Allow a short period for part charging of the batteries and then isolate the mains supply to the lling in order to check the correct
operation of the tting in emergency mode. In the rst use, after a continuous charge for 24 hours, a mains failure should be
simulated to ensure that the tting work for its specied time (only at a safe & appropriate time). The tting will be fully charged with
in 24 hours’ continuous charging.
REGARD TO SAFETY TO THE INSTRUCTIONS:
1. Minimum distances around the apparatus should be ensured
for sufcient ventilation.
2. The ventilation should not be impeded by being covered
with newspapers, table-cloths, curtains, etc.
3. Pay attention to the environment by disposal of batteries.
4. If the external exible cable or cord of this luminaire is
damaged, it shall be exclusively replace by a qualied person
in order to avoid a hazard.
5. Batteries are the Ni-Cd type and have a normal service life
of approximately 4 years. Batteries should in any case, be
replaced only with the type specied, and exclusively replaced
by a qualied person.
6. Before commencing installation (and before maintenance at
any time), ensure that the main supply and the battery pack are
disconnected.
TESTING
How to use the test button:
• Press for 1 second to reset the timer function, the monthly
test will then be conducted after 30 days and the annual test
after 360 days.
• Press for 3 seconds to initiate a 5 minute functional test.
INDICATOR WORKING PERFORMANCE
Normal - Green indicator working
Battery failure - Red indicator ashing once every 3 seconds
Light source failure - Red indicator ashing twice every 3
seconds
Failure of duration test - Red indicator ashing three times
every 3 seconds
Auto test function fails - Red indicator ashing four times
every 3 seconds
INSTALLATION:
1. Remove four screws and lift off front cover.
2. Make cable entry hole using an appropriate hole cutter and
drill out xing points in back of housing.
3. Using the back of the tting as a template, mark and drill out
xing holes on your mounting surface. Prepare xing points to
mounting surface as appropriate. Secure the back of the tting
to the mounting surface using suitable xings and apply silicon
sealant to the xings if IP rating is to be maintained.
4. Thread the supply cable through the gland and into the
tting and connect the un-switched supply cable to terminals.
(Fitting a cable gland will also be necessary if moisture or
weather-proong is required.) Then mark the current date on
the battery pack and connect the battery lead.
5. Ret the front cover and tighten screws.
6. Adjust the angle of each head as required. Then restore the
power and check tting is working correctly.
FUNCTIONS OF LED INDICATOR
1. Auto test indicator
2. Failure/ charging indicator
3. Lamp head 1 indicator
4. Lamp head 2 indicator
AUTO TESTING
This product is tted with an automatic, self-test function
that will commission and test itself in accordance with the
requirements of the British Standards. Monthly and annual
tests will be automatically completed as detailed below with
tests including battery charge condition, functional test and
duration test.
1. An automatic test will run once every month for 10
minutes. The light will return to normal after 10 minutes.
2. An automatic test will run once a year for 3 hours. the light
will return to normal after 10 minutes.