Rockwell Automation Allen-Bradley OptixPanel User manual

Installation Instructions
Original Instructions
OptixPanel Compact Operator Panels
Bulletin 2800C
Equipment with the UL/cUL mark complies with the requirements of UL 61010-1, UL 61010-2-201, CSA C22.2 No. 61010-1, and CSA C22.2 No. 61010-
2-201. Copies of the certificate of compliance are available at rok.auto/certifications.
European Union Directive and UKCA Compliance
This equipment meets the European Union Directive and UK requirements when installed within the European Union, UK, or EEA regions and have the CE or UKCA marking. A
copy of the declaration of the conformity is available at rok.auto/certifications.
Installation Guidelines
Follow these guidelines to make sure that your OptixPanel™ operator panel provides service with excellent reliability.
• When choosing the installation site, consider the following:
- The site must have sufficient power.
- The site must be indoors and non-hazardous.
- The site must not expose the computer to direct sunlight.
• The operator panel can operate in the following environmental conditions:
- Operating temperature: 0…50 °C (32…122 °F).
- Storage temperature: -20…+60 °C (-4…140 °F).
Operation/storage relative humidity (RH) noncondensing: 20%…90%.
Follow these requirements to mount the operator panel.
• Choose a suitable mounting height.
• To help prevent overheating and to provide access to the I/O ports for cable connections, mount the operator panel with
the following minimum clearances from all four sides of the outer frame and back of the operator panel chassis:
- X direction ≥ 50 mm (1.96 in.)
- Y direction ≥ 100 mm (3.93 in.)
- Z direction ≥ 50 mm (1.96 in.)
• For optimal performance, mount the operator panel in the horizontal orientation and vertical (upright) position, so the I/O
ports face down.
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in
IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to EN 61326-1. Without appropriate precautions, there can be potential
difficulties with electromagnetic compatibility in other environments caused by conducted as well as radiated disturbance.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements.
• UL 50, UL 50E, CSA C22.2, No. 94.1, and CSA C22.2, No. 94.2, as applicable, for explanations of the degrees of protection provided by enclosures.
ATTENTION: This operator panel is intended to operate in an industrial or control room environment, which uses some form of power isolation from the
public low-voltage mains. Some computer configurations cannot comply with the EN 61000-3-2 Harmonic Emissions standard as specified by the EMC
Directive of the European Union. Obtain permission from the local power authority before you connect any computer configuration that draws more
than 75 W of AC power directly from the public mains. All I/O cables are rated for indoor use only.
IMPORTANT The vertical position can be tilted up to 20° forward or 20° backward from the upright position. However, this acceptable tilt angle range decreases
the maximum operating air temperature to 45 °C (113 °F).
Installation min. clearance
X
X
Y
Y
Z
-20°-20°
0°
Installation max. tilt

2Rockwell Automation Publication 2800C-IN001B-EN-P - June 2023
OptixPanel Compact Operator Panels Installation Instructions
Prepare the Panel Cutout
Observe these guidelines to install the operator panel in a panel.
• Plan the panel cutout area that is needed for your operator panel.
• To ensure installation with the proper IP protection grade, the following conditions have to be satisfied:
• The mounting panel material must be 3…6 mm (0.11…0.24 in.) thick with a max deformation limit on the plane of 0.5 mm (0.01 in.).
• For a uniform gasket seal, the roughness of the panel surface must be ≤ 120 microns (Rz 120).
• Verify that the area around the panel is clear of obstructions.
Required Tools for Installation
Install the operator panel
To install the operator panel in the panel cutout, perform the following steps.
1. Remove all electrical power from the panel before you make the cutout.
2. Cut an opening in the panel area to the dimensions needed for your operator panel.
3. After the cutout is completed, clean the panel area of all debris and metal fragments.
4. Make sure that the sealing gasket is positioned properly on the computer.
5. From the front of the panel, insert the operator panel into the cutout (A) and rotate it (B) until it adheres
completely to the panel (C).
6. Slide the mounting clips into the holes on all four sides of the operator panel and repeat the procedure in step 7 through step 9 for all clips.
WARNING: Failure to follow these guidelines can result in personal injury or damage to the panel components. Take precautions so any metal fragments
during the panel cutout do not enter components that are installed already in the panel.
AVERTISSEMENT: Lorsqu'un panneau est découpé, des morceaux de métal peuvent être produits. Vous devez prendre les mesures de sécurité
nécessaires pour prévenir la pénétration des morceaux dans les composants déjà installés dans le panneau.
Table 1 - Cut Out dimensions
Display Size, in. Format(1)
(1) Widescreen (W) format is offered with analog resistive and projective capacitive (PCAP) touch
screens.
Panel Cutout Dimensions(2) [mm (in.)]
(2) Tolerance ±1 mm (0.04 in.).
A B
4.3 W 129.5 (5.09) 88.5 (3.48)
7.0 W 195.0 (7.67) 138.5 (5.45)
Tools required:
• Panel cutout tools.
• Hexagonal key 1.5 mm (supplied) and torque limiting screwdriver with a 1.5 mm hex
key bit.
• Mounting clips (supplied), for the needed quantity, see Figure 1 on page 3
• Safety glasses.
IMPORTANT You need two people to install the operator panel; one person holds the operator panel in place while the second person installs the mounting clips.
IMPORTANT The gasket is a part of the display and forms a compression-type seal. Do not use sealing compounds.
Panel Cutout Areas
A
B
Supplied tools
Sequence No. Description
1 Clip
2 Hexagonal key
12
Sealing
gasket
Clip hole
Clip hole
Clip hole
Sealing gasket / Clip holes
ABC

Rockwell Automation Publication 2800C-IN001B-EN-P - June 2023 3
OptixPanel Compact Operator Panels Installation Instructions
7. Insert the clip into the mounting hole side (D).
8. Rotate it down (E) and pull it outward (F).
9. According to the tighten sequence in Figure 1, tighten the mounting clips (G) with the supplied hexagonal key and verify the torque of 0.2 N•m (1.8 lb•in) with a
limiting screwdriver (needed a 1.5 mm hex key bit).
Figure 1 - Mounting clips tighten and torque sequence by display size
Connectors/LEDs/Buttons
• Connect peripheral cables to the appropriate I/O ports on the computer. To comply with EN 61326-1, use the following for cable types. All I/O cables must be used
only indoors, and USB cables must be less than 3 m (9.84 ft) long.
ATTENTION: Tighten the mounting clips to the specified torque to provide a proper seal and to help prevent product damage. Rockwell Automation
assumes no responsibility for water or chemical damage to the computer or other equipment within the enclosure because of improper installation.
Table 2 - Connectors / LEDs / Buttons
Item
No. Description Required
cable LED
Color Function
1Front Power
On LED — Green Indicates that the system is powered on and
boot sequence was successful.
2 DC power Unshielded — Power connector.
3 Restart button — —
Forces an internal reset, as if power was lost
temporarily and then returned.
IMPORTANT: Use this button only if there are
no better options, like keyboard or mouse
commands, or if the resumed DC power does
not restart the computer. System reset can
cause data loss and possible corruption to
the operating system.
4Factory reset
button — — Allows the total restoration of the firmware
and factory settings with the deletion of all
application data.
5Factory Reset
LED —Blue Factory reset procedure in progress.
OFF Standard/common status.
6 USB 2.0 Shielded — USB 2.0 connector.
7 LAN Shielded — RJ45 connector.
8 COM Shielded — RS232/422/485 serial port connector.
9 LED COM1 TX — Green Transmission signal for COM interface.
10 LED COM1 RX — Green Receive signal for COM interface.
11 Restart /
Power LED —
Red Power supply ON and Boot sequence FAIL.
Restart button pressed.
Green Power supply ON and correct BOOT
sequence.
DEFG
2
1
4.3 in. (4 clips)
I/O Ports
4
3
7.0 in. (6 clips)
2
1
I/O Ports
34
5
6
OptixPanel Compact - rear view
2
4
36
5
789
10
OptixPanel front view*
1
*LED 1 is present only in:
OptixPanel Compact systems
7.0 in. size.
11

4Rockwell Automation Publication 2800C-IN001B-EN-P - June 2023
OptixPanel Compact Operator Panels Installation Instructions
DC Power Supply Guidelines
All panel PCs have the following features:
• The internal power supply of the operator panel has a galvanically isolated DC-DC converter board for
increased electrical noise immunity.
• Reverse polarity circuitry, overvoltage, and a 3 A soldered fuse provide input power protection.
Follow these guidelines to select the DC power to supply the computer.
• The operator panel must be powered with a voltage of 24V DC (18…32V DC SELV input voltage range).
• Power consumption is rated at 11 W max @ 50 °C (122 °F) ambient temperature.
Connect DC Power
To minimize ground loop currents and noise, we recommend that DC powered models use only one grounded connection.
Install the Factory-supplied DC Power Connector Assembly
Terminal block cabling procedure
1. Remove the DC terminal block (5) from the operator panel.
2. Use wires not included, (1) (2) (3) with 1.5 mm2 (16 AWG) cross section.
3. Strip 7 mm (0.275 in.) from the end of each power wire (4).
4. Insert each stripped end into the DC terminal block and fix it with the corresponding screws (7) with 0.22…0.25 N•m (0.16…0.18 ft•lb) torque.
5. Insert the cable tie (9) through the slots of the terminal block (11) connector clamp [step (A)].
6. Slide the connector half with the attached tie onto the end of the DC terminal block [step (B)].
7. Tighten the tie and remove the excess part [step (C)].
ATTENTION: The system has to be powered with a 24V DC (18…32V) power supply that satisfies the requirements of safe extra low voltage (SELV) in
accordance with IEC/EN/DIN EN/UL61010-1 and UL61010-2-201. The power supply has to fulfill the requirements NEC Class2 or LPS in accordance with
IEC/EN/DIN EN/UL61010-1 and UL61010-2-201.
Tools required:
• Adjustable torque screwdriver with M2 and M3 flat-blade screw bits.
• Wire stripper, cutter, and crimper tool.
• Cutting pliers.
Table 3 - Terminal Block Connection Specifications
Item No. Description Value
1 DC+ (24V DC nominal)
1.5 mm2 (16 AWG) wire
2 DC- (0V DC nominal)
3 Ground wire
4 Stripped wire length 7 mm (0.275 in.)
5 Terminal block —
6 Polarity symbol —
7Torque range to secure DC power wires 0.22…0.25 N•m
(0.16…0.18 ft•lb)
8 Torque value to reinstall DC terminal block to computer 0.3 N•m (0.22 lb•in)
9 Cable tie (qty: 1) —
10 Labels (qty: 2) —
11 Half cover with cable tie slot —
12 Half closing cover —
The colors of wires should follow regulations applicable where the system will be used.
lpk
(<5 A)
lpk: load peak
T: time
T<2ms
Inrush current
DC power connector assembly
+–
24V - - -
Terminal block cover kit
1
8
4
7
2
3
11
56
9
12
10
Terminal block cover assembly
D E F GCBA

Rockwell Automation Publication 2800C-IN001B-EN-P - June 2023 5
OptixPanel Compact Operator Panels Installation Instructions
8. Install the white labels (10) supplied with the terminal block cover kit [steps (D) (E)]. The white label can be used for identification or other information.
9. Align and install the other connector (12) clamp half [step (F)] to complete the assembly [step (G)]. When installed correctly, both tabs of the clamp half lock into
place.
Connect DC Power
1. Connect the DC terminal block (complete with cables and cover) to the operator panel chassis and fix it with the corresponding screws (8) with 0.3 N•m (0.22 ft•lb)
torque.
2. Power on the system.
3. Front Power LED (1) and Restart/Power LED (11) light green.
4. The operating system desktop appears after few seconds.
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation. You can view or download publications at rok.auto/literature.
Resource Description
OptixPanel Compact User Manual, publication 2800C-UM001 Provides details on how to install, configure, operate, and troubleshoot the OptixPanel operator panels.
OptixPanel Technical Data, publication 2800-TD001 Provides technical specifications about the OptixPanel operator panels.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines to install a Rockwell Automation industrial system.
Product Certifications website rok.auto/certifications Provides declarations of conformity, certificates, and other certification details.
1
11
On OptixPanel Compact systems
front LED (b) is present only on
7.0 in. size.

Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur
PN-696497
DIR 10007325296.01 (Version 01)
Allen-Bradley, expanding human possibility, OptixPanel, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
*PN-696497*
PN-696497
Waste Electrical and Electronic Equipment (WEEE)
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation Support
Use these resources to access support information.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product notification updates. rok.auto/support
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Technical Documentation Center Quickly access and download technical specifications, installation instructions, and user manuals. rok.auto/techdocs
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center (PCDC) Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/pcdc
Publication 2800C-IN001B-EN-P - June 2023 | Supersedes Publication 2800C-IN001A-EN-P - June 2023
Copyright © 2023 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Vendor Code: 80460122.01
Table of contents
Other Rockwell Automation Control Panel manuals
Popular Control Panel manuals by other brands

Beckhoff
Beckhoff CP79 Series Installation and operating instructions

Tangent Wave
Tangent Wave CP300 user manual

DSC
DSC PC2550 installation manual

Potter
Potter PFC 2000RC Installation, operation and instruction manual

Viessmann
Viessmann Vitotronic 200 GW1 operating instructions

McDantim
McDantim Trumix TM300 installation instructions