Sabiana Carisma CRC-ECM Quick start guide

CRC-ECM
Carisma CRT-ECM
CRS-ECM
Fan Coil Units
The Fan Coil Unit with
EC Brushless Electronic Motor
and Inverter Board
TECHNICAL GUIDE
99A4670160 D/06/18
Cert. n° 0545
www.eurovent-certification.com
SABIANA SpA
Società a socio unico
Via Piave 53 - 20011 Corbetta (MI) Italy
T. +39 02 97203 1 r.a. • F. +39 02 9777282
www.sabiana.it
Follow us on
Sabiana app

WM
-
KNX
recessed thermostat
UP
-
KNX power unit
WM
-
KNX
with rectangular plate
WM
-
KNX
with square plate
The KNX bus system is a building automation standard for controlling, managing and monitoring a wide range of
products for:
-
heating, cooling, ventilation
-
lighting
-
alarm systems
-
audio and video systems
-
electricity and gas
Since 2016, Sabiana is a certified member of the KNX association
and the certified products can be added to this system in compliance
with the tests carried out at KNX laboratories.
KNX devices
The Sabiana
WM
-
KNX
room thermostat controls and adjusts the temperature of a room or area in a building. In
combination with one or several
UP
-
KNX
power units, the thermostat is able to control the operation of terminal
units such as fan coils. The appliance consists of an LCD display with adjustable backlight and a sensor for measuring
the room temperature.
WM
-
KNX
is suitable for installation in a recessed wall box.
KNX bus system
• Fan absorption • Water pressure drop • Sound power
• Cooling total emission at the following conditions:
- Water temperature +7°C E.W.T. +12°C L.W.T.
- Entering air temperature +27°C dry bulb +19°C wet bulb
• Cooling sensible emission at the following conditions:
- Water temperature +7°C E.W.T. +12°C L.W.T.
- Entering air temperature +27°C dry bulb +19°C wet bulb
• Heating emission (2 pipe units) at the following conditions:
- Water temperature +45°C E.W.T. +40°C L.W.T.
- Entering air temperature +20°C
• Heating emission (4 pipe units) at the following conditions:
- Water temperature +65°C E.W.T. +55°C L.W.T.
- Entering air temperature +20°C
Carisma CRC-ECM/CRT-ECM/CRS-ECM
Sabiana take part to the Eurovent program of fan coil
performance certification. The official figures are published
in the web site www.eurovent-certification.com.
The tested performances are:
Carisma fan coils combine a beautiful design with very
interesting performances in terms of sound level and
energy consumption.
Carisma ECM models are available in five different
models, for wall and ceiling installation, with casing and
concealed.
All Sabiana fan coils take part to the Eurovent program
of fan coil performance certification.
The ECM range makes use of the excellent experience
gained with the Cassette fan coils with inverter board,
first in the world in production since 2009, and which
have had great success on all markets.
The innovative brushless and sensorless type synchro-
nous electronic motor with permanent magnets, is
controlled by an inverter board designed and developed
in Italy. The board is mounted on the unit, closed to the
motor, without the need to be cooled down by the air
flow.
The air flow rate can be varied in continuous by means
of a 1-10 V signal generated by Sabiana controls or by
independent control systems. The continuous air flow
control improves the acoustic comfort and allows a more
punctual reply to the variation of the thermal loads and
a greater stability of the requested ambient temperature.
The extreme efficiency, also at low speed, makes possible
a great reduction in electric consumption (less than 50%
in comparison to CRC, CRT and CRSO range motor) with
absorption values under normal operating conditions that
do not exceed 16 Watt for CRC−ECM models, do not
exceed 8 Watt for CRT−ECM models and do not exceed
50 Watt for CRS−ECM models on the entire range. The
excellent values of the CRC, CRT and CRSO range in terms
of sound levels have been maintained in all working
conditions, without any resonance phenomenon at any
frequency.
The full compliance with the Electromagnetic Compatibility
Directive and with the other severe Standards in force is certified
by an independent institute.
CONTENTS
• CRC–ECM version
• Construction Page 4
• Models Page 5
• Dimensions, Weight, Water content Page 6
• EUROVENT Certification Page 10
• Operation limits Page 13
• Emission tables Page 14
• Correction factors table Page 24
• Water pressure drop Page 25
• CRT–ECM version
• Construction Page 26
• Models Page 27
• Dimensions, Weight, Water content Page 28
• EUROVENT Certification Page 32
• Operation limits Page 34
• Emission tables Page 35
• Water pressure drop Page 43
• CRS–ECM version
• Construction features Page 44
• Dimensions, Weight, Water content Page 46
• EUROVENT Certification Page 48
• Main performance and technical characteristics Page 50
• Operation limits Page 51
• Emission tables Page 52
• Correction factors tables Page 58
• Water pressure drop Page 60
•
CRC–ECM/CRT–ECM/CRS–ECM version
• Accessories Page 62
•
CRYSTALL
electrostatic filter Page 83
• ECM configuration Page 84
• Electronic controls to be fitted Page 85
• Wall electronic controls Page 85
• Controls and units MB version Page 86
• KNX bus system Page 87
The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right,
whilst maintaining the essential characteristics of the types described and illustrated, to make,
at any time, without the requirement to promptly update this piece of literature, any changes that it considers
useful for the purpose of improvement or for any other manufacturing or commercial requirements.
87
CRC–
ECM
/
CRT–
ECM
/
CRS–
ECM
CRC–ECM
/
CRT–ECM
/
CRS–ECM version
Carisma

3
Carisma
Range includes 3 air flow rates (from 350 to 1450 m3/h), each
equipped with 3 or 4 row coil and with the possibility to add
a 1 or 2 row coil for 4 pipe systems.
It is the most comprehensive range, perfect to meet all
air-conditioning requirements of work environments like
offices, shops, restaurants and hotel rooms featuring
ducted installations with available pressure up to 80 Pa.
CRC–ECM
and
CRT–ECM
version
Plastic outlet grid
in one single piece:
extraordinary
design and strength
CRS–ECM version with high pressure centrifugal fan
Range includes 5 air flow rates (from 95 to 900 m3/h) and 5
models (for wall and ceiling installation, with casing and
concealed), each equipped with 3 row coil and with the
possibility to add a 1 row coil for 4 pipe systems.
It is the most comprehensive range, perfect to meet all
air-conditioning requirements of work environments like
offices, shops, restaurants and hotel rooms.
CRT–ECM version with tangential fan
Range includes 5 air flow rates (from 115 to 1395 m3/h) and
5 models (for wall and ceiling installation, with casing and
concealed), each equipped with 3 or 4 row coil and with
the possibility to add a 1 or 2 row coil for 4 pipe systems.
This is the series with the lowest electrical consumption
in relation to both heat performance as well as working
static performance and is particularly suited to satisfying
the strictest energy consumption needs of class A buildings,
and to ensuring excellent acoustic comfort.
CRC–ECM version with centrifugal fan
Page 44
Page 26
Page 4

4
CRC–ECM
CRC–ECM version Carisma
Outer casing
Made of strong synthetic lateral corners and from galvanized and prepainted front steel panel.
The plastic top grid has fixed louvres and is reversible in order to distribute the air in two different directions.
Standard colours:
• Lateral corners and top grid: Pantone Cool Grey 1C (light grey)
• Frontal panel: RAL 9003 (white)
• Other colours on request.
Inner casing
Made from 1 mm galvanized steel insulated with 3 mm polyolefin (PO)
foam (class M1).
Filter
Polypropylene cellular fabric regenerating filter.
The filter frame of galvanized steel is inserted into special
plastic sliding guides fastened to the internal structure for
easy insertion and removal of the filter.
Filter presence is highlighted by a plastic front cover featuring
the same colour as the top grid.
Fan assembly
The fans have aluminium or plastic blades directly keyed on the motor with double aspiration and they are dynamically
and statically balanced during manufacture in order to have an extremely quiet operation.
Electronic motor
Three phase permanent magnet brushless electronic motor that is controlled with reconstructed current according to
a BLAC sinusoidal wave. The inverter board that controls the motor operation is powered by 230 Volt, single-phase and,
with a switching system, it generates a three-phase frequency modulated, wave form power supply. The electric power
supply required for the machine is therefore single-phase with voltage of 230-240V and frequency of 50
-
60Hz.
Coil
It is manufactured from drawn copper tube and the aluminium fins are mechanically bonded onto the tube by an
expansion process. The coil has two 1/2 inch BSP internal connections and 1/8 inch BSP air vent and drain.
The coil is not suitable for use in corrosive atmosphere or in environments where aluminium may be subject to
corrosion.
The connections are on the left side facing the unit. On request we can deliver the unit with the connections
on the right end side. This operation can also be easily carried out on site during installation.
Condensate collection tray
Made from plastic (ABS UL94 HB) with an “L”-shaped plastic fitted on the inner casing; in the MO
-
MVB and IV
-
IO
model the tray is insulated with 3 mm polyolefin (PO) foam (class M1). The outside diameter of the condensate
discharge pipe is 15mm.
Accessories and Controls
See pages 62
-
85.
Construction

5
CRC–ECM
CRC–ECM version Carisma
100 (min.)
100 (min.)
100
MV
Vertical Casing –Wall Installation
MV
Vertical Casing –Ceiling Installation
MO-MVB
Vertical Casing –Floor Installation
MO-MVB
Horizontal Casing
IV-IO
Vertical Concealed
IV-IO
Horizontal Concealed
Models
NOTE: the MV model can also be installed horizontally
leaving behind a 100 mm gap for air intake.

6
CRC–ECM
CRC–ECM version Carisma
Ø 1/2" F
M
37
O
N
T
Ø 15 ext.
B
H
230
WATER INLET
WATER OUTLET
P
R
S
321
T
H
B
230
W
ATER
OUTLET
WATER INLET
Ø 15 ext.
Ø 1/2" F
71 44 125 133
158 158C
60 60
A
530
A
B
170
158 158
71 44 125 133
C
100
60 60
A
530
630
A
B
170
100
MV
MO-MVB
Dimension, Weight, Water content
Feet (optional)
Coil connections on the left
Heating additional coil (1 or 2 rows)3 or 4 row coils
COIL CONNECTIONS

7
CRC–ECM
CRC–ECM version Carisma
17,2
18,0
18,6
18,0
18,8
22,5
23,7
24,4
23,5
24,7
27,7
29,2
30,1
29,0
30,5
32,1
33,9
35,0
33,6
35,4
35,9
37,7
38,8
37,4
39,2
15,4
16,2
16,8
16,2
17,0
20,2
21,4
22,1
21,2
22,4
24,9
26,4
27,3
26,2
27,7
28,8
30,6
31,7
30,3
32,1
32,2
34,0
35,1
33,7
35,5
2467924679
0,6
0,8
0,2
0,4
0,9
1,3
0,3
0,6
1,6
2,2
0,5
1,0
1,7
2,4
0,5
1,0
1,9
2,8
0,6
1,2
24679
770
225
454
205
145
260
460
185
105
475
55
260
820
985
225
669
205
145
260
460
185
105
475
55
260
1035
1200
225
884
205
145
260
460
185
105
475
55
260
1250
1415
225
1099
205
145
260
460
185
105
475
55
260
1465
1415
255
1099
235
170
270
450
210
110
465
85
290
1465
24679
A
B
C
H
M
N
O
P
R
S
T
V
Z
Model
Rows Rows
3
4
+1
+2
Model
Weight without packagingWeight with packaging
3
3+1
3+2
4
4+1
Model
600
V
Z
PACKAGING
Dimension, Weight, Water content
Weight (kg)
Water content (litres)
Dimension (mm)

8
CRC–ECM
CRC–ECM version Carisma
M
37
O
N
U
Ø 15 ext.
G
H
230
Ø 1/2" F
WATER INLET
WATER OUTLET
P
R
S
321
U
H
G
230
Ø 15 ext.
Ø 1/2" F
W
ATER
OUTLET
WATER INLET
133 125
44
71
153
17
D
12 12
G
H
Ø 15 ext.
230
119*
E*
F150 10
153
17 119*
71 44 125 133
F10
D
E
*
12 12
511
D
22 22
29
12
G
H
Ø 15 ext.
230
100
12
IV
-
IO Vertical Installation
IV
-
IO Horizontal Installation
Dimension, Weight, Water content
Supply frame dimension = E x119 mm
*
Supply frame dimension = E x119 mm
*
Coil connections on the left
Heating additional coil (1 or 2 rows)3 or 4 row coils
COIL CONNECTIONS
Auxiliary condensate tray (optional)

9
CRC–ECM
CRC–ECM version Carisma
13,6
14,4
15,0
14,4
15,2
18,1
19,3
20,0
19,1
20,3
22,8
24,3
25,2
24,1
25,6
27,0
28,8
29,9
28,5
30,3
30,4
32,2
33,3
31,9
33,7
11,8
12,6
13,2
12,6
13,4
16,3
17,5
18,2
17,3
18,5
20,5
22,0
22,9
21,8
23,3
24,2
26,0
27,1
25,7
27,5
27,3
29,1
30,2
28,8
30,6
2467924679
600
X
Y
PACKAGING
Dimension, Weight, Water content
24679
474
430
454
218
205
145
260
460
185
105
475
65
260
820
689
645
669
218
205
145
260
460
185
105
475
65
260
820
904
860
884
218
205
145
260
460
185
105
475
65
260
1035
1119
1075
1099
218
205
145
260
460
185
105
475
65
260
1250
1119
1075
1099
248
235
170
270
450
210
110
465
95
290
1250
D
E
F
G
H
M
N
O
P
R
S
U
X
Y
Model
0,6
0,8
0,2
0,4
0,9
1,3
0,3
0,6
1,6
2,2
0,5
1,0
1,7
2,4
0,5
1,0
1,9
2,8
0,6
1,2
24679
Rows
3
4
+1
+2
Model
Rows
Weight without packagingWeight with packaging
3
3+1
3+2
4
4+1
Model
Weight (kg)
Water content (litres)
Dimension (mm)

10
CRC–ECM
CRC–ECM version Carisma
120
0,73
0,55
0,77
2,2
1,6
7,0
30
21
1 (E)
MIN
170
0,97
0,74
1,04
3,6
2,7
9,0
36
27
3
MED
220
1,18
0,92
1,29
5,1
3,9
11,0
41
32
5 (E)
270
1,37
1,09
1,52
6,7
5,2
15,0
47
38
7,5
MAX
330
1,59
1,28
1,80
8,6
7,0
21,0
51
42
10 (E)
210
1,41
1,03
1,42
7,9
6,6
6,0
30
21
1 (E)
MIN
280
1,80
1,33
1,84
12,0
10,4
9,0
36
27
3
MED
350
2,18
1,64
2,26
17,0
14,9
12,0
42
33
5 (E)
430
2,57
1,95
2,69
22,6
20,4
17,0
47
38
7,5
MAX
515
2,95
2,26
3,14
28,9
26,7
25,0
51
42
10 (E)
305
1,96
1,46
1,96
5,5
4,5
7,0
33
24
1 (E)
MIN
395
2,44
1,83
2,46
8,0
6,8
10,0
38
29
3
MED
495
2,93
2,22
3,00
11,1
9,6
15,0
44
35
5 (E)
610
3,44
2,64
3,55
14,8
12,9
22,0
49
40
7,5
MAX
735
3,96
3,08
4,14
19,0
17,0
32,0
54
45
10 (E)
400
2,60
1,92
2,56
10,5
8,5
9,0
37
28
1 (E)
MIN
500
3,13
2,33
3,13
14,5
12,1
13,0
43
34
3
MED
610
3,68
2,77
3,72
19,4
16,4
18,5
48
39
5 (E)
755
4,36
3,32
4,43
26,1
22,2
28,5
53
44
7,5
MAX
890
4,94
3,80
5,08
32,6
28,3
41,0
57
48
10 (E)
605
3,45
2,63
3,74
8,9
7,3
16,0
44
35
1 (E)
MIN
785
4,22
3,28
4,65
12,7
10,7
25,0
50
41
3
MED
945
4,82
3,79
5,41
16,1
14,0
41,0
55
46
5 (E)
1175
5,60
4,49
6,46
21,1
19,1
65,0
60
51
7,5
MAX
1395
6,26
5,10
7,38
25,9
24,2
99,0
64
55
10 (E)
m3/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
(E) = Eurovent certified performance.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3room and a reverberation time of 0.5 sec.
CRC−ECM 63CRC−ECM 43CRC−ECM 23
Model
EUROVENT Certification
m3/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 93CRC−ECM 73
Model
CRC−
eCM units with 3 Row Coil
COOLING
Entering air temperature + 27°C d.b. + 19°C w.b.
Water temperature + 7°C E.W.T. + 12°C L.W.T.
HEATING
Entering air temperature + 20°C
Water temperature + 45°C E.W.T. + 40°C L.W.T.
2 pipe units.
The following standard rating conditions are used:
www.eurovent-certification.com

11
CRC–ECM
CRC–ECM version Carisma
115
0,77
0,56
0,78
3,2
2,6
7,0
30
21
1 (E)
MIN
160
1,06
0,78
1,08
5,5
4,7
8,8
36
27
3
MED
210
1,32
0,98
1,37
8,0
7,1
11,0
41
32
5 (E)
260
1,57
1,19
1,65
11,0
9,9
14,6
47
38
7,5
MAX
325
1,86
1,42
1,98
14,8
13,6
21,0
51
42
10 (E)
200
1,43
1,03
1,42
4,0
3,1
6,0
30
21
1 (E)
MIN
265
1,83
1,34
1,83
6,1
4,9
9,0
36
27
3
MED
340
2,27
1,67
2,30
8,9
7,3
12,0
42
33
5 (E)
415
2,71
2,02
2,77
12,3
10,2
17,0
47
38
7,5
MAX
505
3,17
2,39
3,32
16,1
13,7
25,0
51
42
10 (E)
290
2,05
1,48
2,02
8,2
6,6
7,0
33
24
1 (E)
MIN
375
2,59
1,89
2,59
12,4
10,3
10,0
38
29
3
MED
475
3,19
2,34
3,23
17,8
15,1
15,0
44
35
5 (E)
590
3,84
2,84
3,93
24,8
21,4
22,0
49
40
7,5
MAX
720
4,51
3,38
4,68
33,0
29,1
32,0
54
45
10 (E)
380
2,61
1,90
2,57
7,3
5,9
9,0
37
28
1 (E)
MIN
475
3,20
2,34
3,17
10,5
8,6
13,0
43
34
3
MED
585
3,82
2,82
3,84
14,3
12,0
18,5
48
39
5 (E)
735
4,61
3,44
4,66
20,0
16,9
28,5
53
44
7,5
MAX
875
5,30
3,99
5,43
25,6
22,0
41,0
57
48
10 (E)
575
3,59
2,69
3,76
6,3
5,6
16,0
44
35
1 (E)
MIN
755
4,49
3,40
4,81
9,3
8,7
25,0
50
41
3
MED
910
5,21
3,99
5,63
12,1
11,4
41,0
55
46
5 (E)
1145
6,18
4,81
6,84
16,4
16,1
65,0
60
51
7,5
MAX
1365
7,04
5,53
7,93
20,8
20,9
99,0
64
55
10 (E)
(E) = Eurovent certified performance.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3room and a reverberation time of 0.5 sec.
EUROVENT Certification
m3/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 64CRC−ECM 44CRC−ECM 24
Model
m3/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 94CRC−ECM 74
Model
CRC−
eCM units with 4 Row Coil
COOLING
Entering air temperature + 27°C d.b. + 19°C w.b.
Water temperature + 7°C E.W.T. + 12°C L.W.T.
HEATING
Entering air temperature + 20°C
Water temperature + 45°C E.W.T. + 40°C L.W.T.
2 pipe units.
The following standard rating conditions are used:
www.eurovent-certification.com

12
CRC–ECM
CRC–ECM version Carisma
120
0,73
0,55
0,71
2,3
1,0
7,0
30
21
1 (E)
MIN
170
0,97
0,74
0,91
3,8
1,6
9,0
36
27
3
MED
220
1,18
0,92
1,08
5,4
2,1
11,0
41
32
5 (E)
270
1,37
1,09
1,24
7,2
2,7
14,5
47
38
7,5
MAX
330
1,59
1,28
1,43
9,4
3,5
21,0
51
42
10 (E)
210
1,41
1,03
1,29
7,3
3,6
6,0
30
21
1 (E)
MIN
280
1,80
1,33
1,57
11,5
5,2
9,0
36
27
3
MED
350
2,18
1,64
1,85
16,0
6,9
12,0
42
33
5 (E)
430
2,57
1,95
2,13
21,6
8,8
17,0
47
38
7,5
MAX
515
2,95
2,26
2,41
28,1
11,0
25,0
51
42
10 (E)
305
1,96
1,46
1,76
6,4
1,2
7,0
33
24
1 (E)
MIN
395
2,44
1,83
2,10
9,6
1,7
10,0
38
29
3
MED
495
2,93
2,22
2,45
13,2
2,2
15,0
44
35
5 (E)
610
3,44
2,64
2,83
17,7
2,9
22,0
49
40
7,5
MAX
735
3,96
3,08
3,22
23,3
3,6
32,0
54
45
10 (E)
400
2,60
1,92
2,33
9,7
2,4
9,0
37
28
1 (E)
MIN
500
3,13
2,33
2,72
13,8
3,1
13,0
43
34
3
MED
610
3,68
2,77
3,12
18,4
4,0
18,5
48
39
5 (E)
755
4,36
3,32
3,63
24,8
5,2
28,5
53
44
7,5
MAX
890
4,94
3,80
4,06
31,8
6,3
41,0
57
48
10 (E)
605
3,45
2,63
2,99
8,9
3,7
16,0
44
35
1 (E)
MIN
785
4,22
3,28
3,58
12,7
5,1
25,0
50
41
3
MED
945
4,82
3,79
4,05
16,1
6,3
41,0
55
46
5 (E)
1175
5,60
4,49
4,69
21,1
8,2
65,0
60
51
7,5
MAX
1395
6,26
5,10
5,24
25,9
9,9
99,0
64
55
10 (E)
EUROVENT Certification
(E) = Eurovent certified performance.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3room and a reverberation time of 0.5 sec.
m3/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 63+1CRC−ECM 43+1CRC−ECM 23+1
Model
m3/h
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
Inverter power
Speed
Air flow
Cooling total emission (E)
Cooling sensible emission (E)
Heating (E)
Dp Cooling (E)
Dp Heating (E)
Fan (E)
Sound power (E) Lw
Sound pressure (*) Lp
CRC−ECM 93+1CRC−ECM 73+1
Model
CRC−
eCM units with 1 Row additional Coil
4 pipe units.
The following standard rating conditions are used:
www.eurovent-certification.com
COOLING
Entering air temperature + 27°C d.b. + 19°C w.b.
Water temperature + 7°C E.W.T. + 12°C L.W.T.
HEATING
Entering air temperature + 20°C
Water temperature + 65°C E.W.T. + 55°C L.W.T.

13
CRC–ECM
CRC–ECM version Carisma
Lowest
Highest
Model
50
250
100
350
100
500
100
650
100
750
CRC−ECM 2 CRC−ECM 4 CRC−ECM 6 CRC−ECM 7 CRC−ECM 9
Lowest
Highest
Model
100
500
100
750
150
1000
150
1500
200
2000
CRC−ECM 23 CRC−ECM 43 CRC−ECM 63 CRC−ECM 73 CRC−ECM 93
Lowest
Highest
Model
100
750
150
1000
150
1500
200
2000
300
2250
CRC−ECM 24 CRC−ECM 44 CRC−ECM 64 CRC−ECM 74 CRC−ECM 94
Lowest
Highest
Model
50
250
50
350
100
500
100
650
100
750
CRC−ECM 2 CRC−ECM 4 CRC−ECM 6 CRC−ECM 7 CRC−ECM 9
Highest water inlet temperature...............................+ 85 °C
Lowest water inlet temperature................................+ 5 °C
for entering water temperatures below + 5°C, contact “SABIANA” technical department
Highest working pressure........................................1000 kPa (10 bars)
Note: For MO model the maximum installation height is 2,8 m.
On heating it must be payed attention to rooms where the floor temperature
is particularly low (for example less than 5°C).
In this situation the floor can cool the lower layer of air to a level that can stop
the uniform diffusion of the hot air coming from the unit.
Motor electrical data (max. absorption)
Water flow limits for 3 row coil (l/h)
Water flow limits for 4 row coil (l/h)
Water flow limits for 1 row additional coil (l/h)
Water flow limits for 2 row additional coil (l/h)
Operation limits
W
A
230/1
50Hz
Model
CRC−ECM 2 CRC−ECM 4 CRC−ECM 6 CRC−ECM 7 CRC−ECM 9
21,0
0,18
25,0
0,22
32,0
0,28
41,0
0,34
99,0
0,81

Qv
m3/h
Vdc
Model
eCM
Pc
Ps
Pc
Ps
48%
R.H. WT:
46%
14
Legend
WT = Water temperature
Pc = Cooling total emission
Ps = Cooling sensible emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
330
270
220
170
120
515
430
350
280
210
735
610
495
395
305
890
755
610
500
400
1395
1175
945
785
605
CRC
23
CRC
43
CRC
63
CRC
73
CRC
93
CRC–ECM
CRC–ECM version Carisma
WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C
1,72
1,49
1,27
1,04
0,79
3,17
2,76
2,35
1,93
1,52
4,26
3,70
3,15
2,62
2,12
5,31
4,69
3,96
3,37
2,79
6,76
6,05
5,19
4,55
3,72
1,27
1,08
0,91
0,74
0,55
2,25
1,94
1,63
1,33
1,03
3,07
2,63
2,21
1,83
1,46
3,79
3,31
2,76
2,33
1,92
5,06
4,46
3,77
3,27
2,63
299
258
220
181
137
550
478
406
334
262
738
641
544
453
365
921
812
684
581
482
1180
1051
900
787
642
7,9
6,1
4,6
3,3
2,0
32,9
25,8
19,3
13,7
8,9
21,6
16,8
12,6
9,1
6,3
37,1
29,7
22,0
16,5
11,9
30,3
24,7
18,8
14,8
10,4
1,53
1,32
1,13
0,93
0,71
2,84
2,48
2,11
1,74
1,37
3,81
3,32
2,82
2,36
1,90
4,04
4,21
3,56
3,03
2,52
6,01
5,39
4,64
4,07
3,33
1,19
1,02
0,86
0,69
0,52
2,11
1,82
1,53
1,25
0,97
2,89
2,48
2,08
1,71
1,37
3,56
3,11
2,60
2,19
1,80
4,76
4,20
3,55
3,07
2,47
266
230
196
162
123
493
429
365
300
236
661
574
488
407
329
702
729
615
523
434
1051
938
804
704
575
6,4
4,9
3,7
2,7
1,6
27,0
21,2
15,9
11,3
7,4
17,6
13,8
10,3
7,5
5,2
30,4
24,4
18,1
13,6
9,8
24,7
20,2
15,4
12,2
8,6
1,12
0,98
0,84
0,70
0,53
2,14
1,88
1,60
1,33
1,05
2,86
2,50
2,14
1,79
1,45
3,60
3,20
2,71
2,32
1,93
4,43
3,99
3,46
3,05
2,51
1,04
0,88
0,74
0,60
0,45
1,84
1,59
1,33
1,08
0,84
2,52
2,16
1,81
1,49
1,19
3,11
2,71
2,26
1,90
1,57
4,17
3,67
3,10
2,68
2,15
196
171
147
121
93
373
326
278
229
181
498
434
370
310
251
627
555
470
400
333
780
698
602
529
434
3,7
2,9
2,2
1,6
1,0
16,3
12,8
9,7
6,9
4,6
10,6
8,3
6,3
4,6
3,2
18,5
14,9
11,1
8,4
6,1
14,6
12,0
9,3
7,4
5,2
0,90
0,77
0,66
0,53
0,39
1,62
1,40
1,18
0,96
0,74
2,21
1,90
1,59
1,32
1,05
2,74
2,39
1,99
1,69
1,38
3,63
3,21
2,71
2,35
1,90
0,90
0,77
0,66
0,53
0,39
1,62
1,40
1,18
0,96
0,74
2,21
1,90
1,59
1,32
1,05
2,74
2,39
1,99
1,69
1,38
3,63
3,21
2,71
2,35
1,90
159
135
115
93
69
283
243
204
167
129
386
331
277
229
182
478
416
346
292
240
642
563
474
409
330
2,5
1,9
1,4
1,0
0,6
9,9
7,6
5,6
3,9
2,5
6,7
5,1
3,7
2,7
1,8
11,3
8,8
6,4
4,8
3,4
10,4
8,2
6,1
4,6
3,1
Cooling emission of 3 row coil
Entering air temperature: 27°C –R.H.: 50%
7/12°C 8/13°C 10/15°C 12/17°C
0,95
1,00
0,90
1,00
0,94
1,00
0,88
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
Correction factors for different R.H.

Pc
Ps
Pc
Ps
48%
R.H. WT:
46%
15
Qv
m3/h
Vdc
Model
eCM kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
330
270
220
170
120
515
430
350
280
210
735
610
495
395
305
890
755
610
500
400
1395
1175
945
785
605
CRC
23
CRC
43
CRC
63
CRC
73
CRC
93
Legend
WT = Water temperature
Pc = Cooling total emission
Ps = Cooling sensible emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow
CRC–ECM
CRC–ECM version Carisma
WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C
1,52
1,32
1,13
0,93
0,70
2,82
2,46
2,10
1,73
1,36
3,79
3,30
2,81
2,34
1,89
4,74
4,19
3,54
3,01
2,50
6,00
5,37
4,61
4,05
3,31
1,19
1,02
0,86
0,70
0,52
2,12
1,83
1,54
1,25
0,97
2,89
2,48
2,08
1,72
1,37
3,57
3,12
2,60
2,19
1,80
4,77
4,21
3,56
3,08
2,48
265
229
195
161
122
490
426
362
298
234
658
571
485
404
326
822
725
611
520
431
1048
934
801
700
572
6,4
4,9
3,7
2,7
1,6
26,9
21,1
15,8
11,2
7,3
17,6
13,7
10,3
7,5
5,1
30,4
24,3
18,0
13,6
9,8
24,5
20,0
15,3
12,1
8,5
1,33
1,15
0,99
0,82
0,62
2,49
2,18
1,86
1,53
1,20
3,34
2,91
2,48
2,07
1,68
4,19
3,70
3,13
2,67
2,22
5,25
4,71
4,06
3,56
2,92
1,12
0,95
0,80
0,65
0,48
1,98
1,71
1,44
1,17
0,91
2,71
2,32
1,95
1,61
1,28
3,34
2,92
2,53
2,05
1,69
4,47
3,94
3,33
2,88
2,32
232
201
172
142
108
433
377
323
265
208
580
504
429
358
289
727
642
542
462
383
920
821
705
617
505
5,0
3,9
3,0
2,1
1,3
21,5
16,9
12,7
9,0
5,9
14,0
11,0
8,2
6,0
4,1
24,3
19,5
14,5
10,9
7,9
19,5
16,0
12,2
9,7
6,8
0,99
0,84
0,69
0,57
0,44
1,78
1,57
1,34
1,11
0,88
2,37
2,08
1,78
1,50
1,22
3,00
2,67
2,27
1,95
1,63
3,96
3,50
2,96
2,52
2,08
0,99
0,84
0,69
0,56
0,41
1,70
1,47
1,24
1,01
0,78
2,33
2,00
1,68
1,38
1,10
2,88
2,51
2,10
1,77
1,45
3,96
3,50
2,96
2,48
1,99
173
147
121
100
77
311
272
233
193
153
413
361
309
260
211
523
464
394
337
281
699
613
515
438
361
3,0
2,2
1,6
1,1
0,7
11,8
9,4
7,1
5,1
3,4
7,6
6,0
4,6
3,4
2,3
13,4
10,9
8,2
6,2
4,5
12,0
9,6
7,0
5,3
3,7
0,82
0,70
0,60
0,48
0,36
1,48
1,28
1,08
0,88
0,68
2,02
1,74
1,46
1,21
0,96
2,50
2,18
1,82
1,54
1,27
3,30
2,92
2,47
2,15
1,74
0,82
0,70
0,60
0,48
0,36
1,48
1,28
1,08
0,88
0,68
2,02
1,74
1,46
1,21
0,96
2,50
2,18
1,82
1,54
1,27
3,30
2,92
2,47
2,15
1,74
145
123
105
85
63
259
223
187
153
118
353
302
253
209
167
437
381
317
268
220
585
513
432
373
302
2,1
1,6
1,2
0,8
0,5
8,5
6,5
4,8
3,3
2,1
5,7
4,3
3,2
2,3
1,5
9,7
7,6
5,5
4,1
2,9
8,8
7,0
5,1
3,9
2,6
Cooling emission of 3 row coil
Entering air temperature: 26°C –R.H.: 50%
7/12°C 8/13°C 10/15°C 12/17°C
0,95
1,00
0,90
1,00
0,94
1,00
0,88
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
Correction factors for different R.H.

Qv
m3/h
Vdc
Model
eCM
Pc
Ps
Pc
Ps
48%
R.H. WT:
46%
16
Legend
WT = Water temperature
Pc = Cooling total emission
Ps = Cooling sensible emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
330
270
220
170
120
515
430
350
280
210
735
610
495
395
305
890
755
610
500
400
1395
1175
945
785
605
CRC
23
CRC
43
CRC
63
CRC
73
CRC
93
CRC–ECM
CRC–ECM version Carisma
Cooling emission of 3 row coil
Entering air temperature: 25°C –R.H.: 50%
7/12°C 8/13°C 10/15°C 12/17°C
0,95
1,00
0,90
1,00
0,94
1,00
0,88
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
Correction factors for different R.H.
WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C
1,33
1,15
0,99
0,81
0,62
2,49
2,17
1,85
1,52
1,20
3,34
2,90
2,47
2,07
1,67
4,18
3,69
3,12
2,66
2,21
5,25
4,70
4,05
3,56
2,91
1,12
0,96
0,80
0,65
0,48
1,99
1,71
1,44
1,17
0,91
2,71
2,33
1,96
1,61
1,28
3,35
2,93
2,44
2,06
1,69
4,48
3,95
3,33
2,89
2,32
232
200
171
141
108
432
376
320
264
207
579
503
428
357
288
726
640
541
460
382
920
820
703
616
503
5,0
3,9
3,0
2,1
1,3
21,6
16,9
12,7
9,0
5,9
14,1
11,0
8,3
6,0
4,1
24,4
19,6
14,5
10,9
7,9
19,5
15,9
12,2
9,6
6,8
1,13
0,99
0,85
0,70
0,53
2,15
1,88
1,61
1,33
1,05
2,88
2,51
2,14
1,80
1,45
3,63
3,21
2,72
2,32
1,93
4,49
4,04
3,49
3,07
2,52
1,04
0,89
0,75
0,60
0,45
1,85
1,59
1,34
1,09
0,84
2,53
2,17
1,82
1,50
1,19
3,12
2,73
2,27
1,92
1,57
4,18
3,68
3,11
2,69
2,16
198
172
147
122
93
375
327
278
230
181
501
436
371
310
251
631
557
471
401
334
789
706
607
532
436
3,8
3,0
2,3
1,6
1,0
16,7
13,1
9,9
7,1
4,6
10,8
8,5
6,4
4,7
3,2
18,9
15,2
11,3
8,5
6,2
14,9
12,2
9,4
7,5
5,2
0,90
0,77
0,66
0,53
0,39
1,63
1,40
1,18
0,97
0,75
2,22
1,90
1,60
1,33
1,06
2,74
2,40
2,00
1,69
1,33
3,63
3,21
2,72
2,36
1,91
0,90
0,78
0,66
0,53
0,39
1,63
1,40
1,18
0,97
0,74
2,22
1,91
1,60
1,33
1,05
2,74
2,40
2,00
1,70
1,39
3,63
3,22
2,72
2,36
1,90
159
135
115
93
69
284
244
205
168
130
387
331
277
230
183
479
417
347
293
230
642
563
474
409
331
2,5
1,9
1,4
1,0
0,6
10,1
7,7
5,7
4,0
2,5
6,8
5,2
3,8
2,7
1,8
11,5
9,0
6,5
4,9
3,4
10,4
8,2
6,1
4,7
3,1
0,74
0,63
0,54
0,44
0,32
1,34
1,16
0,97
0,80
0,62
1,82
1,57
1,32
1,10
0,87
2,26
1,98
1,65
1,40
1,15
2,97
2,63
2,23
1,94
1,57
0,74
0,63
0,54
0,44
0,32
1,34
1,16
0,97
0,80
0,62
1,82
1,57
1,32
1,10
0,87
2,26
1,98
1,65
1,40
1,15
2,97
2,63
2,23
1,94
1,57
131
111
94
77
57
235
202
170
139
108
319
274
229
190
151
396
345
287
243
200
528
464
391
337
273
1,8
1,3
1,0
0,7
0,4
7,1
5,5
4,0
2,8
1,8
4,8
3,6
2,7
1,9
1,3
8,1
6,4
4,6
3,4
2,4
7,4
5,8
4,3
3,2
2,1

Pc
Ps
Pc
Ps
48%
R.H. WT:
46%
17
Qv
m3/h
Vdc
Model
eCM kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
325
260
210
160
115
505
415
340
265
200
720
590
475
375
290
875
735
585
475
380
1365
1145
910
755
575
CRC
24
CRC
44
CRC
64
CRC
74
CRC
94
Legend
WT = Water temperature
Pc = Cooling total emission
Ps = Cooling sensible emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow
CRC–ECM
CRC–ECM version Carisma
Cooling emission of 4 row coil
Entering air temperature: 27°C –R.H.: 50%
7/12°C 8/13°C 10/15°C 12/17°C
0,95
1,00
0,90
1,00
0,94
1,00
0,88
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
Correction factors for different R.H.
WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C
2,00
1,69
1,42
1,14
0,84
3,42
2,92
2,44
1,97
1,54
4,85
4,12
3,42
2,79
2,20
5,70
4,95
4,11
3,43
2,81
7,60
6,68
5,61
4,84
3,87
1,42
1,18
0,98
0,78
0,57
2,38
2,02
1,67
1,34
1,04
3,36
2,84
2,33
1,89
1,48
3,98
3,43
2,82
2,34
1,90
5,50
4,79
3,97
3,40
2,69
348
294
245
197
145
592
506
421
340
266
839
713
590
481
379
987
857
710
593
484
1324
1160
972
837
669
16,9
12,5
9,1
6,2
3,6
18,5
14,0
10,1
7,0
4,5
37,4
28,1
20,2
14,1
9,2
29,1
22,7
16,3
11,9
8,3
23,7
18,8
13,8
10,6
7,1
1,79
1,52
1,27
1,02
0,75
3,06
2,63
2,19
1,77
1,39
4,36
3,71
3,08
2,52
1,99
5,12
4,46
3,70
3,10
2,53
6,77
5,96
5,02
4,34
3,48
1,33
1,11
0,92
0,73
0,53
2,23
1,89
1,56
1,25
0,97
3,16
2,67
2,19
1,78
1,39
3,74
3,23
2,65
2,20
1,79
5,17
4,50
3,73
3,19
2,52
312
264
220
178
131
531
454
379
307
240
755
642
533
434
343
888
771
639
535
437
1182
1037
871
750
601
13,8
10,3
7,5
5,1
3,0
15,2
11,5
8,4
5,8
3,7
30,9
23,2
16,7
11,7
7,7
24,0
18,7
13,5
9,8
6,9
19,3
15,3
11,3
8,7
5,9
1,35
1,15
0,96
0,78
0,58
2,32
2,00
1,67
1,36
1,07
3,32
2,84
2,37
1,94
1,54
3,90
3,40
2,83
2,38
1,95
5,04
4,46
3,77
3,27
2,64
1,16
0,97
0,80
0,64
0,46
1,94
1,64
1,36
1,09
0,84
2,75
2,32
1,91
1,54
1,21
3,26
2,81
2,30
1,91
1,55
4,51
3,91
3,24
2,77
2,19
235
200
168
136
100
403
346
290
235
185
577
492
409
335
265
677
590
491
412
337
883
778
656
567
456
8,3
6,2
4,6
3,1
1,9
9,2
7,0
5,1
3,6
2,3
19,0
14,3
10,4
7,3
4,8
14,7
11,5
8,3
6,1
4,3
11,4
9,1
6,8
5,2
3,6
1,02
0,85
0,71
0,56
0,41
1,71
1,45
1,20
0,96
0,75
2,43
2,05
1,69
1,36
1,07
2,87
2,47
2,04
1,69
1,37
3,94
3,43
2,85
2,45
1,93
1,02
0,85
0,71
0,56
0,41
1,71
1,45
1,20
0,96
0,75
2,43
2,05
1,69
1,36
1,07
2,87
2,47
2,04
1,69
1,37
3,94
3,43
2,85
2,45
1,93
179
149
123
98
71
299
253
208
167
129
423
356
293
236
184
501
431
354
293
237
695
602
497
426
335
5,0
3,7
2,6
1,8
1,0
5,4
4,0
2,8
1,9
1,2
10,8
8,0
5,7
3,9
2,5
8,5
6,5
4,6
3,3
2,3
7,4
5,7
4,1
3,1
2,0

Qv
m3/h
Vdc
Model
eCM
Pc
Ps
Pc
Ps
48%
R.H. WT:
46%
18
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
325
260
210
160
115
505
415
340
265
200
720
590
475
375
290
875
735
585
475
380
1365
1145
910
755
575
CRC
24
CRC
44
CRC
64
CRC
74
CRC
94
Legend
WT = Water temperature
Pc = Cooling total emission
Ps = Cooling sensible emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow
CRC–ECM
CRC–ECM version Carisma
Cooling emission of 4 row coil
Entering air temperature: 26°C –R.H.: 50%
7/12°C 8/13°C 10/15°C 12/17°C
0,95
1,00
0,90
1,00
0,94
1,00
0,88
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
Correction factors for different R.H.
WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C
1,78
1,51
1,26
1,02
0,75
3,05
2,61
2,18
1,76
1,38
4,33
3,69
3,06
2,50
1,97
5,09
4,43
3,67
3,08
2,51
6,74
5,93
4,99
4,31
3,45
1,33
1,12
0,92
0,74
0,53
2,24
1,90
1,57
1,26
0,98
3,17
2,67
2,20
1,78
1,40
3,75
3,23
2,66
2,21
1,79
5,18
4,50
3,74
3,98
2,53
310
262
219
176
130
528
452
376
304
238
750
638
529
431
340
883
766
635
531
434
1177
1031
866
745
597
13,8
10,2
7,5
5,1
3,0
15,1
11,5
8,3
5,7
3,7
30,8
23,1
16,6
11,6
7,6
23,9
18,6
13,4
9,8
6,8
19,3
15,3
11,2
8,6
5,8
1,57
1,33
1,12
0,90
0,66
2,69
2,31
1,93
1,56
1,23
3,84
3,27
2,72
2,22
1,76
4,51
3,93
3,26
2,74
2,24
5,92
5,22
4,40
3,80
3,05
1,25
1,04
0,86
0,69
0,50
2,09
1,77
1,47
1,17
0,91
2,96
2,50
2,06
1,66
1,30
3,51
3,02
2,48
2,06
1,67
4,85
4,21
3,50
2,99
2,36
273
232
194
157
115
467
400
334
271
212
666
567
470
384
304
782
680
565
473
387
1035
908
764
659
528
11,0
8,2
6,0
4,1
2,4
12,1
9,2
6,7
4,6
3,0
24,7
18,6
13,4
9,4
6,2
19,2
15,0
10,8
7,9
5,6
15,3
12,1
8,9
6,9
4,7
1,12
0,95
0,81
0,65
0,49
1,94
1,67
1,41
1,14
0,90
2,79
2,39
2,00
1,64
1,30
3,27
2,86
2,39
2,01
1,65
4,30
3,67
3,12
2,72
2,20
1,07
0,89
0,74
0,59
0,43
1,79
1,52
1,26
1,01
0,78
2,55
2,15
1,77
1,43
1,12
3,02
2,60
2,13
1,77
1,44
4,30
3,62
3,00
2,56
2,02
195
166
140
114
85
338
291
244
198
156
486
415
346
283
225
569
497
414
348
286
757
643
544
472
382
6,0
4,5
3,3
2,3
1,4
6,8
5,2
3,8
2,6
1,7
14,0
10,6
7,7
5,4
3,6
10,8
8,5
6,2
4,5
3,2
8,7
6,5
4,9
3,8
2,6
0,93
0,78
0,65
0,51
0,37
1,57
1,33
1,10
0,88
0,68
2,22
1,87
1,55
1,25
0,98
2,63
2,26
1,87
1,55
1,26
3,59
3,13
2,60
2,24
1,77
0,93
0,78
0,65
0,51
0,37
1,57
1,33
1,10
0,88
0,68
2,22
1,87
1,55
1,25
0,98
2,63
2,26
1,87
1,55
1,26
3,59
3,13
2,60
2,24
1,77
163
136
113
90
65
274
232
191
153
119
388
326
268
217
169
459
394
325
269
217
635
549
454
390
307
4,3
3,1
2,3
1,5
0,9
4,6
3,4
2,4
1,7
1,1
9,3
6,9
4,9
3,3
2,2
7,3
5,6
4,0
2,8
2,0
6,3
4,9
3,5
2,7
1,7

Pc
Ps
Pc
Ps
48%
R.H. WT:
46%
19
Qv
m3/h
Vdc
Model
eCM kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
kW kW l/h kPa
Pc Ps Qw
Dp(c)
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
325
260
210
160
115
505
415
340
265
200
720
590
475
375
290
875
735
585
475
380
1365
1145
910
755
575
CRC
24
CRC
44
CRC
64
CRC
74
CRC
94
Legend
WT = Water temperature
Pc = Cooling total emission
Ps = Cooling sensible emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow
CRC–ECM
CRC–ECM version Carisma
Cooling emission of 4 row coil
Entering air temperature: 25°C –R.H.: 50%
7/12°C 8/13°C 10/15°C 12/17°C
0,95
1,00
0,90
1,00
0,94
1,00
0,88
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
Correction factors for different R.H.
WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C
1,57
1,33
1,11
0,90
0,66
2,68
2,30
1,92
1,56
1,22
3,83
3,26
2,71
2,21
1,75
4,50
3,91
3,25
2,72
2,23
5,91
5,20
4,39
3,79
3,04
1,25
1,04
0,86
0,69
0,50
2,10
1,78
1,47
1,18
0,92
2,97
2,51
2,06
1,67
1,31
3,52
3,03
2,49
2,07
1,68
4,86
4,22
3,50
2,99
2,37
273
231
193
156
115
466
399
333
269
211
664
565
469
382
302
780
678
562
471
385
1033
906
762
657
526
11,0
8,2
6,0
4,1
2,4
12,1
9,2
6,7
4,6
3,0
24,8
18,6
13,4
9,4
6,2
19,2
15,0
10,8
7,9
5,5
15,3
12,2
9,0
6,9
4,7
1,35
1,15
0,97
0,78
0,58
2,33
2,00
1,68
1,36
1,07
3,33
2,84
2,37
1,94
1,53
3,91
3,41
2,84
2,38
1,95
5,08
4,49
3,79
3,28
2,64
1,16
0,97
0,80
0,64
0,46
1,95
1,65
1,37
1,09
0,85
2,77
2,33
1,92
1,55
1,12
3,27
2,82
2,32
1,92
1,56
4,52
3,93
3,26
2,78
2,20
236
200
168
136
100
405
347
290
235
185
578
493
410
335
265
679
591
491
412
337
891
783
659
569
457
8,5
6,3
4,6
3,2
1,9
9,4
7,2
5,2
3,6
2,4
19,3
14,6
10,5
7,4
4,9
15,0
11,7
8,5
6,2
4,4
11,7
9,3
6,9
5,3
3,6
1,02
0,85
0,71
0,56
0,39
1,72
1,46
1,21
0,92
0,73
2,44
2,05
1,69
1,33
1,06
2,88
2,48
2,05
1,62
1,34
3,95
3,44
2,86
2,46
1,94
1,02
0,85
0,71
0,56
0,39
1,72
1,46
1,21
0,92
0,71
2,44
2,05
1,69
1,31
1,03
2,88
2,48
2,05
1,62
1,32
3,95
3,44
2,86
2,46
1,94
179
149
124
99
68
300
254
209
160
127
424
357
294
230
184
502
432
356
281
232
696
603
498
427
336
5,1
3,7
2,7
1,8
0,9
5,5
4,1
2,9
1,8
1,2
11,1
8,1
5,8
3,8
2,5
8,7
6,7
4,7
3,1
2,2
7,5
5,8
4,2
3,2
2,1
0,84
0,70
0,59
0,47
0,34
1,41
1,21
1,00
0,80
0,62
2,01
1,70
1,40
1,13
0,89
2,38
2,05
1,70
1,41
1,14
3,23
2,82
2,35
2,03
1,60
0,84
0,70
0,59
0,47
0,34
1,42
1,21
1,00
0,80
0,62
2,01
1,70
1,40
1,14
0,89
2,38
2,05
1,70
1,41
1,14
3,23
2,82
2,35
2,03
1,60
148
123
103
82
59
246
210
174
139
108
352
296
244
196
154
416
358
295
244
198
573
497
411
353
278
3,6
2,6
1,9
1,3
0,7
3,9
2,9
2,1
1,4
0,9
7,8
5,8
4,1
2,8
1,8
6,1
4,7
3,4
2,4
1,7
5,3
4,1
2,9
2,2
1,5

Qv
m3/h
Vdc
Model
eCM
20
Legend
WT = Water temperature
Ph = Emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow
kPa
Dp(c)
kW
Ph
l/h
Qw
kPa
Dp(c)
kW
Ph
l/h
Qw
kPa
Dp(c)
kW
Ph
l/h
Qw
kPa
Dp(c)
kW
Ph
l/h
Qw
kPa
Dp(c)
kW
Ph
l/h
Qw
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
10
7,5
5
3
1
330
270
220
170
120
515
430
350
280
210
735
610
495
395
305
890
755
610
500
400
1395
1175
945
785
605
CRC
23
CRC
43
CRC
63
CRC
73
CRC
93
CRC–ECM
CRC–ECM version Carisma
Heating emission of 3 row coil
Entering air temperature: 20°C
WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C
3,64
3,09
2,61
2,10
1,55
6,33
5,43
4,55
3,70
2,85
8,37
7,17
6,04
4,97
3,95
10,25
8,94
7,50
6,30
5,16
14,95
13,06
10,94
9,40
7,55
313
265
224
181
133
544
467
391
318
245
719
616
520
427
339
882
769
645
542
444
1285
1123
941
809
649
6,7
5,0
3,7
2,5
1,5
25,2
19,2
14,1
9,8
6,2
16
12,2
9,0
6,4
4,3
26,7
21
15,4
11,3
8,0
22,9
18,1
13,2
10,1
6,9
2,78
2,36
1,99
1,61
1,19
4,86
4,17
3,50
2,85
2,20
6,41
5,50
4,64
3,82
3,04
7,87
6,87
5,77
4,85
3,98
11,42
9,99
8,38
7,21
5,79
239
203
171
138
102
418
359
301
245
189
551
473
399
328
261
677
591
496
417
342
982
859
720
620
498
4,3
3,2
2,4
1,6
1,0
16,3
12,5
9,1
6,4
4,0
10,3
7,9
5,9
4,2
2,8
17,3
13,6
10
7,4
5,2
14,7
11,6
8,5
6,5
4,5
1,92
1,63
1,38
1,12
0,83
3,39
2,91
2,44
1,99
1,54
4,45
3,82
3,23
2,66
2,12
5,49
4,79
4,03
3,93
2,79
7,90
6,92
5,81
5,00
4,03
165
140
119
96
71
291
250
210
171
133
383
329
278
229
182
472
412
347
338
240
679
595
500
430
347
2,3
1,7
1,3
0,9
0,5
8,9
6,8
5,0
3,5
2,2
5,6
4,3
3,2
2,3
1,5
9,5
7,5
5,5
4,1
2,9
8,0
6,3
4,6
3,6
2,4
2,22
1,89
1,59
1,28
0,95
3,87
3,32
2,78
2,26
1,74
5,11
4,38
3,69
3,03
2,41
6,26
5,46
4,58
3,85
3,15
9,13
7,98
6,68
5,74
4,61
383
324
274
221
163
665
571
478
389
300
879
753
635
522
415
1077
939
788
662
542
1570
1372
1149
988
793
10
7,5
5,6
3,8
2,2
37,9
28,9
21,2
14,7
9,3
24,1
18,4
13,6
9,6
6,4
40,1
31,5
23,2
17
12
34,5
27,2
19,9
15,3
10,4
1,80
1,52
1,29
1,04
0,77
3,14
2,69
2,26
1,84
1,42
4,14
3,55
3,00
2,46
1,96
5,08
4,43
3,72
3,13
2,56
7,38
6,46
5,41
4,66
3,74
309
262
222
179
132
540
463
388
316
244
712
610
515
424
337
874
762
640
538
441
1270
1111
931
801
643
7,0
5,2
3,9
2,7
1,6
26,7
20,4
14,9
10,4
6,6
17
12,9
9,6
6,8
4,5
28,3
22,2
16,4
12,1
8,5
24,2
19,1
14
10,7
7,3
This manual suits for next models
2
Table of contents