1.0 Genera Information
2.0 Fixing
LST radiators are for use on indirect systems only. The system
should be designed to follow the recommendations of BS5449
or BS6880, as appropriate, with particular care taken to avoid
air entry or water discharge through an open vent. The
installation work must be done in accordance with recognised
good practice and precautions taken to avoid contamination,
which could lead to corrosion. If a corrosion inhibitor or other
water treatment is to be used, the manufacturer’s instructions
must be strictly followed.
lA pair of templates are supplied with the product to ensure the correct positioning of the wall brackets for the emitter
and the enclosure (see fig. 1).
Emitter Height - B (mm
Enclosure Height - A (mm
LST SUPER
SIDE ELEVATION
LST SUPER EXTRA
SIDE ELEVATION
LOOKING TOWARDS WALL LST SUPER PLUS
SIDE ELEVATION
572 672 872 972
300 400 600 700
Fig. 1 (All measurements are in mm)
IMPORTANT: It is advisable to leave a further 5mm
clearance above any final floor covering to allow for
easy fitting and removal.
3.0 Water Connections
lIf surface mounting pipework is being used, this must be
routed and mounted to run within the rectangular cut-outs
provided at each end of the enclosure. To remove the
cut-out, flex from side to side until the connection is broken.
If pipework enters one side only, the other cut-out should be
left intact.
lCarry out the plumbing connections in the usual way. Fig 1
shows the clearances between the heat emitter and the
enclosure. Ensure that pipework and valves are within these
limits to enable correct fitting of the enclosure.
LST radiators may be fitted with the following types of thermo-
static radiator valves:
4.0 Thermostatic Radiator Va ves
Valve Type Order Code
Connection Options
Close coupled TRV kit CCKTC 333
Remote Adjusting TRV 2TRVADJHEAD2 333
Remote Sensing TRV 2TRVRSHEAD2 3
Direct Fit TRV Kit DIRECTFIT 33
lRemove both security screws.
lLift the LST enclosure out of the wall bracket slots and pull
forward.
lTo reposition the enclosure, lift the enclosure onto the
brackets ensuring correct engagement with the bracket slots.
Replace the security screws.
lIf the unit is fitted with a Close Coupled or Remote TRV kit
then excessive movement of the casing will be restricted by
a safety chain.
5.0 C eaning and Maintenance - LST Enc osure
TBSE TBOE BOE
IMPORTANT: For the correct installation of radiators it is essential that the fixing of the radiator is carried out in such a way
that it is suitable for intended use AND predictable misuse. A number of elements need to be taken into consideration
including the fixing method used to secure the radiator to the wall, the type and condition of the wall itself, and any additional
potential forces or weights that may happen to be applied to the radiator, prior to finalising installation.
LST
*60mm for the 420mm wide version.
Not available for the 420mm wide model.
Order code CCKTC420 = 420 wide model and only available as BOE.