RKC INSTRUMENT Z-COM User manual

Module Type Controller SRZ
Communication Extension
Module
Z
-
CO
M
Instruction Manual
(PLC/Host Communication)
(800) 576 - 6308
www.rkc-usa.com
Distributed By Inc,
RKC

All Rights Reserved, Copyright 2006, RKC INSTRUMENT INC.
Modbus is a registered trademark of Schneider Electric.
The name of each programmable controller (PLC) means the products of each manufacturer.
Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.

IMS01T07-E1 i-1
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please place this
manual in a convenient location for easy reference.
SYMBOLS
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not taken,
damage to the instrument may result.
WARNING
!
CAUTION
WARNING
!

IMS01T07-E1
i-2
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply,
source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure including
replacement of sensor, contactor or SSR, and all wiring must be completed before power is
turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines from
high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components
have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in this
manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior written
approval from RKC.
CAUTION

IMS01T07-E1 i-3
CONTENTS
Page
1. OUTLINE ...........................................................................1-1
1.1 Features......................................................................................................1-2
1.2 Checking the Product..................................................................................1-4
1.3 Model Code.................................................................................................1-5
1.4 Parts Description.........................................................................................1-6
1.5 Example of System Configuration...............................................................1-8
1.5.1 When one SRZ unit is connected............................................................................1-8
1.5.2 Multi-drop connection by PLC communication ........................................................1-9
1.5.3 Multi-drop connection by host communication ......................................................1-10
2. SETTING PROCEDURE TO OPERATION .......................2-1
2.1 When Use PLC Communication and Host Communication..........................2-2
2.2 Only When Use Host Communication ..........................................................2-8
2.3 When Use Loader Communication.............................................................2-13
3. COMMUNICATION SETTING ...........................................3-1
3.1 Communication Setting Procedures .............................................................3-2
3.2 Communication Setting of Z-COM Module ...................................................3-3
3.2.1 SRZ unit address setting.........................................................................................3-3
3.2.2 Communication speed and communication protocol setting by
DIP switch...............................................................................................................3-6
3.2.3 Communication speed and communication protocol setting via
host communication ..............................................................................................3-10
3.2.4 Communication setting for loader communication ................................................3-13
3.3 Communication Setting of the Functional Modules.....................................3-14
3.3.1 Address setting of the functional modules.............................................................3-14
3.3.2 Temperature control channel of the SRZ unit .......................................................3-15
3.3.3 Digital input/output channel of Z-DIO module .......................................................3-16
4. MOUNTING .......................................................................4-1
4.1 Mounting Cautions .......................................................................................4-2
4.2 Dimensions...................................................................................................4-5
4.3 Joinable Number of Modules........................................................................4-6
4.4 DIN Rail Mounting ........................................................................................4-7
4.5 Panel Mounting ............................................................................................4-9
4.6 Removing from the DIN Rail.......................................................................4-10

IMS01T07-E1
i-4
Page
5. WIRING ..............................................................................5-1
5.1 Wiring Cautions ............................................................................................5-2
5.2 Wiring of Power Supply ................................................................................5-3
5.2.1 Terminal Configuration (base).................................................................................5-3
5.2.3 Wiring method.........................................................................................................5-3
6. HOST COMMUNICATION .................................................6-1
6.1 Outline ..........................................................................................................6-2
6.2 Wiring ...........................................................................................................6-3
6.2.1 When SRZ unit is connected to a host computer with RS-422A .............................6-4
6.2.2 When SRZ unit is connected to a host computer with RS-485................................6-7
6.2.3 Multiple SRZ unit connections...............................................................................6-11
6.2.4 Termination resistor of Z-COM module .................................................................6-13
6.2.5 Connections for loader communication.................................................................6-14
6.3 Communication Requirements ...................................................................6-15
6.4 RKC Communication Protocol ....................................................................6-17
6.4.1 Polling procedures ................................................................................................6-17
6.4.2 Selecting procedures ............................................................................................6-23
6.4.3 Communication data structure ..............................................................................6-27
6.4.4 Channel number of communication ......................................................................6-29
6.4.5 RKC communication data list ................................................................................6-31
6.5 Modbus Communication Protocol...............................................................6-55
6.5.1 Message Format ...................................................................................................6-55
6.5.2 Function code .......................................................................................................6-56
6.5.3 Communication mode ...........................................................................................6-56
6.5.4 Slave responses ...................................................................................................6-57
6.5.5 Calculating CRC-16 ..............................................................................................6-58
6.5.6 Message format ....................................................................................................6-61
6.6.7 Data configuration.................................................................................................6-65
6.5.8 Modbus communication data list...........................................................................6-71
7. PLC COMMUNICATION ....................................................7-1
7.1 PLC Communication Outline ........................................................................7-2
7.2 MITSUBISHI MELSEC Series ......................................................................7-3
7.2.1 Outline.....................................................................................................................7-3
7.2.2 Wiring......................................................................................................................7-5
7.2.3 PLC communication environment setting..............................................................7-11
7.2.4 Setting on the PLC (Computer link module)..........................................................7-18

IMS01T07-E1 i-5
Page
7.3 OMRON SYSMAC Series...........................................................................7-19
7.3.1 Outline...................................................................................................................7-19
7.3.2 Wiring....................................................................................................................7-21
7.3.3 PLC communication environment setting..............................................................7-25
7.3.4 Setting on the PLC................................................................................................7-29
7.4 Data Transfer..............................................................................................7-30
7.4.1 PLC communication data transfer.........................................................................7-30
7.4.2 Data transfer procedures ......................................................................................7-35
7.4.3 Data processing precautions.................................................................................7-38
7.5 PLC Communication Data Map ..................................................................7-39
7.6 Usage Example ..........................................................................................7-54
7.6.1 Handling procedures .............................................................................................7-54
7.6.2 System configuration.............................................................................................7-56
7.6.3 SRZ unit setting ....................................................................................................7-57
7.6.4 Connection to host computer ................................................................................7-59
7.6.5 Connection with PLC.............................................................................................7-59
7.6.6 Setting of the PLC communication environmental setting
(system data) and SRZ setting data......................................................................7-60
7.6.7 PLC setting ...........................................................................................................7-64
7.6.8 Initial setting ..........................................................................................................7-66
7.6.9 Data setting...........................................................................................................7-67
8. COMMUNICATION DATA DESCRIPTION .......................8-1
8.1 Reference to Communication Data Contents ...............................................8-2
8.2 Communication Data of Z-COM Module.......................................................8-3
9. TROUBLE SHOOTING ......................................................9-1
10. SPECIFICATIONS .........................................................10-1
10.1 Communication Specifications..................................................................10-2
10.2 Product Specifications ..............................................................................10-6

i-6 IMS01T07-E1
MEMO

OUTLINE
IMS01T07-E1 1-1
This chapter describes features, package contents, model code, and system configuration, etc.
1.1 Features ...........................................................................................1-2
1.2 Checking the Product .......................................................................1-4
1.3 Model Code ......................................................................................1-5
1.4 Parts Description ..............................................................................1-6
1.5 Example of System Configuration.....................................................1-8
1.5.1 When one SRZ unit is connected ..............................................................1-8
1.5.2 Multi-drop connection by PLC communication...........................................1-9
1.5.3 Multi-drop connection by host communication.........................................1-10

1. OUTLINE
1-2 IMS01T07-E1
1.1 Features
The communication extension module Z-COM module has the following features:
The SRZ unit sets all of the data items via communication. Therefore before operation, it is necessary to set
value of each data item via communication.
The Z-COM module is connected to an SRZ functional module* (hereafter called “functional module”)
for the purpose of performing programmable controller communication (hereafter called “PLC
communication”) or host communication. The Z-COM module cannot be used alone.
The combination of Z-COM module and functional module is called an SRZ unit.
* SRZ functional module: Temperature control module Z-TIO module (hereafter called the Z-TIO module)
Digital I/O module Z-DIO module (hereafter called the Z-DIO module)
SRZ unit
Z-COM module Z-TIO modules Z-DIO modules
• Host communication
SRZ unit interfaces with the host computer or the operation panel via Modbus or RKC
communication protocols.
(RS-422A and RS-485 communication interfaces are used for both protocols.)
• PLC communication
SRZ unit can be connected to the MITSUBISHI MELSEC series or OMRON SYSMAC series
programmable controller (hereafter called the PLC) without using any program.
PLC communication
(MAPMAN)
[RS-422A or RS-485]
SRZ unit
Host communication:
RKC communication (ANSI X3.28) or Modbus
[RS-422A or RS-485]
Relay, SSR, thyristor, etc.
Control output
Temperature sensor
Measured input
PLC
MITSUBISHI MELSEC series
OMRON SYSMAC series
Push button switch, etc.
Event output
Power unit
DC 24 V
RUN/STOP
transfer
Flasher, etc.
Host computer or
Operation panel

1. OUTLINE
IMS01T07-E1 1-3
The four communication ports (COM. PORT1 to COM. PORT4) of the Z-COM module can be used to
perform the following types of communication. Two systems are used for communication.
COM. PORT Usage 1 Usage 2
COM. PORT1
Communication 1 COM. PORT2 * Host communication Host communication
COM. PORT3
Communication 2 COM. PORT4 * PLC communication Host communication
* SRZ unit extension communication port
Z-COM module
COM. PORT1
Communication 1
Communication 2
Host communication
PLC communication
or
Host communication
Communication
port
COM. PORT2
COM. PORT3
COM. PORT4
Number of temperature control
• Up to 16 Z-TIO modules can be connected to one Z-COM module. For example, when up to 16
Z-TIO modules (4-channel type) are connected to one Z-COM module, the maximum number of
temperature control channels per one unit becomes 64.
• For PLC communication, up to four Z-COM modules can be multi-drop connected to one PLC
communication port. Therefore, temperature control of up to 256 channels per one PLC
communication port can be performed.
• For host communication, up to 16 Z-COM modules can be multi-drop connected to one
communication port of host computer. Therefore, temperature control of up to 1024 channels per one
communication port of host computer can be performed.

1. OUTLINE
1-4 IMS01T07-E1
1.2 Checking the Product
Before using this product, check each of the following:
Model code
Check that there are no scratch or breakage in external appearance (case, front panel, or terminal, etc.)
Check that all of the items delivered are complete. (See below)
Name Q’TY Remarks
Z-COM module 1
Z-COM Installation Manual (IMS01T05-E) 1 Enclosed with instrument
Z-COM PLC Communication Quick Instruction
Manual (IMS01T06-E) 1 Enclosed with instrument
Z-COM Host Communication Quick Instruction
Manual (IMS01T09-E) 1 Enclosed with instrument
Joint connector cover KSRZ-517A 2 Enclosed with instrument
Power terminal cover KSRZ-518A 1 Enclosed with instrument
Z-COM Instruction Manual
(PLC/Host communication) (IMS01T07-E1) 1
This manual (sold separately) *
* This manual can be downloaded from our website:
URL: http://www.rkcinst.com/english/manual_load.htm
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC
sales office or the agent.
Accessories (sold separately)
Name Q’TY Remarks
End plate DEP-01 2
Termination resistor connector for Z-COM
W-BW-01 1 For RS-485
Termination resistor connector for Z-COM
W-BW-02 1 For RS-422A
Connection cable W-BF-01-3000 1
For PLC connection (Cable length: 3 m)
Terminal treatment:
Modular connector and Spade lug terminal *
Connection cable W-BF-02-500 1
For SRZ unit extension (Cable length: 0.5 m)
Terminal treatment:
Modular connectors (at both ends)
Connection cable W-BF-02-1000 1
For SRZ unit extension (Cable length: 1 m)
Terminal treatment:
Modular connectors (at both ends)
Connection cable W-BF-02-3000 1
For SRZ unit extension (Cable length: 3 m)
Terminal treatment:
Modular connectors (at both ends)
* Other types of cable, such as cable with 9-pin D-SUB connector, are also available. Please contact RKC sales office or the agent.

1. OUTLINE
IMS01T07-E1 1-5
1.3 Model Code
Check whether the delivered product is as specified by referring to the following model code list. If the
product is not identical to the specifications, please contact RKC sales office or the agent.
Z-COM module
Z - COM - A - /
(1) (2) (3) (4) (5)
Hardware coding only Quick start code
(1) Communication 1 (COM. PORT1, COM. PORT2)
4: RS-422A
5: RS-485
(2) Communication 2 (COM. PORT3, COM. PORT4)
4: RS-422A
5: RS-485 *
* When using the OMRON SYSMAC series, RS-485 cannot be selected.
(3) Quick start code (communication protocol selection)
N: No quick start code (Configured as factory default)
1: Specify quick start code 1
(4) Communication 1 protocol (COM. PORT1, COM. PORT2)
No code: No specify quick start code
1: RKC communication (ANSI X3.28)
2: Modbus
(5) Communication 2 protocol (COM. PORT3, COM. PORT4)
No code: No specify quick start code
1: RKC communication (ANSI X3.28)
2: Modbus
3: PLC communication (MITSUBISHI MELSEC series special protocol)
(AnA/QnA series or Q series)
4: PLC communication (OMRON SYSMAC series special protocol)
5: PLC communication (MITSUBISHI MELSEC series special protocol)
(A series, FX2N/FX2NC series or FX3U/FX3UC series)

1. OUTLINE
1-6 IMS01T07-E1
1.4 Parts Description
Z-COM module mainframe
Front view
DIP switch
Base
(See page 1-7)
Right side view
Module
mainframe
Indication lamp
(RX2/TX2)
Indication lamp
(RX1/TX1)
Loade
r
communication
connecto
r
Indication lamp
(FAIL/RUN)
A
ddress setting switch
COM. PORT1
Communication 1
COM. PORT2
Communication port
COM. PORT3
COM. PORT4
Communication port
Communication 2
Indication lamps
FAIL/RUN*[Green or Red] When normal (RUN): A green lamp is on
Self-diagnostic error (FAIL): A green lamp flashes
Instrument abnormality (FAIL): A red lamp is on
RX1/TX1 [Green]
The green lamp is lit when data corresponding to communication 1
(COM. PORT1, COM. PORT2) is sent or received.
RX2/TX2 [Green]
The green lamp is lit when data corresponding to communication 2
(COM. PORT3, COM. PORT4) is sent or received.
* When error occurs, see Chapter TROUBLESHOOTING (P. 9-1).
Communication port (modular connector)
COM. PORT1
(Communication 1)
Used to connecting the Operation panel or Host computer.
[RS-485 or RS-422A]
COM. PORT2
(Communication 1)
The COM. PORT2 is used for the extension of SRZ unit.
[RS-485 or RS-422A]
COM. PORT3
(Communication 2)
Used to connecting the programmable controller (PLC), Operation
panel or Host computer. [RS-485 or RS-422A]
COM. PORT4
(Communication 2)
The COM. PORT4 is used for the extension of SRZ unit.
[RS-485 or RS-422A]
Switches
Address setting switch Set SRZ unit address with address setting switch.
DIP switch •Sets communication speed, communication protocol and data bit
configuration corresponding to each of communication 1 and
communication 2.
•Sets dip switch setting validity/invalidity.

1. OUTLINE
IMS01T07-E1 1-7
Base
Mounting holes (M3 screw)
Power supply
terminals
Joint connector
Mounting
bracket
Terminal 3, 4 and 5
Usage is prohibited.
Front Rear
Mounting holes (M3 screw) Holes for screws to fix the base to a panel, etc.
Customer must provide the M3 screws.
Joint connector
Used to mechanically and electrically connect each module.
Power supply terminals These are terminals to supply power to the Z-COM module and joined
function modules.
Terminal number Signal name
1 24 V DC (+)
2 24 V DC (−)
Terminal 3, 4 and 5 These terminals cannot be used for the Z-COM module.
(Usage is prohibited.)
In addition, when the Z-COM module is connected to a functional
module, do not use terminals 3, 4, and 5 of the functional module.
Mounting bracket Used to fix the module on DIN rails and also to fix each module joined
together.

1. OUTLINE
1-8 IMS01T07-E1
1.5 Example of System Configuration
The following is an example of system configuration when the SRZ unit is connected to PLC, host
computer or operation panel.
One SRZ unit consists of one Z-COM module and several functional modules.
1.5.1 When one SRZ unit is connected
Number of connected modules for functional modules and Number of temperature
controls
• When joining functional modules of the same type to Z-COM module
Up to 16 functional modules (Z-TIO, Z-DIO) can be connected to one Z-COM module with SRZ unit.
As the number of temperature control channels per Z-TIO module is 4, the maximum number of
temperature control channels per unit becomes 64 (4-channel ×16 Z-TIO modules).
• When joining functional modules of two or more differential types to Z-COM module
Up to 31 functional modules (Z-TIO, Z-DIO) can be connected to one Z-COM module with SRZ unit.
(However, the maximum joinable number of functional modules of the same type is 16.)
Example
Communication 1 (COM. PORT1, COM. PORT2): Host communication (RS-422A)
Communication 2 (COM. PORT3, COM. PORT4): PLC communication (RS-422A)
Z-TIO module: 16 modules
Z-DIO module: 15 modules
Host computer
RS-422A
RS-232C
Z-COM module (Unit address 0)
The address of the Z-COM module will be the SRZ
unit address.
PLC
communication
Host communication
(RKC communication or Modbus)
16 Z-TIO modules
Up to 31 modules can be connected
RS-232C/
RS-422A
converter
RS-422A
SRZ unit
0
(0)
15 Z-DIO modules
1
(1)
E
(14)
F
(15)
0
(0)
1
(1)
E
(14)
Z-TIO module
address
Z-DIO module
address
PLC
Communication
converter
COM-A

1. OUTLINE
IMS01T07-E1 1-9
1.5.2 Multi-drop connection by PLC communication
Number of connected modules for SRZ units and Number of temperature controls
• For PLC communication, up to four units (i.e. four Z-COM modules) can be multi-drop connected to
one PLC communication port.
• As up to 16 Z-TIO modules can be connected to one Z-COM module, temperature control of up to
256 channels can be performed. (4-channel ×16 Z-TIO modules ×four SRZ units)
Example
Communication 1 (COM. PORT1, COM. PORT2): Host communication (RS-422A)
Communication 2 (COM. PORT3, COM. PORT4): PLC communication (RS-422A)
SRZ unit: four units
Host computer
RS-422A
RS-232C
Z-COM module (Unit address 0)
PLC communication
Host communication
(RKC communication or Modbus)
16 Z-TIO modules
Up to 31 modules can be connected
RS-232C/
RS-422A
converter
RS-422A
SRZ unit
0
(0)
15 Z-DIO modules
1
(1)
E
(14)
F
(15)
0
(0)
1
(1)
E
(14)
Z-TIO module
address
Z-DIO module
address
PLC
0
(0)
1
(1)
E
(14)
F
(15)
0
(0)
1
(1)
E
(14)
Z-COM module (Unit address 1)
Z-TIO modules Z-DIO modules
0
(0)
1
(1)
E
(14)
F
(15)
Z-COM module (Unit address 2)
Z-TIO modules
0
(0)
1
(1)
E
(14)
F
(15)
Z-COM module (Unit address 3)
Z-TIO modules
Up to four SRZ units can be
multi-drop connected to one PLC
communication port.
Number of temperature control:
256 CH max.
Communication
converter
COM-A

1. OUTLINE
IMS01T07-E1
1-10
1.5.3 Multi-drop connection by host communication
Number of connected modules for SRZ units and Number of temperature controls
• For host communication, up to 16 units (i.e. 16 Z-COM modules) can be multi-drop connected to one
host communication port.
• As up to 16 Z-TIO modules can be connected to one Z-COM module, temperature control of up to
1024 channels can be performed. (4-channel ×16 Z-TIO modules ×16 SRZ units)
Example
Communication 1 (COM. PORT1, COM. PORT2): Host communication 1 (RS-422A)
Communication 2 (COM. PORT3, COM. PORT4): Host communication 2 (RS-422A)
SRZ unit: four units
Host computer
RS-232C
Z-COM module (Unit address 0)
Host communication 1
(Modbus)
16 Z-TIO modules
Up to 31 modules can be connected
RS-232C/
RS-422A
converter
RS-422A
SRZ unit
0
(0)
15 Z-DIO modules
1
(1)
E
(14)
F
(15)
0
(0)
1
(1)
E
(14)
Z-TIO module
address
Z-DIO module
address
0
(0)
1
(1)
E
(14)
F
(15)
0
(0)
1
(1)
E
(14)
Z-COM module (Unit address 1)
Z-TIO modules Z-DIO modules
0
(0)
1
(1)
E
(14)
F
(15)
Z-COM module (Unit address 15)
Z-TIO modules
RS-422A
Host communication 2
(Modbus)
Operation panel
Communication
converter
COM-A
Up to 16 SRZ units can be multi-drop
connected to one communication
port of host computer or operation
panel.
Number of temperature control:
1024 CH max.

SETTING
PROCEDURE
TO OPERATION
IMS01T07-E1 2-1
2.1 When Use PLC Communication and Host Communication..............2-2
2.2 Only When Use Host Communication ..............................................2-8
2.3 When Performing Operation Setting via Loader Communication ...2-13

2. SETTING PROCEDURE TO OPERATION
2-2 IMS01T07-E1
2.1
When Use PLC Communication and Host Communication
Conduct necessary setting before operation according to the procedure described below.
Remove the product from its packaging and verify that no parts are missing.
See 1.2 Checking the Product (P. 1-4).
To perform host communication, a communication program must be created. Refer to the RKC
communication protocol or the Modbus communication protocol to create a communication program.
For RKC communication protocol, see 6.4 RKC Communication Protocol (P. 6-17).
For Modbus protocol, see 6.5 Modbus Protocol (P. 6-55).
Set the communication port of the host computer.
•Communication speed
•Data bit configuration
The communication settings of the host computer and the communication settings of the SRZ
unit must be set to the same values.
Set the SRZ unit address.
See 3.2.1 SRZ unit address setting (P. 3-3).
Checking the Product
Preparation of host
communication program
A
Communication port setting
of the host computer
Unit address setting
of the SRZ unit
Table of contents
Other RKC INSTRUMENT Control System manuals

RKC INSTRUMENT
RKC INSTRUMENT FAREX SR MINI SYSTEM Use and care manual

RKC INSTRUMENT
RKC INSTRUMENT SR Mini HG Assembly Instructions

RKC INSTRUMENT
RKC INSTRUMENT SR Mini HG Use and care manual

RKC INSTRUMENT
RKC INSTRUMENT SR Mini System Owner's manual

RKC INSTRUMENT
RKC INSTRUMENT SR Mini System Assembly Instructions

RKC INSTRUMENT
RKC INSTRUMENT AC8112 User manual
Popular Control System manuals by other brands

Fly Sky
Fly Sky FS-GT2 instruction manual

GSM Activate
GSM Activate GSM Auto Dialler Plus manual

HySecurity
HySecurity HydraWedge SM50 installation instructions

Fly Sky
Fly Sky FS-HW-G4P user manual

Spraying Systems
Spraying Systems AutoJet SCS Series owner's manual

smart home
smart home Securelinc Programming guide