If the test pressure has been reached, but
“--” appears, the fan is running too slowly to
accurately measure flow.
- Switch to a lower Range Plug
- Change [Range] to match
- Re-adjust fan speed
Cannot achieve test pressure at full speed?
If fan reaches 100% speed before reaching
test pressure:
- Change to a higher Range Plug and try again.
- Change [Range] on the gauge to match.
- Check seals on all registers. Look for
disconnected ducts or ducts open to outdoors
Flow in [Channel B] reads “--” at test pressure?
Desired results not achieved?
Flow: CFM (m3/h) - Flow at the induced
pressure is the simplest result
Flow/Area: CFM/100 sq ft (m3/(h*m2) or
m3/(s*m2) or liters/(s*m2)) - Flow in CFM
per 100 square feet (or m3/(h·m2) may be
required. Requires an area to be entered.
When a Result is chosen that requires an area,
[Area] will be shown on the Home screen. Tap
it to enter the area.
The area can also be changed from the
[Settings] menu.
Get the results you need
Tap on the gauge and select the range
to match your fan, whenever a Range
Plug is changed.
Tap the [Channel B] key to select a different
Result, or tap the [Result to be displayed] key
on the [Settings] menu.
18 29 47 74
Use smaller Range number for tighter ducts,
and larger number for leakier ducts.
Additional troubleshooting
Visit www.retrotec.com/support for more
support options such as FAQ, Webinars,
Manuals, Tech Support, and Repairs.
Check gauge operation and check for blocked,
leaking or pinched tubes weekly, and anytime
results are in question. This will eliminate a
common source of error
To perform the gauge check, you will need the
gauge and Umbilical
Set [Time Average] to 5 seconds in [Settings].
Tap [Channel B] and select“Pressure: Pa”.
Connect the yellow tube between the red and
yellow ports.
If readings on Channel A and Channel B are
within 2% and don’t drop rapidly, the tube is
not blocked or leaking and the gauge is correct.
Repeat between different ports with each of the
tubes you use for testing.
Field check gauge weekly