RIB WVSUS-EN3 User manual

WVSUS-EN3
This guide covers Resonate Vacancy/Occupancy sensor model WVSUS-EN3.
The package includes the sensor, installation guide, lens mask sticker and
two wire adaptor straps for soft ceiling tile mounting. The cover is
removable. Please note: the cover must be fully seated for proper operation.
The WVSUS-EN3 (also referred to as the sensor in this guide) is a
wireless, energy harvesting sensor that monitors room occupancy state using
a passive infrared motion (PIR) detector. The WVSUS-EN3 sensors are
intended for indoor use only, mounted on a ceiling at 8-10 feet from the floor.
Installation Guide
393265
The WVSUS-EN3 is compatible with any EnOcean enabled RIB® Relay. This
means any relay with a part number that fits the "RIBWxxx-EN3" format.
B2354

2
The WVSUS-EN3 sensor is powered by solar energy from natural or artificial
light sources. The solar energy is transformed into electrical energy which
is then used as a power source for the sensor. Powered by two solar cells,
the sensor will begin operation without a battery within 2 minutes of being in
sufficient light. The sensor will operate with 6 foot candles (65 lux) light
energy. The WVSUS-EN3 also has instantaneous operation (battery
powered).
The motion sensor supports the Occupancy Sensor EnOcean profile A5-07-01.
The sensor will transmit occupancy or vacancy depending on the occupancy
state of the room. The sensor will broadcast occupancy immediately upon a
state change from vacant to occupied. The sensor broadcasts a telegram when
movement is detected and repeats occupied telegrams with a minimum 100
second period between subsequent transmissions.
After detecting motion, the sensor is shut-down to conserve energy for 100
seconds. When the sensor awakens and further motion is detected, the sensor
will transmit an occupied telegram. If no motion is detected within 100
seconds, the sensor transmits a vacancy telegram, 200 seconds total since the
previous transmission. The sensor will remain active until the next occupancy
state is triggered by motion detection. If the sensor does not detect motion, it
resends the vacancy telegram every 1000 seconds.
The sensors use a PIR sensor element that detects motion by measuring the
infrared energy emitted by objects. The sensors are calibrated to detect the
temperature range of the human body. The sensor has a lens that breaks the
viewing angle of the sensor into zones (movement zones), infrared energy moving
in and out of a zone is how the occupied state is defined. The amount of
movement that triggers the sensor is dependent upon the density of the zones
where the motion takes place. A
Lens B: use for large moon detecon or larger rooms.
8/2.4m
30/9.1m 20/6m 10/3m 010/3m 20/6m 30/9.1m
10/3m
0
8/2.4m
15/4.5m
10/3m 5/1.5m 05/1.5m 10/3m
15/4.5m
10/3m
0
8/2.4m
15/4.5m 10/3m 5/1.5m 05/1.5m 10/3m 15/4.5m
10/3m
0
Lens A: use for small moon detecon or small rooms.

3
higher density of zones means smaller moon will trigger the sensor.
For detecon of small moon (typing, drinking from a coee cup), use the A
lens which has more movement zones. Place the sensor close to the locaon
where the moon may occur.
The sensor comes with a scker that can be applied to the lens to mask o areas
where moon detecon is not desired.
An LED under the lens will blink once every 100 seconds when the sensor is
detecng moon. Addionally, the LED color indicates the status of the baery
when applicable, see the following table.
Red No baery or weak
Amber 50% discharged
Green Full charge
t
The mounting location of the sensor is important as this will directly affect the
RIBWxxx-EN3's reception of the telegrams. Before installing, refer to the
sections in the guide detailing the installation of wireless devices, layout
tips and test operation modes.
NOTE: The sensor cannot detect occupancy through solid objects including items placed
by a tenant, such as le cabinets or shelves.
NOTE: Do not locate the sensor near forced air vents as hot moving air may cause
the sensor to false trigger. Leave at least 4’ (1.2 m) minimum between air vents and
the sensor.
NOTE: Incandescent lights may cause false trips when turning on.
1. Select a location to mount the sensor on the ceiling by identifying the
movement patterns that will be the most common in the space.
•For smaller office spaces where hand motion on a desktop is common,
locate the sensor off to one end of the desk, in line with the desk edge or
slightly behind so the PIR lens has direct line-of-sight to the keyboard
desktop area. Insure that the PIR lens does not have direct line-of-sight
out a doorway where walk-by traffic could trigger the sensor. Use the
included lens mask stickers to mask off these areas.
•Larger offices where larger body motion is more common, placement of
the sensor is less critical.
2. For the best sensor performance, mount the WVSUS-EN3 sensor so at least
one of the solar cells is facing a light fixture. The sensor will operate in low
light levels however, for best performance; a minimum of 6 foot candles
must be maintained. If the controlled lights in the space are dimmable
either manually or via daylight harvesting, insure the light level at the
lowest dimmed level meets this 6 FC requirement. If the light value does
not meet this requirement, install a battery.

3. Remove the cover by inserting a small screwdriver under the white
enclosures lip. Gently twist the screw driver and pull the cover away from
the base.
4. Choose a mounting method. The WVSUS-EN3 sensor can be mounted:
•With the integrated magnets to a steel T-bar ceiling frame or other
metallic surface by placing the sensor on to the metal rail.
•With screws and anchors (not provided) to a wall-board ceiling.
i. Use a pencil to mark the mounting base keyhole locations and
remove the sensor.
ii. Using a drill, bore the two holes and insert the anchors.
iii. Install the screws, leaving them loose while you place the sensor.
iv. Tighten the screws.
•With the provided wire adapter straps to a soft ceiling tile.
i. Mark the sensor mounting location on the
ceiling tile with a pencil. Remove the ceiling tile
from the T-bar frame.
ii. Insert the so ceiling le adapters through the
pair of small holes beside both keyholes on the
sensors mounng plate.
iii. Poke the adapter nes through the ceiling le,
then bend each ne over in opposite direcons for
a secure t.
iv. Replace the ceiling le.
•With double sided tape or Velcro™, not provided. Cut two lengths of
tape and remove the backing. Place on the mounng surface of the
sensors back plate, pressing down. Remove the backing from the tapes
other side and place the sensor on the ceiling surface, pressing rmly.
5. Refer to the section titledRIBWxxx-EN3.
6. Once linking is complete, replace the sensor cover.
seated. If the cover is not firmly attached, it could obstruct the lens and
adversely affect operation.
Lens mask sckers are provided in the packaging for
your convenience.
1. As needed, peel o the lens masks to t the desired
area to be blocked.
2. Apply the mask gently to the secon of the lens exterior
to block the required area from occupancy sensing.
Lens Mask Applied
Wire Mounts
IBWxxx-EN3
This process requires the controller or RIBWxxx-EN3 to be
mounted, powered and within range of the sensor to be
linked.
4

5
The sensor is a solar powered device that absorbs energy through a solar panel;
storing it for use during low light periods. Before assigning the sensor to
a RIBWxxx-EN3/controller, the WVSUS-EN3 must be exposed to a good light
source for at least 2 minutes.
1. Remove the cover by inserng a small screwdriver under the white
enclosures lip. Gently twist the screw driver and pull the cover away from
the base.
2. Acvate LEARN or LINK mode at the receiver, if necessary refer to the
manufacturers documentaon.
3. Press the sensors LINK buon.
4. Deacvate LEARN mode at the receiver.
The battery is not required for normal
operation when the WVSUS-EN3
receives adequate natural or artificial
light, minimum 6 foot candles or 65
lux. The WVSUS-EN3 model comes with
a battery (requires installation).
1. Remove the cover by inserng a small
screwdriver under the white enclosures lip. Gently twist the screw driver
and pull the cover away from the base.
2. To remove an old baery, use a small screwdriver as a lever and insert
under the baery. Gently twist the screwdriver so the baery pops out.
3. Install or replace the baery with a new CR1632 coin cell baery insuring
the posive side (+) will be facing up.
4. Place the baery in the holder and press in place with your thumb.
Install CR1632 battery. Remove cover to expose TEST BUTTON. There are 3
available tests: Light Level, Walk and Sensitivity.
Baery Holder
Link Buon
1. To enter test mode, press and hold the test button for 6 seconds. The green
LED will begin to blink (LEDs are located under the lens).
2. Press the test button for 6 more seconds to start Light Level Test. The
green LED will blink in accordance to the light level it is detecting. This will
change (2 second lag time) if you move the sensor to areas with different
light levels. See blink indicator table on the next page.

6
The green LED will blink according to the energy produced by the solar cell
Lux
0 0 0 below operang level
150-100 4.5 to 9 min. operang level
2100-200 9 to 18 operaonal
3200-400 18 to 36 operaonal
4400-800 36 to 72 operaonal
5 800+ 72+ operaonal
The test will repeat every 2 seconds and run for a duration of 100 seconds.
To exit Light Level test, hold button for 10 seconds.
:
1. Enter test mode, hold test button for 6 seconds. The Green LED will blink.
2. Quickly press and release the test button. The Amber LED will blink.
3. Quickly press and release the test button again. The Red LED will blink.
Hold test button for 6 more seconds to begin Walk Test.
The red LED will blink on every motion event. This allows an installer to verify
the sensor can monitor and detect motion in an area as required. The RED will
begin blinking when motion is detected. The test will run for a duration of 100
seconds. To exit Walk Test, hold button for 10 seconds.
The sensitivity feature allows the installer to adjust
the sensitivity level. False occupancy states caused by other elements can be
reduced by reducing the sensitivity level. The default setting is max. sensitivity.
1. Enter test mode, hold test button for 6 seconds. Green LED will blink.
2. Quickly press and release the test button. Amber LED will blink.
3. Quickly press and release the test button again. Red LED will blink.
4. Quickly press and release the test button again. Red and Amber LEDs will
blink.
5. Hold test button for 6 more seconds to start Sensitivity Test.

7
One of the LEDs will begin blinking based on the selected settings, see the
. A press and release of the button will allow you to
scroll through the settings as shown in the sensitivity adjust table.
High Green LED blinking
Medium Amber LED blinking
Low Red LED blinking
NOTE: The low sensivity seng is used as the base line for the lens detecon ray
diagrams found on the data-sheet.
4. To select a seng press and hold the test buon for 10 seconds when the
desired LED is blinking. To exit without saving, allow the test to me-out in
60 seconds.
Careful planning is needed when locang the receivers and transmiers based
on the construcon materials in the space and possibility of tenant’s furniture
disrupting the transmissions.
The occupancy sensor should be installed in the space where the
RIBWxxx-EN3 is mounted and connected to the occupancy control
equipment. The signal will travel through some material barriers.
Refer to the tables on the next page for range consideraons with building
materials that reduce the radio signal power.

8
Wood 0 - 10%
Plaster 0 - 10%
Glass 0 - 10%
Brick 5 - 35%
MDF 5 - 35%
Ferroconcrete 10 - 90%
Metal 90 - 100%
Aluminum 90 - 100%
Avoid locang transmiers and receivers on the same wall.
Avoid locang transmiers and receivers where the telegrams must penetrate
walls at acute angles. This increases the material the telegram must pass through
reducing the signal power.
Avoid large metal obstrucons as they create radio shadows. Place receivers in
alternate locaons to avoid the shadow or use repeaters to go around the obstacle.
Do not locate receivers close to other high frequency transmiers.
Leave at least 3’ between the receiver and any other source of interference
including, ballasts, LED drivers, computers, video equipment, Wi-Fi/LAN
routers, GSM modems and monitors. Transmiers are not aected by these
sources of interference.
CEC Title 24 Compliant
Built in an ISO9001 cered facility
FCC Part 15.231 (902 MHz models only)
Contains FCC ID: TCM300U
The enclosed device complies with Part 15 of the FCC Rules.
Operaon is subject to the following two condions:
(I.) this device may not cause harmful interference and
(ii.) this device must accept any interference received, including
interference that may cause undesired operation.
IC RSS-210(902 MHz models only)
Contains IC: 5713A-STM300U
Line of sight: 80’ (24m) corridors
Line of sight: 150’ (46m)open halls
Plasterboard: 80’ (24m) through 3 walls
Brick: 33’ (10m) through 1 wall
FerroConcrete: 33’ (10m) through 1 wall
Ceiling: not recommended
This manual suits for next models
1
Table of contents
Other RIB Security Sensor manuals
Popular Security Sensor manuals by other brands

Optex
Optex URX-P01WH Installation instructions and operators manual

Felix Storch
Felix Storch F-901B Reference manual

SSP
SSP SAFIX operating instructions

Optex
Optex BX SHIELD Series installation instructions

Renkforce
Renkforce 2108039 operating instructions

Toshiba
Toshiba TCB-LD1UPE Installation & operation manual