Rosemount Nuclear Instruments 710DU User manual

00813-0100-4471
English
May 1999
Rev. AB
Model 710DU
Trip/Calibration
System
™

2
Model 710DU Trip/Calibration System
•Qualified per IEEE Std 323-1974 and
IEEE Std 344-1975
•Use with 4–20 transmitters or 3-wire
100 Vplatinum RTD’s
•Exceptional reliable modular design
•Up to 8 precision trip points per signal
FEATURES
Rosemount® Model 710DU Trip/Calibration
Systems continuously monitor critical process
parameters and provide highly accurate alarm
action. As many as eight precision-calibrated trip
points can be assigned to a single sensor channel.
Any trip point can be quickly verified or changed.
The system consists of a card file with a plug-in
calibration unit and space for up to 12 interchangeable
trip unit modules. These features make Model 710DU
Systems highly flexible, simple to install or reconfigure,
and easy to calibrate.
OPERATION
Trip Unit
One master trip unit is required for each 4–20 mA
transmitter or RTD input. A basic master trip unit
displays the sensor output, provides one high or low
trip circuit, a high/low gross failure circuit, and a
proportional analog output for driving up to seven
slave trip units.
Each slave adds one additional trip point and gross
failure circuit to the transmitter loop. The trip
output of any master or slave trip unit can drive an
external relay. The auxiliary analog output of the
master trip unit can be used to drive an external
proportional controller or recorder.
The trip point circuit features precision external
adjustment with either high or low nonlatching trip
action. The gross failure circuits are internally
adjustable with manual reset high and low trip
action. Trip point and gross failure indicating lamps
are furnished on each trip unit.
Calibration Unit
The trip point for any master or slave trip unit
within the card file can be read or accurately
calibrated by the calibration unit. This unit provides
space for a unique digital readout assembly and
permits the operator to automatically replace the
field transmitter input signal to any channel with a
precisely adjustable calibration signal. This enables
the trip point to be compared exactly with the
desired input signal level. After the trip points for all
channels within the file have been set, the readout
assembly can be removed and plugged into any other
calibration unit.
Applications
Model 710DU trip/calibration systems are ideally
suited to nuclear power applications or any process
where frequent calibrations of trip points are
essential. Critical process trip points are repeatable
within 0.13% of span for 4–20 mA transmitter inputs
and 0.75% of span for RTD inputs under normal
conditions. System components have been qualified
per IEEE Std 323-1974 and IEEE Std 344-1975 as
stated in Rosemount Qualification Reports
D8200037 and D8300112.
710-001AB
Rosemount and the Rosemount logotype are registered trademarks of
Rosemount Inc.
Cover Photo: 710-001AB

Rosemount Nuclear Instruments, Inc.
3
Qualified Life
Qualified life is dependent on continuous ambient
temperature at the installation site (see Figure 1)
as well as the number of functional cycles. See
Rosemount Qualification Report D8200037 for
more detail regarding qualified life.
FIGURE 2. Model 710DU Trip/Calibration System Diagram.
710-0581A
24 V
POWER
SUPPLY
Calibrate
Command
Calibration
Current
Calibration Status Test
Jack
Trip Status
Auxiliary Analog
Output Test Jack
Gross Failure Output
Trip Output
Test Jack Sensor Signal
3-WIRE 100 V
PLATINUM
RTD
4–20 mA
PRESSURE
TRANSMITTER
CALIBRATION
UNIT WITH
READOUT
ASSEMBLY
RTD INPUT
MASTER TRIP
UNIT
(1 REQUIRED
FOR EACH
RTD)
4–20 mA
INPUT
MASTER
TRIP UNIT
SLAVE
TRIP
UNIT
Trip Status
Trip Status
Sensor Signal Test Jack
Gross Failure Output
Trip Output
Slave Input Test Jack
Gross Failure Output
Trip Output
Auxiliary Analog Output
Test Jack
Trip Status
Signal from
Selected
Master or Slave
Trip Unit
Calibration
Current
Calibrate
Command
To Additional
Master or
Slave Trip
Units
To Additional Slave Trip Units
(7 Maximum per Master Trip Unit)
Card File
1–5 V dc Auxiliary Analog
Output
Calibrate
Command
Calibration
Current
FIGURE 1. Qualified Life vs. Temperature.
Qualified Life
710-0308A
Temperature (°F)
Time (Years)

4
Model 710DU Trip/Calibration System
TRIP UNIT CONFIGURATIONS
Master Trip Units
The master trip unit may be installed in any of the
12 card file positions. It provides an analog meter
(scaled in °C, °F, %, GPM, etc.) to display the sensor
signal. It also has one trip point and one gross
failure output circuit.
The trip point circuit has a 0–1 logic output signal
(0–24 V dc) for driving an external relay. A precision
adjustment screw is provided on the faceplate for
setting the trip point signal level. Switches for
selecting either a high or low trip action and a reset-
differential adjustment for the nonlatching trip
output are located on the circuit card.
The gross failure circuit provides a similar 0–1
logic output signal, but has internally adjustable set
points for both high and low latching trip action.
Each master trip unit has a trip status output
signal and an indicator lamp for the trip point, plus
a gross failure lamp and gross failure reset switch.
Both the trip output and gross failure output circuits
can be used to drive independent external relays.
Test jacks are also provided for monitoring the
sensor input and auxiliary analog output signal.
Slave Trip Units
Each slave trip unit adds one additional trip
output circuit and one gross failure output circuit to
any transmitter loop with a master trip unit. It has
the same features as a master trip unit, except that
it has no meter and no analog output.
FIGURE 3. Master or Slave Trip Unit Functions.
710-0581B
4–20 mA Transmitter Input or 3-Wire Platinum
RTD to Master Trip Unit with Process Meter or
Analog Output from Master to Slave Trip Unit
Trip
Unit
Trip Point Output for High or Low Trip
Action from 4–20 mA or Equivalent RTD
Span
Gross Failure Output for High Trip Action
from 19.5–40.5 mA, and Low Trip Action
from 0.5–4 mA on Master or Slave Trip Units
Analog Output from Master Trip Unit
(Proportional to Sensor Signal) Drives
up to 7 Slaves
Auxiliary 0–10 V dc Analog Output from
Master Trip Unit (Proportional to Sensor
Signal) for External Loads
Calibration Unit Input to Master Trip Unit
for Setting Trip Point on Master or Its
Associated Slave Trip Units
Trip Status Output from Master or
Slave Trip Unit to Calibration Unit
710-003AB
Master Trip Unit
Slave Trip Unit
710-002AB

Rosemount Nuclear Instruments, Inc.
5
CALIBRATION UNIT AND READOUT
Calibration Unit
The calibration unit provides a rapid, precise
means to check or adjust the trip point on any of the
12 channels in a card file. A removable readout
assembly (interchangeable among all calibration
units) gives high-resolution digital display of an
adjustable calibration current, which replaces the
transmitter input to any master trip unit selected.
When output of the selected master or slave trip unit
changes state, a second digital display latches and
provides a precise readout of the calibration current
level. A transient current can be added or subtracted
with the stable current for checking the response
time of externally driven equipment or for verifying
gross failure set points. During calibration, the
channel being tested is automatically placed in the
gross failure mode.
The calibration unit has a power switch, transient
current polarity switch, stable and transient current
adjustments, and a selector switch for applying the
calibration current to any master trip unit channel
while reading the trip point of the master or its
associated slaves. A calibration status signal (for
remote display) and a lamp on the faceplate indicate
that the system is in the calibration mode.
Test jacks are provided to monitor the time
response of the user's system.
Readout Assembly
The digital readout assembly displays both calibration
and trip current levels with 0.01 mA resolution. A trip
status output signal from the master or slave trip unit
latches the tracking trip current display. A trip status
lamp and reset button are provided.
Calibration Unit
Readout Assembly
710-004AB
710-005AB
FIGURE 4. Calibration Unit Function.
710-0581C
Trip Status Signal from
Master or Slave Trip Unit Calibration
Unit and
Readout
Assembly
Calibrate Command Signal to a Master Trip Unit
Opens Field Sensor Loop and Generates Gross
Failure Output
3.5–20.5 mA Stable Calibration Current Replaces
Sensor Input to a Master Trip Unit
A Transient Current Can Be Summed with the
Stable Current for Checking Response Time
Calibration Status Output
NOTE
When optional readout assembly is installed,
the upper display tracks the calibration current
until the trip status signal is generated.

6
Model 710DU Trip/Calibration System
SPECIFICATIONS
Electrical Specifications
Power Supply
24 V dc (nominal) power required
Inputs
2-wire 4–20 mA transmitters or 3-wire 100 V
platinum RTD
Current Drain
Master trip unit is 260 mA; slave trip unit,
calibration unit, and readout assembly are 225 mA
each; and transmitter loop is limited to 100 mA.
Outputs
Independent 24 V dc signals for each trip output and
each gross failure output circuit can drive external
relays (24 V, minimum). Auxiliary 1–5 V dc analog
signals (master trip units only) proportional to each
sensor input can drive external loads (1500 V,
minimum).
Trip Unit Adjustment and Controls
Trip Point
10-turn, screwdriver-slotted, precision wire-wound
potentiometer on faceplate
Trip Reset Differential
Single-turn potentiometer on circuit card
Trip Logic
Switches on circuit card select trip output above or
below trip current level and permit trip status lamp
to be on or off in tripped mode
Gross Failure Limits
Single-turn potentiometers on circuit card for high
and low current levels
Gross Failure Reset
Push-button switch resets gross failure circuit.
Frequency Response
Single-turn potentiometer on circuit card for
4–20 mA master trip unit
Zero and Span
25-turn, screwdriver-slotted, precision metal film
potentiometer on circuit card (RTD master trip unit only)
Linearity
Single-turn potentiometer on circuit card
(RTD master trip unit only)
Indicator LEDs
Trip status and gross failure LED on faceplate
Test Jacks
Signal input and auxiliary analog output voltages
may be read with external meters on master trip
units, and slave input signal on slave trip units.
Calibration Unit Adjustment and Controls
Power
On/off toggle switch for 24 V dc power to calibration
unit and readout assembly
Transient Polarity
Positive/negative toggle switch for transient current
Transient Current
Single-turn, push/pull potentiometer sets and
engages transient calibration current.
Stable Current
10-turn potentiometer adjusts current, which
replaces sensor input to master trip unit
Channel Selector
Dual push/pull and rotary switch selects master trip
unit channel, applies calibration current, and selects
master or slave trip unit for trip current readout.
Digital Display
Readout assembly displays calibration current and
trip current.
Display Reset
A trip current display reset button reverses the
latching logic for the trip current display and trip
status LED so trip current can be read for reversed
trip status logic.
Indication
LED on calibration unit is lighted when system is in
calibration mode. LED on readout assembly is
lighted by trip status signal.
Test Jacks
Signal return, trip status output, and transient
trigger may be monitored for time response
measurements.

Rosemount Nuclear Instruments, Inc.
7
Performance Specifications
Trip Points
Adjustable from 4–20 mA ±0.01 mA;
repeatable within 0.13% for 4–20 mA master trip
(0.20% for slave trip) and 0.75% for RTD master trip
(0.82% for slave trip) of calibrated span for 6 months
under normal conditions; reset differential
adjustable from 0.6 to 7.5% of span, or from 0.6 to
15% of span for the 15% reset differential option
Gross Failure Limits
Adjustable from 0.5–4 mA (low limit) and
19.5–40.5 mA (high limit)
Analog Meter
±3% full-scale accuracy
Auxiliary Analog Output
0–10 V dc, accurate to within 0.15% of span of the
calibrated 1–5 V dc signal under normal conditions
(0.78% of span for RTD master trip); frequency
response adjustable from 0.8–8.0 Hz on 4–20 mA for
master trip units only.
Stable Current
3.50–20.50 mA ±0.005 mA
Transient Current
0.50 to 20.50 mA ±0.05 mA
Digital Readout
Display Accuracy:
00.00–20.00 ±0.01 mA
20.01–30.00 ±0.01 mA
30.01–45.00 ±0.05 mA
Resolution:
0.01 mA
Power Supply Range
22–28 V dc
Physical Specifications
Card File Dimensions
19 in. W 3631/32 in. H 311 in. D
File Space
1.2-in. file centers for up to 12 master or slave trip
units plus a calibration unit; all units have captive
screws for securing to card file
Field Terminals
All connections are made to barrier strips on the rear of
the card file. Screw terminals are sized for #6 spade lugs.
Analog Indication
Master trip units have 13/4-in. vertical meters scaled
in appropriate engineering units.
Paint
Flat black with white letters, baked enamel paint
CARD FILE
The 710DU system card file is designed to
accommodate one plug-in calibration unit plus any
combination of up to 12 interchangeable, plug-in
master and slave trip units. Terminal strips on the rear
of the file are provided for all field wiring and master/
slave interconnections. The file fits a standard 19-in.
relay rack and has mounting provisions for installing a
tamper-proof bar over the set point adjustments on the
trip units. The unit is constructed so that a relay can be
tripped if a card is removed from the card file.
The Model 710DU trip/calibration systems are
furnished with all interconnecting wires between the
calibration unit and the master or slave trip units.
Accessory Extender Cards
Calibration, readout, and trip unit extender cards
are available to make all internal adjustments easily
accessible when frequent alteration of the system
configuration is necessary, or when troubleshooting
is required.
Bench Test Facility
The 710DU bench test facility is for calibration of
readout assemblies, troubleshooting faulty master
and slave trip units, and performing acceptance
tests. This test facility is intended to aid technicians
and is designed to operate from a 115 V ac or
230 V ac, 50–60 Hz power source.

Rosemount Nuclear Instruments, Inc.
12001 Technology Drive
Eden Prairie, MN 55344
Tel (612) 828-8252
Telex 4310012
Fax (612) 828-8280
© 1999 Rosemount Nuclear Instruments, Inc.
http://www.rosemount.com
00813-0100-4471 Rev. AB
¢00813-0100-4471j¤ ™
ORDERING INFORMATION
Model Product Description
710DU Trip/Calibration System for Nuclear Applications, qualified per IEEE Std 323-1974 and IEEE Std 344-1975
Code Option
0
1Standard Unit
15% Reset Differential
Code Assembly Description
TT
TR
TS
Master Trip Unit, 4–20 mA Input
Master Trip Unit, RTD Input
Slave Trip Unit
Code Meter Option
XXXXX Assigned by Rosemount for each Meter Scale Used on TT and TR Assemblies Only
Typical Model Number: 710DU0TR74024
Model Product Description
710DU0 Trip/Calibration System for Nuclear Applications
Code Assembly Description
CF
CL
RA1
BT
BC
B1
B2
ET
EC
ER
Card File
Calibration Unit
Readout Assembly
Blank Panel, Trip Unit
Blank Panel, Calibration Unit
Bench Test Facility (115 Vac Power)
Bench Test Facility (230 Vac Power)
Extender, Trip Unit
Extender, Calibration Unit
Extender, Readout Assembly
Typical Model Number: 710DU0 RA1
Table of contents
Popular Test Equipment manuals by other brands

SIGLENT TECHNOLOGIES
SIGLENT TECHNOLOGIES SDS1202X-E user manual

Megger
Megger MIT221 user manual

Agilent Technologies
Agilent Technologies InfiniiVision 5000 Series Demo guide

Alcolizer
Alcolizer Centurion user manual

Buhler
Buhler GAS 222.31 AMEX Installation and operation instruction

Dräger
Dräger Alcotest 6000 Instructions for use