 53
14 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Safety and warning notes
RES-409 Page 3
1 Safety and warning notes
This RESISTRON temperature controller is
manufactured according to DIN EN 61010-1. In the
course of its manufacture it passed through quality
assurance, whereby it was subjected to extensive
inspections and tests.
It left the factory in perfect condition.
The recommendations and warning notes contained in
these operating instructions must be complied with, in
order to guarantee safe operation.
The device can be operated within the limits indicated
in the "Technical Data" without impairing its operational
safety. Installation and maintenance may only be
performed by technically trained, skilled persons who
are familiar with the associated risks and warranty
provisions.
1.1 Use
RESISTRON temperature controllers may only be used
for heating and temperature control of heatsealing
bands which are expressly suitable for them, and
providing the regulations, notes and warnings
contained in these instructions are complied with.
In case of non-compliance or use contrary to
the intended purpose, there is a risk that
safety will be impaired or that the heatsealing band,
electrical wiring, transformer etc. will overheat.
Ensuring such compliance is the personal
responsibility of the user.
1.2 Heatsealing band
A basic prerequisite for reliable and safe operation of
the system is the use of suitable heatsealing bands.
The resistance of the heatsealing band which
is used must have a positive minimum
temperature coefficient in order to guarantee
trouble-free operation of the RESISTRON
temperature controller.
The temperature coefficient must be specified as
follows:
e.g. Alloy-20: TCR = 1100 ppm/K
NOREX: TCR = 3500 ppm/K
The RESISTRON temperature controller must be set
and coded according to the temperature coefficient of
the heatsealing band.
The use of incorrect alloys with a too low
temperature coefficient and incorrect coding
of the RESISTRON temperature controller lead to
uncontrolled heating and ultimately to burn-out of
the heatsealing band!
The heatsealing bands that were originally supplied
must be identified by detail specification, part number
or some other means that will assure that replacement
bands are identical.
1.3 Impulse transformer
A suitable impulse transformer is necessary to ensure
that the control loop functions perfectly. This
transformer must be designed according to VDE 0570/
EN 61558 (isolating transformer with reinforced
insulation) and have a one section bobbin. When the
impulse transformer is installed, suitable shock
protection must be provided in accordance with the
national installation regulations for electrical
equipment. In addition, water, cleaning solutions and
conductive fluids must be prevented from seeping into
the transformer.
Incorrect installation of the impulse
transformer impairs electrical safety.
1.4 Current transformer PEX-W2/-W3
The current transformer supplied with the RESISTRON
temperature controller is an integral part of the control
system.
Only the original ROPEX PEX-W2 or PEX-W3
current transformer may be used. Other
transformers may cause the equipment to
malfunction.
The current transformer may only be operated if it is
connected to the RESISTRON temperature controller
correctly (see section 9, "Startup and operation"). The
relevant safety instructions contained in section 8.3,
"Power supply", must be obeyed. External monitoring
modules can be used in order to additionally increase
!
!
TCR 10 4–
10 K 1–
!
!
!

Application
Page 4 RES-409
operating safety. They are not included in the scope of
supply of the standard control system and are
described in a separate document.
1.5 Line filter
The use of an original ROPEX line filter is mandatory in
order to comply with the standards and provisions
mentioned in section 1.7 "Standards / CE marking" on
page 4. This device must be installed and connected
according to the instructions contained in section 8.3,
"Power supply" as well as the separate documentation
enclosed with the line filter.
1.6 Warranty provisions
The statutory provisions for warranties apply for a
period of 12 months following the delivery date.
All devices are tested and calibrated in the factory.
Devices that have been damaged due to faulty
connections, dropping, electrical overloading, natural
wear, incorrect or negligent handling, chemical
influences or mechanical overloading as well as
devices that have been modified, relabeled or
otherwise altered by the customer, for example in an
attempt to repair them or install additional components,
are excluded from the warranty.
Warranty claims must be examined in the factory and
approved by ROPEX.
1.7 Standards / CE marking
The controller described here complies with the
following standards, provisions and directives:
Compliance with these standards and provisions is only
guaranteed if original accessories and/or peripheral
components approved by ROPEX are used. If not, then
the equipment is operated on the user's own
responsibility.
The CE marking on the controller confirms that the
device itself complies with the above-mentioned
standards.
It does not imply, however, that the overall system also
fulfils these standards.
It is the responsibility of the machine manufacturer and
of the user to verify the completely installed, wired and
operationally ready system in the machine with regard
to its conformity with the safety provisions and the EMC
directive (see also section 8.3, "Power supply"). If
peripheral components (e.g. the transformer or the line
filter) from other manufacturers are used, no functional
guarantee can be provided by ROPEX.
2 Application
This RESISTRON temperature controller is an integral
part of the "Series 400", the outstanding feature of
which is its microprocessor technology. All
RESISTRON temperature controllers are used to
control the temperature of heating elements
(heatsealing bands, beaded bands, cutting wires,
heatsealing blades, solder elements etc.), as required
in a variety of heatsealing processes.
The controller is most commonly used for impulse-
heatsealing PE films in:
• Vertical and horizontal f/f/s machines
• Pouch, filling and sealing machines
• Film wrapping machines
• Pouch-making machines
• Group packaging machines
•etc.
DIN EN 61010-1
(VDE 0411-1)
Safety provisions for electrical
measuring, control and laboratory
devices (low voltage directive).
Overvoltage category III, pollution
severity 2, safety class II.
DIN EN 60204-1 Electrical equipment of machines
(machinery directive)
EN 50081-1 EMC interference emissions
according to EN 55011, group 1,
class B
EN 50082-2 EMC interference immunity:
ESDs, RF radiation, bursts, surges.

Principle of operation
RES-409 Page 5
The use of RESISTRON temperature controllers
results in:
• Repeatable quality of the heatseals under any
conditions
• Increased machine capacity
• Extended life of the heatsealing bands and teflon
coatings
• Simple operation and control of the sealing process
3 Principle of operation
The resistance of the heatsealing band, which is
temperature-sensitive, is monitored 50x per second
(60x at 60Hz) by measuring the current and voltage.
The temperature calculated with the help of these
measurements is displayed and compared with the set
point.
The primary voltage of the impulse transformer is
adjusted by phase-angle control, if the measured
values deviate from the set point. The resulting change
in the current through the heatsealing band leads to a
change in the band temperature and thus also its
resistance. This change is measured and evaluated by
the RESISTRON temperature controller.
The control loop is closed: ACTUAL temperature = SET
temperature. Even minute thermal loads on the
heatsealing band are detected and can be corrected
quickly and precisely.
A highly high response thermo-electric control loop is
formed which is highly accurate because purely
electrical variables are measured at a high sampling
rate. A high secondary current can be controlled
because power is controlled on the primary side of the
transformer. This allows optimum adaptation to the
load and to the required dynamic range despite the
exceptionally compact dimensions of the controller.
PLEASE NOTE!
RESISTRON temperature controllers play a significant
role in enhancing the performance of modern
machines. However, the full benefit can only be
obtained from the advanced technology offered by this
control system if all the system components, in other
words the heatsealing band, the impulse transformer,
the wiring, the timing signals and the controller itself,
are carefully compatible and interrelated.
We will be pleased to
contribute our many
years of experience
towards optimizing your
heatsealing system.
R=f(T)
+
_
Set point
Start
Indicators
and
controls
or
bus interface
Actual value
LINE
RESISTRON controller
Heatsealing band R = f (T)
Current
transformer
Impulse transformer
UR
IR
prim.
U1
sec.
U2

Description of the controller
Page 6 RES-409
4 Description of the controller
The microprocessor technology endows the
RESISTRON temperature controller RES-409 with
previously unattainable capabilities:
• Very simple operation thanks to AUTOCAL, the
automatic zero calibration function.
• Good dynamic response of the control system
thanks to AUTOTUNE, which adapts automatically
to the controlled system.
• High precision thanks to further improved control
accuracy and linearization of the heatsealing band
characteristic.
• High flexibility: The AUTORANGE function (as of
February 2006) covers a secondary voltage range
from 0.4V to 120V and a current range from 30A to
500A.
• Automatic adjustment to the line frequency in the
range from 47Hz to 63Hz.
• Increased protection against dangerous conditions,
such as overheating of the heatsealing band.
The RESISTRON temperature controller RES-409 is
equipped with a CAN-Bus interface type CAN 2.0A
according ISO 11898 (Remark: CANopen is not
supported). This interface can be used to control all the
controller functions and interrogate controller
information.
The ACTUAL temperature of the heatsealing band is
supplied to the CAN-Bus interface and to an analog
0 to 10VDC output. The real heatsealing band
temperature can thus be displayed on an external
temperature meter (e.g. ATR-x).
The RES-409 features an integrated fault diagnosis
function, which tests both the external system
(heatsealing band, wiring etc.) and the internal
electronics and outputs a selective error message in
case of a fault.
To increase operational safety and interference
immunity, all CAN-Bus signals are electrically isolated
from the controller and the heating circuit.
Either coding switches on the temperature controller
itself or the CAN-Bus interface can be used to adapt to
different heatsealing band alloys (Alloy-20, NOREX
etc.) and set to the required temperature range
(0…300°C, 0…500°C etc.).
The compact design of the RESISTRON temperature
controller RES-409 and the plug-in connections make
this controller easy to install.
5 Accessories and modifications
A wide range of compatible accessories and peripheral
devices are available for the RESISTRON temperature
controller RES-409. They allow it to be optimally
adapted to your specific heatsealing application and to
your plant's design and operating philosophy.
5.1 Accessories
The products described below are only a few of the
wide range of accessories available for RESISTRON
temperature controllers ("Accessories" leaflet).
Analog temperature meter ATR-x
For front panel mounting or mounting on a top hat rail (DIN TS35 rail).
Analog indication of the ACTUAL temperature of the heatsealing band in °C. The
meter damping of the unit is optimized for the abrupt temperature changes that occur
in impulse mode.
Digital temperature meter DTR-x
For front panel mounting or mounting on a top hat rail (DIN TS35 rail).
Digital indication of the ACTUAL temperature of the heatsealing band in °C, with
HOLD function.

Accessories and modifications
RES-409 Page 7
5.2 Modifications (MODs)
Owing to its universal design, the RESISTRON
temperature controller RES-409 is suitable for a very
wide range of heatsealing applications.
Two modifications (MOD) are available for the
RESISTRON temperature controller RES-409 for
implementing special applications.
MOD 01
Amplifier for low secondary voltages
(UR= 0.25…16VAC). This modification is necessary,
for example, for very short or low-resistance
heatsealing bands.
MOD 26 (bis Januar 2007)
Additional terminal for connecting an external switching
amplifier (booster). This modification is necessary for
high primary currents (continuous current > 5A, pulsed
current > 25A).
This modification is supplied as standard
with all controllers manufactured as of
February 2007 (section 10.13 "Booster connec-
tion" on page 43)
Line filter LF-xx480
Essential in order to ensure CE conformity.
Optimized for the RESISTRON temperature controller.
Impulse transformer ITR-x
Designed according to VDE 0570/EN 61558 with a one section bobbin.
Optimized for impulse operation with RESISTRON temperature controllers.
Specified according to the heatsealing application
(ROPEX Application Report).
Communication interface CI-USB-1
Interface for connecting a RESISTRON temperature controller with diagnostic inter-
face (DIAG) to the PC (USB port). Associated PC visualization software for dis-
playing setting and configuration data, and for recording SET and ACTUAL tempe-
ratures in real time.
Booster B-xxx400
External switching amplifier, necessary for high primary currents (continuous
current > 5A, pulsed current > 25A).
Monitoring current transformer
For detecting frame short-circuits on the heatsealing band.
Used as an alternative to the standard PEX-W2/-W3 current transformer.
Measurement cable UML-1
twisted measurement cable for the UR-voltage measurement.
Trailing cable, halogene und silicone free.
!

Technical data
Page 8 RES-409
6 Technical data
Type of construction Housing for installation in the electrical cabinet
Snaps onto a standard top hat rail (DIN TS35 rail, 35 mm) acc. to DIN EN 50022
Dimensions: 90 x 75mm; height: 135mm (incl. terminals)
Line voltage All controllers manufactured as of February 2007:
115VAC version: 110VAC -15%…120VAC +10% (equivalent to 94…132VAC)
230VAC version: 220VAC -15%…240VAC +10% (equivalent to 187…264VAC)
400VAC version: 380VAC -15%…415VAC +10% (equivalent to 323…456VAC)
All controllers manufactured as of January 2004 up to January 2007:
115VAC version: 115VAC -15%…120VAC +10% (equivalent to 98…132VAC)
230VAC version: 230VAC -15%…240VAC +10% (equivalent to 196…264VAC)
400VAC version: 400VAC -15%…415VAC +10% (equivalent to 340…456VAC)
All controllers manufactured up to December 2003:
115VAC, 230VAC or 400VAC, tolerance: +10% / -15%
depending on version selected (section 13 "How to order" on page 53)
Line frequency 47…63Hz, automatic adjustment to frequencies in this range
CAN-Bus interface CAN Bus-interface type CAN 2.0A according ISO 11898
(CANopen is not supported)
2 x 3-pole M8 circular connector acc. to IEC 947-5-2
All controllers manufactured as of February 2007:
Baud rates: 20kBaud; 50kBaud; 100kBaud, 125kBaud; 205kBaud;
250kBaud; 500kBaud; 800kBaud; 1MBaud
All controllers manufactured up to January 2007:
Baud rates: 10kBaud; 50kBaud; 125kBaud; 205kBaud;
250kBaud; 500kBaud; 800kBaud; 1MBaud

Technical data
RES-409 Page 9
Heatsealing band
type and temperature
range
All controllers manufactured as of February 2007:
The temperature range and temperature coefficient settings can also be specified
in the ROPEX visualization software (section 10.12 "Diagnostic interface /
visualization software (as of February 2007)" on page 43) in addition to using the
rotary coding switch (see below) or the CAN interface:
Temperature range: 200°C, 300°C, 400°C or 500°C
Temperature coefficient: 400…4000ppm (variable setting range)
Five different ranges can be set with the rotary coding switch:
Temperature coefficient 1100ppm, 0…300°C (e.g. Alloy A20)
Temperature coefficient 780ppm, 0…300°C (e.g. Alloy L)
Temperature coefficient 1100ppm, 0…500°C (e.g. Alloy A20)
Temperature coefficient 780ppm, 0…500°C (e.g. Alloy L)
Temperature coefficient 3500ppm, 0…300°C (e.g. NOREX)
Various ranges can be selected via the CAN interface:
Temperature coefficient 1100ppm (e.g. Alloy A20)
0…200°C, 0…300°C, 0…400°C, 0…500°C
Temperature coefficient 780ppm (e.g. Alloy L)
0…200°C, 0…300°C, 0…400°C, 0…500°C
Temperature coefficient 3500ppm (e.g. NOREX)
0…200°C, 0…300°C, 0…400°C, 0…500°C
All controllers manufactured as of February 2007:
The settings with the rotary coding switch are considered to be the
factory setting. This corresponds to CAN message address 8, value 10 (dec)
(section 10.3 "Receiving CAN messages" on page 27).
All controllers manufactured up to January 2007:
Six different ranges can be set via the CAN interface:
Temperature coefficient 1100ppm, 0…200°C (e.g. Alloy A20)
Temperature coefficient 1100ppm, 0…300°C (e.g. Alloy A20)
Temperature coefficient 1100ppm, 0…400°C (e.g. Alloy A20)
Temperature coefficient 1100ppm, 0…500°C (e.g. Alloy A20)
Temperature coefficient 3500ppm, 0…200°C (e.g. NOREX)
Temperature coefficient 3500ppm, 0…300°C (e.g. NOREX)
Analog output
(actual value)
Terminals 17+18
0…10V DC, Imax = 5mA
Equivalent to 0…300°C or 0…500°C
Accuracy: ±1% add. 50mV
Digital logic levels
Terminals 5, 7
(As of February 2007)
LOW (0V): 0…2VDC, electrically isolated
HIGH (24VDC): 12…30VDC (max. current input 6mA)
Reverse polarity-protected
Alarm relay
Terminals 12, 13, 14
Umax = 50V (DC/AC), Imax = 0.2A, changeover contact, potential-free
Maximum load
(primary current of
impulse
transformer)
Imax = 5A (duty cycle = 100%)
Imax = 25A (duty cycle = 20%)
Power dissipation max. 20W
!

Technical data
Page 10 RES-409
Ambient
temperature
+5…+45°C
Degree of protection IP20
Installation If several controllers are installed on one top hat
rail (DIN TS35 rail), a clearance of at least 20mm
should be allowed between them.
The moving clip required for fastening must be
facing down for mounting on a horizontal top hat
rail.
End holders to mechanical fix the controller must be fitted at both ends for
mounting on a vertical top hat rail.
Weight Approx. 0.7kg (incl. connector plug-in parts)
Housing material Plastic, polycarbonate, UL-90-V0
Connecting cables
Type / cross-sections
Rigid or flexible; 0.2…2.5mm² (AWG 24…12)
Plug-in connectors
If ferrules are used, they must be crimped in accordance
with DIN 46228 and IEC/EN 60947-1.
This is essential for proper electrical contact in the terminals.
!

Dimensions
RES-409 Page 11
7 Dimensions
8 Montage und Installation
See also section 1 "Safety and warning notes" on
page 3.
Installation and startup may only be
performed by technically trained, skilled
persons who are familiar with the associated risks
and warranty provisions.
8.1 Installation procedure
Proceed as follows to install the RES-409 RESISTRON
temperature controller:
1. Switch off the line voltage and verify that all circuits
are deenergized.
2. The supply voltage specified on the nameplate of
the RESISTRON temperature controller must be
identical to the line voltage that is present in the
plant or machine. The line frequency is
automatically detected by the temperature controller
in the range from 47Hz to 63Hz.
3. Install the RESISTRON temperature controller on a
standard top hat rail (DIN TS35 rail according to
DIN EN 50022) in the electrical cabinet. If several
controllers are installed on one top hat rail, the
minimum clearance specified in section 6 "Technical
data" on page 8 must be allowed between them.
75.0 90.0
113.0
135.0
!

Montage und Installation
Page 12 RES-409
4. Wire the system in accordance with the instructions
in section 8.3 "Power supply" on page 13,
section 8.6 "Wiring diagram (standard)" on page 15
and the ROPEX Application Report. The information
provided in section 8.2 "Installation steps" on
page 12 must be additionally heeded.
5. Connect the RESISTRON temperature controller to
the CAN master using a cable according to
IEC 947-5-2.
Check the tightness of all system
connections, including the terminals for the
impulse transformer winding wires.
6. Make sure that the wiring conforms to all relevant
national and international installation regulations.
8.2 Installation steps
!
Line
Impulse
transformer
Current transformer
PEX-W2/-W3
U (prim.)
1
Heatsealing band R= f (T)
U (sec.)
2
A
F
Controller
Temperature
meter
ATR-x
Digital
potentiometer
PD-x
Avoid long
cables
Heatseal element
with coppered ends
Use heatseal bands with
suitable temperature coefficient
20mm clearance if several
controllers installed on
one top hat rail
Note
polarity
No additional
resistance
in secondary
circuit
Dimension
transformer correctly
- Secondary voltage
- Power
- Duty cycle
Configure
DIP switches
correctly
Sufficient wire
cross-section
No
push-on
connectors
Twisted
Current measuring
wires IR
R
Connect U measuring
wires directly to
heatsealing band ends
Line filter
LF-xx480
Note
direction
of rotation
Note
number
of turns
(up to Jan. 2007)

Montage und Installation
RES-409 Page 13
8.3 Power supply
ROPEX
temperature
controller
UR
IR
R
PRIM.
U1
Kb
Ka
SEC.
U2
LINE
I
>
I
>
GND/
Earth
N (L2)
L1 (L1)
LINE
FILTER
ON
OFF
K1
3
3
3
1
Short wires
2
2
Line
115VAC, 230VAC, 400VAC
50/60Hz
Circuit breaker
Double-pole, C characteristic
(ROPEX Application Report)
Short-circuit protection only.
RESISTRON temperature controller not protected.
!
Relay Ka
For "HEAT ON - OFF" function (all-pole) or
"EMERGENCY STOP".
Line filter
The filter type and size must be determined according to
the load, the transformer and the machine wiring
(ROPEX Application Report).
Do not run the filter supply wires (line side) parallel
to the filter output wires (load side).
!
RESISTRON temperature controller belonging to the
4xx Series.
Relay Kb
Load break (all-pole), e.g. in combination with the alarm
output of the temperature controller.
When using a series resistor RV-....-1 the relay Kb
shall be installed.
!
Impulse Transformer
Designed according to VDE 0570/EN 61558 (isolating
transformer with reinforced insulation). Connect core to
ground.
Use transformers with a one section bobbin. The
power, duty cycle and voltage values must be deter-
mined individually according to the application (ROPEX
Application Report and "Accessories" leaflet for impulse
transformers).
!
Wiring
The wire cross-sections depend on the application
(ROPEX Application Report).
Guide values:
Primary circuit: min. 1.5mm², max. 2.5mm²
Secondary circuit: min. 4.0mm², max. 25mm²
These wires must always be twisted (>20/m)
These wires must be twisted (>20/m) if several control
loops are laid together ("crosstalk").
Twisting (>20/m) is recommended to improve EMC.

Montage und Installation
Page 14 RES-409
8.4 Line filter
To comply with EMC directives – corresponding to
EN 50081-1 and EN 50082-2 – RESISTRON control
loops must be operated with line filters.
These filters damp the reaction of the phase-angle con-
trol on the line and protect the controller against line
disturbances.
The use of a suitable line filter is part of the
standards conformity and a prerequisite of
the CE mark.
ROPEX line filters are specially optimized for use in
RESISTRON control loops. Providing that they are
installed and wired correctly, they guarantee comp-
liance with the EMC limit values.
You can find the exact specification of the line filter in
the ROPEX Application Report calculated for your par-
ticular heatsealing application.
For more technical information: "Line filter" docu-
mentation.
It is permissible to supply several
RESISTRON control loops with a single line
filter, providing the total current does not exceed
the maximum current of the filter.
The wiring instructions contained in section 8.3 "Power
supply" on page 13 must be observed.
8.5 Current transformer PEX-W3
The PEX-W3 current transformer supplied with the
RESISTRON temperature controller is an integral part
of the control system. The current transformer may only
be operated if it is connected to the temperature con-
troller correctly (section 8.3 "Power supply" on
page 13).
!
!
LINE
PE
Large cross-section
wire to ground
Large cross-section
wire to ground
Large frame contact surface
Do not lay parallel Mounting plate (galvanized)
max. 1m
ROPEX
temperature
controller
Snap-on for DIN-rail 35 x 7,5mm or 35 x 15mm (DIN EN 50022)
terminal
block
terminal
wires
14
60
24 75 14
23 28
26
39
12

Montage und Installation
RES-409 Page 15
8.6 Wiring diagram (standard)
The START 0 and START 1 functions at ter-
minals 5 and 7 are only available on control-
lers manufactured as of February 2007.
14
13
12
4
4
1
1
3
3
L
L
H
H
6
5
7
GND
R
11
9
10
8
4
3
2
1
IR
UR
15
16
18
17
°C
ATR
_
+
U2
prim.
U1
ALARM OUTPUT
max. 50V / 0.2A
Ground
Must be grounded
externally to prevent
electrostatic charging!
Bus GND
Bus GND
CAN bus
Plug 1
3-pole
CAN bus
Plug 2
3-pole
Plug assignment
(RES-409)
CAN bus
START 0 (Set 0)
with 24 VDC signal
START 1 (Set 1)
with 24 VDC signal
ANALOG
OUTPUT
+0...10VDC
RES-409
(also with MOD 01)
CAN bus
Controller
electrically
isolated
Current
transformer
PEX-W2/-W3
Impulse
transformer
Heatsealing
band
LINE
Line filter LF-xx480
sec.
Twisted
0V
(Internnal ground)
No external
grounding allowed!
0V
()
Internnal ground
No external
grounding
allowed!
up to
production
date
January 2007
4
3 3 = blue
4 = black
1 = brown
1
!

Montage und Installation
Page 16 RES-409
8.7 Wiring diagram with booster
connection (MOD 26)
The START 0 and START 1 functions at ter-
minals 5 and 7 are only available on control-
lers manufactured as of February 2007.
RES-409
(also with MOD 01)
14
13
12
ALARM OUTPUT
max. 50V / 0.2A
Ground
Must be grounded
externally to prevent
electrostatic charging!
CAN bus
Controller
electrically
isolated
4
4
1
1
3
3
L
L
Bus GND
Bus GND
H
H
CAN bus
Plug 1
3-pole
CAN bus
Plug 2
3-pole
Plug assignment
(RES-409)
CAN bus
6
5
7
START 0 (Set 0)
with 24 VDC signal
START 1 (Set 1)
with 24 VDC signal
GND
R
Current
transformer
PEX-W2/-W3
Impulse
transformer
11
9
10
8
IR
UR
Heatsealing
band
18
17
°C
ATR
_
+
ANALOG
OUTPUT
+0...10VDC
4
3
2
1
15
16
LINE
Booster
NC
NC
24
IN OUT
13
Line filter LF-xx480
sec.
U2
prim.
U1
Twisted
0V
(Internnal ground)
No external
grounding allowed!
0V
()
Internnal ground
No external
grounding
allowed!
up to
production
date
January 2007
4
3 3 = blue
4 = black
1 = brown
1
!

Startup and operation
RES-409 Page 17
9 Startup and operation
9.1 View of the controller
Termin als
LEDs
Coding switch
Plug-in jumper Nameplate
CAN plug
Coding switch
for CAN parameters

Startup and operation
Page 18 RES-409
9.2 Controller configuration
The controller must be switched off in order
to configure the coding switches and plug-in
jumpers.
9.2.1 Configuration of the DIP switches
for secondary voltage and current
Automatic configuration (AUTORANGE)
(controllers manufactured as of February 2007)
The secondary voltage and current ranges are
automatically configured by the automatic calibration
function (AUTOCAL). The voltage is configured in the
range from 0.4VAC to 120VAC and the current in the
range from 30A to 500A. If the voltage and/or current
are outside the permissible range, a detailed error
message appears on the controller (see
section 10.16 "Error messages" on page 45).
Configuration with DIP switches
(controllers manufactured up to January 2007)
Set the DIP switches for matching the secondary
voltage U2and the secondary current I2to the correct
position for your application.
You can find the exact configuration of the
DIP switches in the ROPEX Application
Report calculated for your particular application.
If the secondary current I2is less than 30A, the
PEX-W2 or PEX-W3 current transformer must have
two turns (ROPEX Application Report).
!
!
3
2
14
5
ON
OFF
1...10V
6...60V
20...120V
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
30...100A
60...200A
120...400A
OFF
ON
ON
OFF
OFF
ON
DIP switch
DIP switch
12
U
2
I
2
345
3
2
145
4
3
ON
OFF
U (V)
2
1-10
SWITC
H
ON
Factory settings
2x

Startup and operation
RES-409 Page 19
9.2.2 Configuration of the rotary coding
switch for the temperature range
and alloy (as of January 2007)
This configuration is provided as standard
on all controllers manufactured as of
February 2007. On older controllers, the
configuration must be set via the CAN interface
(section 10.3 "Receiving CAN messages" on
page 27).
All controllers manufactured as of February
2007:
The settings with the rotary coding switch are
considered to be the factory setting. This
corresponds to CAN message address 8, value 10
(dec) (section 10.3 "Receiving CAN messages"
on page 27).
If the switch is set to "9" (as of February 2007), other
temperature ranges and alloys can be selected in the
ROPEX visualization software (see section 10.12
"Diagnostic interface / visualization software (as of Feb-
ruary 2007)" on page 43). CAN message address 8
must contain the value 10 (dec) for this purpose (see
section 10.3 "Receiving CAN messages" on page 27).
9.2.3 Configuration of the fault relay
If the jumper is not inserted, the fault relay is
permanently energized (fault contact
between terminals 13 and 14 closed). The other
controller functions (e.g. heatsealing band heating,
AUTOCAL etc.) are not affected.
If the "Fault output deenergized at fault/PC CONFIGU-
RATION" position is selected (as of February 2007),
the behavior of the fault output can be configured more
finely in the ROPEX visualization software (see
section 10.12 "Diagnostic interface / visualization soft-
ware (as of February 2007)" on page 43).
0
5
1
2
3
4
6
7
8
9
0
5
1
2
3
4
6
7
8
9
Switch
position
0
1
4
5
8
300°C
300°C
500°C
500°C
300°C
1100ppm/K
780ppm/K
1100ppm/K
780ppm/K
3500ppm/K
e.g. Alloy-20
e.g. Alloy L
e.g. Alloy-20
e.g. Alloy L
e.g. NOREX
Temp.
range
Tem p.
coefficient
Band
alloy
0 = Factory settings
SWITCH POS.
1
0
4
5
8
9
TEMP. RANGE
300°C
300°C
500°C
500°C
300°C
PC CONFIGURATION
ALLOY
780ppm/K
1100ppm/K
(L)
(A20)
1100ppm/K (A20)
780ppm/K
3500ppm/K
(L)
(NOREX)
9 PC-CONFIGURATION
!
!
0
5
1
2
3
4
6
7
8
9
Alarm relay de-
energized by alarm/
PC-CONFIGURATION.
Alarm relay energized
by alarm.
(factory setting)
CONFIGURATION
ALARM OUTPUT
DE-ENERGIZED / PC
AT ALARM
ENERGIZED
!

Startup and operation
Page 20 RES-409
9.2.4 Configuration of the CAN interface
The CAN interface of the RES-409 is configured with
DIP switches. The baud rate and some of the identifiers
can be set. It is also possible to activate a terminating
resistance.
The CAN BUS-interface of the RES-409
supports CAN 2.0A according ISO 11898.
CANopen is not supported.
All controllers manufactured as of February 2007:
All controllers manufactured up to January 2007:
!
Controller housing
Factory settings
3
3
2
2
1
1
4
4
5
678ON
ON
OFF
OFF
TERMINATION IDENTIFIER
SEE
MANUAL
BAUDRATE
SEE
MANUAL
ON ON ON
12345678 1234
OFF
3
8
2
9
1
10
4
7
5
6
671ON
OFF
1
10
2
9
3
8
4
7
5
6
678
ON
OFF
IDENTIFIER
ID. 10
to
ID. 6
BAUD RATE
Controller housing
Factory settings
1
TERMINATION
8
Table of contents
Other Resistron Controllers manuals
Popular Controllers manuals by other brands

Radcal Corporation
Radcal Corporation 9010 manual

Texas Instruments
Texas Instruments Sitara AM335x quick start guide

Embertec
Embertec Emberpulse Complete user's manual

Toshiba
Toshiba nv Series Operating instructions (functional manual)

Seada
Seada SolarWall Pro Series quick start guide

Panasonic
Panasonic FP7 Series user manual

inVENTer
inVENTer sMove Quick operation guide

Curtis
Curtis PMC 1204 Series manual

Viconics
Viconics VT76 Series Integration manual

Johnson Controls
Johnson Controls FX-PCV18 Series installation instructions

Swagelok
Swagelok RDH10 Series user manual

Johnson Controls
Johnson Controls TEC3010 installation instructions