SAH WSK Series User manual

WSK INTELLIGENT TEMPERATURE AND
HUMIDITY
CONTROLLER
USER
MANUAL

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER
USER MANUAL v 1.0
Thanks for choosing the Intelligent temperature and humidity controller
of our company. In order to convenient you to buy and use the controller
with safety, please read this manual carefully and note the following points.
CAUTION
1. The device must be installed and maintained by professional personnel
2. The signal and power supply must be cut off before any operations to the
internal or external part of the controller
The following conditions will cause damage or abnormality to the controller
1. Auxiliary power source voltage over range
2. Distribute system frequence over range
3. Current, voltage input poles incorrect
4. With electric pull out communication plug
5. No according requirement to connect terminal
Warning
1. Wiring warning
If the equipment failure or error occurs, can cause system fault, installation
of external protection circuit to prevent such incidents
In order to prevent the equipment damage or failure, choose the appropriate
fuse protection to prevent the power cord and input, output, strong current shock
2. Power supply
In order to prevent the equipment damage or failure, please use the rated
power
To prevent electric shock, or equipment failure, all wiring complete rear can
supply
3. Prohibited to use in the vicinity of flammable gas
As fire, explosion or equipment damage, banned in flammable, explosive
gas, venting occasion use
4. It is forbidden to touch the instrument inside
To prevent electric shock or burn, it is forbidden to touch the instrument
inside, only the company service engineer can check the internal wiring or
replacement parts. Instrument with
high pressure and high temperature parts. Very dangerous.
5. It is forbidden to change instrument
In order to prevent accidents or equipment failure, it is forbidden to change
equipment
6. Maintenance
Scrapped to prevent electric shock, instrument or fails, only the company's
service engineer can be replacement parts
In order to ensure the instrument is continuous and safe use, should be
regular maintenance. Instrument internal some parts may be damaged with
longer duration of use
CATALOG
1. Introduction…………………………
2.Technical Data………………………………2
3.Definition and Specification Matching………3
4. Outline、 installation hole and wiring………4
5.PanelExplain and Each function………………5
6. Operation Process…………………………6-12
………1

1. Temperature and humidity controller uses a dedicated microprocessor, SMT
SMT technology and high precision temperature and humidity sensor. Make
the product delicate and cabinet, reliable performance, high precision
measurement and control temperature and humidity, strong anti-jamming
capability control mode is simple. Can be widely used in industry, agriculture,
medical, chemical warehouse where the temperature and humidity
measurement and control.
2. Alarm function, this controller has the temperature, humidity process heater
disconnection quotation function, communication function, get more extensive
application in the field of automation control
Remark:
Process alarm output contact and disconnection alarm for the same.
INTRODUCTION
Main Technical Data
Supply voltage
AC: Switching power supply 85V~265V, 50~60Hz
AC: Transformer 110V, 220V, 380V, 50~60Hz
DC: 24V, 36V, 48V, 110V, 220V
Accuracy class
Temperature: ±0.5°C
Humidity: 5%±RH
Resolving power: 14 Bit
Cycle of sampling: 0.5 Sec
Measurement range
Temperature: -40~100°C
Humidity: 0~100%RH
Display
Measured values and set values by LED
Output condition and alarming condition by LED lights
Way of operating
Controlling by two-step (settable turn difference)
Control output
Relay output: Contact capability 250VAC 3A (Resistive load)
Voltage pulse output: 0~12 (Suitable for solid relay SSR)
Output contact
Electrical endurance: 1×10 times
Mechanical durability: 1×10 times
Installation
Panel type and embedded
Others
Insulation resistance: >50MΩ (500VDC)
Insulation capability: 1500VAC per minute
Power consumption: <10VA
Environment: 0~50°C, 30~85%RH no corrosive gas
Weight: About 0.5Kg (The power supply of product is the
switching power supply)
WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER

Public
Terminal
Public
Terminal
Temp
Alarming
Temp
Alarming
Temp
Alarming
Humidity
Alarming
Humidity
Alarm+ing
Humidity
Alarm+ing
Temp and Humidity Sensor
Temp and Humidity Sensor
Temp and Humidity Sensor
Power Supply
Power Supply
Power Supply
Communication
Communication
Communication
Temp
Controlling
Temp
Controlling
Temp
Controlling
Humidity
Controlling
Humidity
Controlling
Humidity
Controlling
WSK INTELLIGENT TEMPERATU+RE AND HUMIDITY CONTROLLERWSK INTELLIGENT TEMPERATU+RE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATU+RE AND HUMIDITY CONTROLLER
WSK INTELLIGENT TEMPERATU+RE AND HUMIDITY CONTROLLER
WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER
The wiring diagram(subject to the product itself the wiring diagram)
485
Frame Size Hole Size
Frame Size and Hole Size
Frame Size and Installation Hole Size and Wiring
Definition of Model No. and Specification Matching
Model identification
Additional communication function
Additional circuit alarm
Additional process alarm
No function above mentioned
Attention: If DC:24V output is needed, please note
that when placing order

WSK INTELLIGENT TEMPERATU+RE AND HUMIDITY CONTROLLERWSK INTELLIGENT TEMPERATU+RE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATU+RE AND HUMIDITY CONTROLLER
WSK INTELLIGENT TEMPERATU+RE AND HUMIDITY CONTROLLER
WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER
Panel Explaination and Each Function
Panel show Content description
Temp Measuring Display value model
Mode content parameter values
Humidity Measuring
Temperature control output indicator light
Humidity control output indicator light
Temperature process alarm indicator lights
Humidity process alarm indicator lights
Temperature disconnection alarm indicator lights
Humidity disconnection alarm indicator lights
The communications light
Instrument power light work
Increasing Key
Decreasing Key
Up Key
Down Key
Displacement Key Mode Key
Confirm Key Quit Key
Operation Process
Boot Up Process
Open the Power
Self-checking of LED device
Automatic
Automatic
Transfomation)
Transfomation)
Displaying the current temperature and humidity
All LEDS light up
Measuring the current
temperature and humidity
Set the mode and modify the parameter
In normal display mode of ℃/%RH, press the “SET” button to enter the
temperature and humidity controlling and alarming settings. Press the “SET”
button for more than 3 seconds to enter the setting mode condition.
Shift Key for more than 3 seconds
“SET”
“SET”Shift Key
To press “SET” shift key again to enter the condition of modifying the content and parameter
To modify the parameter content
Confirm Key to save the changes
Confirm Key to return
Displaying current temperature
and humidity

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER
At this time the parameter can be modified by pressing the shift key “SET”,
Increasing key “ ”, reducing key “ ”. Click the confirm button “ ”
to save the data after modification. If you need continue to modify other
parameter, press the increasing key “ ” and reducing key “ ” selection
need to modify the pattern. In setting mode, if modified, and then click the
confirm button “ ” to return to normal state
Attention
This controller has automatic returning function. When the operator set parameter modification
operation and forget to return to the main display mode, the instrument after 30 seconds
automatically return to the main display mode
etc
.
Before using the controller or modifying the parameter of the controller, please read the
following instructions carefully.
Mode content and parameter list
Communication agreement
The physical layer
communication interface, the asynchronous half-duplex mode
Communications speed can be set to 1200-9600 BPS, the factory default 2400 BPS
Byte transfer formats: one start bit, 8 data bits, parity (N81, E81, 081) optional,
factory default E81
Digital communication protocol:
The controller provides asynchronous duplex RS485 serial communication interface and
adopts the MODBUS-RTU protocol, all kinds of data information can be transmitted on the
communications lines. One route can connect to 32 network controller at the same time,
each controller can be set different mailing Address (the Address No.), different series
controller communication terminal number is different, the communication connection is
shielded twisted-pair cable should be used with copper net, wire diameter is not less than
0.55 mm. Wiring should keep communication lines from high voltage cable, or other strong
electric field environment, T type is recommended for the network connection
(see figure 1), but does not recommend a star or other contact way
temperature and
humidity controller
temperature and
humidity controller
temperature and
humidity controller
power
supply
communication protocol:
The MODBUS-RTU communication protocol uses the master-slave communication
response mode connections on a communication line. First of all, the main computer
of the signal only address addressing to a terminal equipment (machine), and then,
the response signal from the terminal to transmit to host in the opposite direction, i.e.,
in a single communication line signal transmission instead of two direction all
communication data flow (half duplex working mode). MODBUS protocol is
only allowed on the host (PC, PLC, etc.) and the communication between the
terminal equipment (see chart 2), and does not allow independent data exchange
between terminal equipment, so that each terminal equipment not occupy the
communication line when they are initialized again, but only in response to the
native query signal
Master device
query information Device address
Device address
The database
The database
Function code
Function code
Error checkingError checking
Error checking
In response to the
information of the equipment
FIG 1
FIG 2
Display Name Instruction Setting range Default
setting
Password
is the lightest brightness
Back to the factory default setting
LED display brightness of controller
Data format of controller
Communication velocity of controller
Communication address range of controller
Temperature process alarming hysteresis error setting
Humidity process alarming hysteresis error setting
Humidity controlling hysteresis error setting
Temperature controlling hysteresis error setting
Humidity process alarming mode alternative setting
Temperature process alarming mode alternative setting
Humidity process alarming condition
Humidity process alarming setting values
Humidity heater disconnection alarming condition
Temperature heater disconnection alarming condition
Temperature process alarming setting values
Temperature process alarming condition
Lower deviation alarming
Lower deviation alarming
Higher deviation alarming
Higher deviation alarming
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Heat up Cool
Humidification
Dehumidification
Actual measured
values
Actual measured
values
Temperature measured values
Humidity measured values
Mode display values
Mode display values
Temperature controlling setting values
Humidity controlling setting values
Humidity controlling alternative mode
Temperature controlling alternative mode
Temperature measurement value correction
Humidity measurement value correction

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER
The host query:
Query message frames includes device address, function code, data, information, check code. Address
code informs the machine that is selected to perform the destined function equipment, such as functional
code 3 or 4 is for registering the data which is read from the device and return their content; Contains data
from the device to perform functions other additional information, such as reading command, data
segment additional information start from how to register and number of registers to read; Check code is
used to test the correctness of the a frame information, provides from the device with a validation
message content is the right approach, it adopts CRC16 calibration rule
If from the device to produce a normal response, in response to the message from the machine address
code, function code, code and data information CRC16 check code. Data information code, including the
data collected from the device, such as register values or state. If there are errors, we agreed from the
machine does not respond. Transport refers to a data frame in a series of separate data structure and used
for the transmission of data limited rules, defines the RTU mode compatible with MODBUS agreement
under the mode of transmission. Each byte: a start bit, 8 data bits, parity bit (,), 1 stop bit (a parity bit) or
1 stop bit (and white parity bits).
The structure of the data frame:(Message format) Table 1
Address Code
Address Code
Function Code Data Code Check Code
Table
At the beginning of a frame by a byte (eight binary code), the decimal is 0-255, only use the 1-247 in our
system, the other address. These bits indicate the address specified by the user terminal equipment, the
device will accept data from the connected to the host. Each terminal equipment address must be unique,
only by addressing to the terminal response contains the address of the query. When the terminal sends
back a response, in the response from the machine address data and tell the host which terminal is to
communicate with them.
ONE
ONE
ONE ONE TWO
TWO
CODE Meaning Behavior
Function Code: (Table 2)
Tell what is addressing to the terminal to perform the function. Listed in the following table shows the
supported code function, and their meaning and function Table
Query data frame (main machine) ( Table 3)Table
Table
Table
Table
Address
Address
Address
Address
Command
Command
Command
Command
The starting
register
address
(high)
The starting
register
address
(high)
The starting
register
address
(high)
The starting
register
address
(high)
The starting
register
address
(low)
The starting
register
address
(low)
The starting
register
address
(low)
The starting
register
address
(low)
Quantity of
register
(high)
Quantity of
register
(high)
Quantity of
register
(high)
Quantity of
register
(high)
Quantity of
register
(low)
Quantity of
register
(low)
Quantity of
register
(low)
Quantity of
register
(low)
low
low
low
low
high
high
high
high
Record
the data
Response data (from the machine frame), indicating that the data has been written. (table 6)
Query data frame (the host machine) (see table 5)
The response data (from the machine frame) (see table 4)
This function allows the user to change the contents of a register, is written to the data to be
highlighted as writable attribute, the number of address range is not more than, this example
is written communication
Check code:
Error check (CRC) domain are two bytes, containing a 16-bit binary values. CRC value is calculated
by the transport equipment, and then attached to a data frame, the receiving device to recalculate the CRC
value when receiving data, and then compared with acceptance to the CRC in the domain of value, if the
two values are not equal, an error has occurred. As shown in figure 3
Read data (functional code: 3) : this function can users get the terminal equipment acquisition \
recorded data, as well as the system parameters. Host a request there is no limit to the number of data
collected, but not beyond the definition of address range
Communication message example

WSK INTELLIGEN T TEMPE RATUR E AND H UMIDI TY CONTROLLERWSK INTELLI GENT TEM PER ATURE AND HUMI DITY CONT RO LLER
FIG3
Start
or
or
moves to the right one
carry
Next
End of the frame
End
Correspondence address (see table 7)
Table
Heat Up
Cool
Humidification Dehumidification
The actual measured value
The actual measured value
Humidity control mode
Temperature control mode
Temperature controlling setting
Humidity controlling setting
Sensor for real-time detecting humidity values
Sensor for real-time detecting temperature values
Temperature controlling hysteresis error
Humidity controlling hysteresis error
Temperature measurement value
Humidity measurement value
Humidity heater disconnection alarming setting
Temperature heater disconnection alarming setting
Temperature process alarming setting
Humidity process alarming setting
Humidity process alarming state
Temperature process alarming state
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
Lower deviation alarming
Lower deviation alarming
Higher deviation alarming
Higher deviation alarming
3 is the highest
brightness
the lED display brightness
the controller data format
controller communication velocity
controller communication address range
Temperature process alarming mode
Humidity process alarming mode
Temperature process alarming
hysteresis error setting
Humidity process alarming
hysteresis error setting
Address
Address
Project
Project
Description
Description
The data
format
Data
format
Length of
the data
Length of
the data
Instruction
Instruction
Read and
write
Read and
write
The basic setting information
The basic setting information
2
This manual suits for next models
1
Table of contents
Popular Controllers manuals by other brands

SDC
SDC UR4-8 installation instructions

Tews Technologies
Tews Technologies TIP810-SW-42 user manual

Allen-Bradley
Allen-Bradley 2080-LC20-20QWB user manual

Multiplex
Multiplex Roxxy BL-Smart Control 940-6 Operation instructions

Wilo
Wilo Control MR-Lift Installation and operating instructions

HighPoint
HighPoint SSD7103 installation guide