Salda Stouch User manual

STOUCH
EN TECHNICAL MANUAL 3
LT TECHNINIS VADOVAS 24
DE BEDIENUNGSANLEITUNG 45
FR NOTICE TECHNIQUE 67
RU ТЕХНИЧЕСКОЕ РУКОВОДСТВО 89
IT MANUALE TECNICO 111
LV TEHNISKĀ INSTRUKCIJA 134
SE TEKNISK MANUAL 156

2 | STOUCH v2019.1

EN | 3STOUCH v2019.1
1. DESCRIPTION
Stouch controller is specially designed for control of:
• Heat recovery systems, where control boards PRV_V21, EKR, MCB or ECO_v1072are installed;
• Air supply, exhaust units when automatic control is used with ECO_v107 controller;
• Fans with EC motors³;
• Devices which are controlled using Modbus protocol.
1Units: RIS/RIRS 3.0; RIS/RIRS EKO 3.0
2Units: RIRS 200 VER EKO; RIRS 300 VE... EKO
3Using the remote controller “Stouch” for “ECO” fans’ control it is necessary to use additional power
supply and to provide the protection against overloads and/or short circuits.
NOTE: Remote controllers don’t control cooker hoods separately with following units:
RIRS 200 V EKO with “Aut. RIRS-200VEEC-...k (+ 15..25 oC)” automatics;
RIRS 300 V EKO with “Automatika RIRSV 300 VE” automatics.
This function is possible only with the units that have integrated automatics.
Remote controllers ensures comfortable operation, monitoring, maintenance and safety. All opera-
tions are performed remotely by using controller, which shows fault reports and maintenance con-
ditions.
Features:
• Exceptional and ergonomic design;
• Casing: plastic;
• Screen: tempered glass;
• Easy operation;
• Surface mounted;
• One touch control;
• Easily controlled;
• Numbers displayed at screen;
• Acoustic response to touch;
• Can be connected to BMS network;
• Can be directly connected to fan controlled with 0 - 10 VDC signal;
• CO2or pressure sensor can be connected by using 0 - 10 VDC output;
• 4 selectable speeds;
• Maximum fan speed for limited time period (boost);
• Blocking (locking) - protection from children;
• In the user menu, parameters of sound, standby menu and CO2can be changed.
Package includes:
Stouch controller, cable (13 m), fastening elements (screw 3,9 x 25 DIN 7981-2 pcs. nylon plug 5 x
25 - 2 pcs., hammered steel plug 12 x 30 - 2 pcs.), technical manual.

4 | EN STOUCH v2019.1
2. DIMENSIONS
84 mm20,5 mm1,5 mm
84 mm
3. INSTALLATION
60±0,5mm
Ø 40
Ø 5 mm
60±0,5mm
Ø 40
Ø 5 mm
60±0,5mm
Ø 40
Ø 5 mm
1. Separate the cover form the casing as in pic. 1,2;
2. Connect the cable to the controller
2.1- standard cable connection

EN | 5STOUCH v2019.1
14
1 2 3 4
PIN1 - +24V
PIN2 - B+
PIN3 -A-
PIN4 - COM
PIN1 - +24V
PIN2 - B+
PIN3 -A-
PIN4 - COM
2.2 - spec connection (see “8 pin connection”).
3. Put the cover at the intended location on the wall and mark places for the drilling, pic., 3,4;
4. Drill 5 mm holes at the marked places for nylon plugs and the hole throughout the wall to install
the cable.
NOTE: the hole throughout the wall is necessary to connect the plug in cable from the other side of
the wall. The diameter of the hole should correspond the size of cable plugs. 5. Place 2 nylon plugs
into 5 mm holes.
NOTE: metal plugs included into package also can be used pic. 5.
6. Screw the cover to the wall with the screws 2,9 x 16 DIN7981C included into package. Pic. 6
7. If the connection is intended form any side of the casing (as it is shown in pic. 7) than in the middle
of the necessary casing side make a space for the cable with a knife.
8. Connect the necessary cables in the casing, plug them through the hole to another side of the wall
or place to a necessary side of the casing and press the casing on the cover, pic. 8.
IT IS FORBIDDEN to leave the remaining remote controller’s cable in the AHU’s
control box!
4. 8 PIN CONNECTION
Only competent electrician is allowed to make electrical connections in accordance with the appli-
cable international and national electrical safety and electrical equipment installation requirements.
1. Power supply 24 V AC/DC, 100 mA (polarity is not important)
2. Power supply 24 V AC/DC
3. GND
4. RS485 B (Modbus)

6 | EN STOUCH v2019.1
5. RS485 A (Modbus)
6. GND
7. 0-10 VDC input (used for pressure or CO2sensor). The sensor is powered from a separate power
source.
8. 0-10 VDC output (used for control of 0..10 VDC fans).
1. NOTICE: when the remote controllers are used with air-quality converter (the power
supply and analog output GND of witch are not electrically separate), then constant volt-
age (DC) has to be used for their power supply.
2. NOTICE: The power source must be selected according to the used currents of the
remote controller and air quality converter. Power source is not supplied with the remote
controller.
5. RECOMMENDATIONS FOR CONNECTION OF THE REMOTE CON-
TROLLER TO OTHER DEVICES
5.1. WHEN CONTROL PANEL IS USED WITH AIR HANDLING UNIT WITH
INTEGRATED AUTOMATICS
Vin
GND
A
B
GND
AO1
IP54
Duct CO2transsmiter S-KCO2 (DSC-G)
-A 2
-S Touch
CON1
-F
-F
AHU
RS485_2
LN
-G
230VAC_24VDC
1 - 24VDC/AC
2 - 24VAC/DC
3 - GND
4 - RS465-B
5 - RS485-A
6 - GND
7 - 0 - 10VDC IN
8 - 0 - 10VDC OUT
F- Fuse
G- constant voltage
(DC) power supply
M1 - EKO fans

EN | 7STOUCH v2019.1
5.2. WHEN THE REMOTE CONTROLLER IS USED WITH EKO FANS
-M1
2,5kW/4A
2970min-1
PE
N
L
+10V
Tacho
GND
0-10V/PWM
-F
-F
-F
-STouch
CON1
1 - 24VDC/AC
2 - 24VAC/DC
3 - GND
4 - RS465-B
5 - RS485-A
6 - GND
7-0-10VDC IN
8 - 0 - 10VDC OUT
Vin
GND
A
B
GND
AO1
IP54
Duct CO2transsmiter S-KCO2 (DSC-G)
-A 4
N
L
PE
-G
230VAC_24VDC
NOTICE: The power source, security elements, and other components necessary for installation
are not supplied.
6. INFORMATION FOR USER
• Controller allows easy setting of sound, temperature, sleep mode and CO2level parameters from
the user menu.
• Fast button for setting maximum speed.
• Numerical display of set and supply air temperature.
• Selected speed LED indication.
• Symbolical display of active alarms: A.01, A.02, etc., and LED indication.
• Controller sleep mode to reduce power consumption.
• Selectable ventilation system switch o locking feature.
• “Child safety feature” - locks the controller.

8 | EN STOUCH v2019.1
DESCRIPTION OF ELEMENTS
B1 On/O B5 Maximum fan speed for limited time (boost)
B2 Fan speed selection B6 Decrease
B3 Temperature selection S1 Segment display
B4 Increase L4-L7 Fan speed indications
ELEMENTS COOMAND ACTION INDICATION
B1 L1 Switch on Press down for 2
seconds B1 L1 lights on.
B1 L1 Switch o Press down for 2
seconds B1 L1 lights o.
L1 Activation from
sleep mode Press any button. L1 ashes slowly in sleep mode.
B2 B4 B6
L2 Set fan speed Touch B2. L2 lights on. Speed is adjusted by touching
elements B4 and B6
B3 B4 B6
L3
Set tempera-
ture Touch B3. L3 lights on. Temperature is adjusted by
touching elements B4 and B6
B4 B6
L4-L7
Change value
of selected
setting
Increase by touch-
ing B4, decrease
by touching B6
Numbers change in the segment display. L4,
L5, L6, L7 shows selected fan speed.
B4 B5 B6
L2
Switch on/o
the intensive
ventilation
(boost)
Press 2 secons
B5.
L2 is blinking. Split screen shows remaining
time in seconds (if there’re more than 600
sec. then - in minutes). Time can be adjusted
by pressing B4 and B5 (in time of processing
the function).
Maximal BOOST time: 300 minutes (5 hours).
Note: Time can’t be adjusted on PRV con-
troller. If unlimited BOOST time is set on PRV
controller, then split screen shows “---“.

EN | 9STOUCH v2019.1
B1 B4 B6
L4-L7
Review and
cancel alarms
and warnings
Press B2 and B3
for resetting
By pressing B1
faults are tempo-
rary not shown.
In case of failure L4, L5, L6, L7 are blinking
and failure codes appear on split screen
(A.01, A.02 and etc.). In case of warning,
warning codes (.01, .02 and etc.) appear
on split screen. List of errors and warnings
can be reviewed by pressing B4 or B6.
After clearing fault or warning signal remote
controller returns into initial state. By pressing
B1 faults are not shown for one minute, thus
permitting to adjust temperature and fan
settings.
Note: it’s strictly forbidden to clear a fault
or warning without removing its cause. This
must be performed by the service represen-
tatives or maintenance personnel.
B1 B4 B6 Functional
Review
Upon pressing
B1 the functional
codes are not dis-
played temporarily
When the function is active, the segment
display shows functional codes. The list of
functional messages can be reviewed by
touching B4 or B6 buttons. Upon pressing B1
the functional codes are not displayed for one
minute, allowing manipulation of temperature
and fan settings.
NOTE: if failures are active, the functional
codes are not displayed!
B1
L2-L7 CO2 blow o
By pressing B1
indication „CO2“is
not shown tem-
porary.
L2, L3 and L7 are blinking, L4, L5, L6 are
shining. Split screen shows “CO2”. By press-
ing B1 indication “CO2” is not shown for one
minute, thus permitting to adjust temperature
and fan settings.
B2 B3 B5
On/o
“Child safety
feature”
Press down B3,
B2 and B5 for 2
seconds.
Non active elements B1, B4 and B6. After
pressing unavailable button, segment display
shows “−−−”
7. CONNECTION INDICATION
Flashing „Con“ – connecting.
Shining „noC“ – connection lost or there is no connection with the controller.
NOTE: This paragraph applies when the controller is used as a Modbus master.
8. FAN SPEED CONTROL OPTIONS
• Selecting 4 preset speeds;
• Selecting percentage value of speed (0,20 - 100 %) only for 0...10 VDC output and ECO controller;
• User menu speeds are set in intervals of 5 %;
• Service menu speeds are set in intervals of 1 %;
• Operates in 4 speeds, the values of which are displayed on Stouch in Pascals (Pa).
NOTE: the function is available when fan and pressure sensor are connected to Stouch.

10 | EN STOUCH v2019.1
• Maximum ventilation. The unit operates in maximum speed (according to boost conguration).
Maximum speed is limited by timer which can be easily set (see table);
• Maximum speed can be activated using fast button. When preset maximum fan speed (boost)
time is over, previous speed is automatically restored;
• 0..10 VCC CO2sensor can be connected for activation of maximum speed based on the given
CO2parameters.
9. TEMPERATURE
• Temperature from 15 to 30 C may be set by remote controller. Note: Temperature of MCB control-
ler can be adjusted from 0 up to 40C (it depends on MCB settings).
• Supply air and set temperatures can be displayed interchangeably (set temperature is displayed
for 5 seconds, then supply air temperature is displayed for 2 seconds)
10. REMOTE CONTROL (MODBUS)
Controller supports fully congurable Modbus interface. Panel can operate as master and slave
device in modbus network and also it can be fully controlled and congured not only via service
menu but also via modbus interface.
11. USER MENU
In order to reach user menu, press down B2 and B3 for 3 seconds.
In user menu, menu items (P.01, P.02 etc.) settings are displayed sequentially. Menu item is select-
ed using elements B4 and B6. After pressing B5, value of selected parameter is shown and can be
changed using elements B4 and B6. Press B5 to save the parameter and to return to menu.
Due to limitations of segment display, values of P.04 and P.05 are shown divided by 10, i.e. if 20 is
displayed, it means that real value is 20 x 10 = 200.
P.06 - Filter timer resets by pressing B2 and B3 for more than 5 seconds. Filter timer also resets
by clearing fault signal.
Touch element B1 to exit menu.
NO. NAME POSSIBLE VALUES DEFAULT
VALUE
P.01 Sleep mode 0 - O
1 - 99 sleeping time in seconds 0
P.02 Sound 0: O
1: 1 – 9 sound tone 2
P.03 Supply air temperature display
0: Not shown
1: Shown interchangeably with the set
temp
0
P.04 CO2required (ppm) 0 – 99 x 10 ppm 20 x 10
P.05 CO2 allowed dierence 0 – 99 x 10 ppm 5 x 10
P.06 Filtrer timer
PRV control board: indicates days
passed after the last lter change.
MCB control board: indicates days left
to the next lter change.
0

EN | 11STOUCH v2019.1
P.0
Air ow handling by extract air relative
humidity. (Only if connected to MCB
control board)
0: O
1: On 0
P.08
Set value of relative humidity in air at
summer season (Only if connected to
MCB control board)
0..100% 0
P.09
Set value of relative humidity in air at
winter season (Only if connected to
MCB control board)
0..100% 0
P.10 Excessive humidity purging time (Only
if connected to MCB control board) 1..600min. 1
12. INTENDED USE
12.1. MODBUS MASTER (MAIN)
MODBUS
RC AHU
0...10 VDC
RC FAN
MODBUS
0...10 VDC
RC
FAN
MODBUS
0...10 VDC PS
0...10 VDC
RC
FAN
0...10 VDC PS
MODBUS AHU
MODBUS
RC
AHU RC
AHU
BMS
RC - controller (master); AHU - AHU (slave)
This controller can control other devices (controlled by MODBUS protocol) for example, air handling
units. This can be set in service menu by selecting required parameters for service menu items F.1,
F.18, F.19, F.20, F.21. To control not only standard devices, select “CUSTOM” in menu item F.20 and
device addresses in menu items from F.22 up to F.3. If devices have no such addresses, in elds
of given menu items enter “00:00”. Normally, this controller is used with ECO or PRV control boards.
12.2. MODBUS SLAVE
MODBUS
RC AHU
0...10 VDC
RC FAN
MODBUS
0...10 VDC
RC
FAN
MODBUS
0...10 VDC PS
0...10 VDC
RC
FAN
0...10 VDC PS
MODBUS AHU
MODBUS
RC
AHU RC
AHU
BMS
RC - controller (master); AHU - AHU (slave)
Using BMS (Building Management System), several devices can be controlled simultaneously or
one device can be controlled using several controllers. MODBUS protocol allows changing all pa-
rameters of controllers and monitoring data of connected sensors.

12 | EN STOUCH v2019.1
12.3. FAN CONTROL WHEN SPEED IS SET USING CONTROLLER AND/
OR COMPUTER VIA MODBUS
MODBUS
RC AHU
0...10 VDC
RC FAN
MODBUS
0...10 VDC
RC
FAN
MODBUS
0...10 VDC PS
0...10 VDC
RC
FAN
0...10 VDC PS
MODBUS AHU
MODBUS
RC
AHU RC
AHU
BMS
RC - controller (master); FAN - fan
Using this remote controller and CO2transmitter it is possible to reduce inside carbon dioxide level.
This controller allows controlling both device and 0..10 VDC fan. In service menu, select desired
speed control method (F.01). If control based on preset speeds is selected, then select them in menu
items F.03, F.04, F.05, F.06.
NOTE: The air quality converters and remote controller (when fan is controlled) must be powered
from a separate power source. It is not supplied with the remote.
12.4. PRESSURE CONTROL WHEN SELECTED USING CONTROLLER
AND/OR COMPUTER VIA MODBUS
MODBUS
RC AHU
0...10 VDC
RC FAN
MODBUS
0...10 VDC
RC
FAN
MODBUS
0...10 VDC PS
0...10 VDC
RC
FAN
0...10 VDC PS
MODBUS AHU
MODBUS
RC
AHU RC
AHU
BMS
RC - controller (master); PS - pressure sensor; FAN - fan
Desired pressure can be maintained by connecting 0..10 VDC fan and 0..10 VDC pressure convert-
er directly to the controller. Control and pressure sensor parameters can be changed in controller.
When controller is used as Modbus slave device (air handling unit is not controlled by this principle),
it allows controlling all parameters and monitoring of pressure sensor readings.
For pressure based control, select the following parameters in the service menu:
F.01 - 2
F.14 - 1
F.15 and F.16 - based on pressure converter parameters
F.11, F.12 and F.13 - (PID control ratios). If pressure is maintained incorrectly, these parameters
can be adjusted.
F.0 - F.10 - seting of xed speeds (supports dierent pressure level in Pa)
F.43 -1- 0..10VDC output activated.

EN | 13STOUCH v2019.1
12.5. CO2CONTROL
MODBUS
RC AHU
0...10 VDC
RC FAN
MODBUS
0...10 VDC
RC
FAN
MODBUS
0...10 VDC PS
0...10 VDC
RC
FAN
0...10 VDC PS
MODBUS AHU
MODBUS
RC
AHU RC
AHU
BMS
RC - controller (master); AHU - AHU (slave) ; PS - pressure sensors; FAN - fan
This controller allows controlling level of carbon dioxide (CO2) in a room. Connect 0..10 VDC CO2
sensor directly to the controller and congure the controller. In service mode, in item F.14 set 2, and
F.15 and F.16 should be set based on the sensor specication.
After CO2sensor is connected and required parameters are set in the service menu, select desired
CO2level (P.05) and allowed dierence from the set (P.05) limit in the user menu. If allowed dier-
ence is exceeded, controller will automatically start fans at maximum (4) speed and “CO2” will be
shown in digital display. After set CO2level (P.05) is reached, controller will return to previous mode.
NOTE: The air quality converters and remote controller (when fan is controlled) must be powered
from a separate power source. It is not supplied with the remote controller.
13. SERVICE MENU
To enter service menu:
1. Go to “Off” state (if controller is on, press down element B1 for 3 seconds).
2. Press down B1 and B2 for 3 seconds.
3. Using elements B4 and B6, enter security code “022” and conrm with element B5.
In the service menu, settings of menu items (F.01, F.02 etc.) are shown sequentially. Menu item is
selected using elements B4 and B6. After pressing B5, value of selected parameter is shown and
can be changed using elements B4 and B6. Pressing B5 saves the parameters and returns to the
setting menu.
To exit the service menu, press down element B1 for 3 seconds (controller goes to switch o state).
NO. NAME POSSIBLE VALUES DEFAULT
VALUE
F.01 Fan control
0: 0..100 %
1: Fixed speeds
2: Based on xed pressures
1
F.02 Switch of locking
0: Not locked
1: Fan always operates at minimum
speed 1
0
F.03 Speed 1 (%) 0 – 100 20
F.04 Speed 2 (%) 0 – 100 40
F.05 Speed 3 (%) 0 – 100 70
F.06 Speed 4 (boost) (%) 0 – 100 100

14 | EN STOUCH v2019.1
F.0 Speed 1 (Pa) 0 – 999 x 10 5
F.08 Speed 2 (Pa) 0 – 999 x 10 10
F.09 Speed 3 (Pa) 0 – 999 x 10 25
F.10 Speed 4 (boost) (Pa) 0 – 999 x 10 40
F.11 Pressure PID – P 0 – 999 5
F.12 Pressure PID – I 0 – 999 10
F.13 Pressure PID – D 0 – 999 0
F.14 Converter
0: No
1: Pressure
2: CO2
0
F.15 Converter MIN 0 - 250 x 10 0
F.16 Converter MAX 1 - 250 x 10 200
F.1 Controller Modbus master/slave ad-
dress
0: Master
1 - 247: Slave 0
F.18 Modbus data transfer rate
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
4
F.19 Setting of data package
0: N,8,1;
1: E,8,1;
2: O,8,1;
3: N,8,2;
4: E,8,2;
5: O,8,2;
1
F.20
Operated device (remote controller au-
tomatically recognizes PRV, EKR, MCB
ir ECO control boards).
0: None
1: Custom
2: ECO
3: PRV
4: MCB
5: EKR
0
F.21 Modbus address of controlled device 1 - 247 1
F.22 SET Temperature address 00:00 - FF:FF 00:00
F.23 SET Fan speed (%) address 00:00 - FF:FF 00:00
F.24 SET Fan speed xed address 00:00 - FF:FF 00:00
F.25 SET Pressure address 00:00 - FF:FF 00:00
F.26 SET CO2address 00:00 - FF:FF 00:00
F.2 Temperature address 00:00 - FF:FF 00:00
F.28 Alarm 1 address 00:00 - FF:FF 00:00
F.29 Alarm 2 address 00:00 - FF:FF 00:00

EN | 15STOUCH v2019.1
F.30 Alarm 3 address 00:00 - FF:FF 00:00
F.31 Alarm 4 address 00:00 - FF:FF 00:00
F.32 Alarm 5 address 00:00 - FF:FF 00:00
F.33 Alarm 6 address 00:00 - FF:FF 00:00
F.34 Alarm 7 address 00:00 - FF:FF 00:00
F.35 Alarm 8 address 00:00 - FF:FF 00:00
F.36 Alarm 9 address 00:00 - FF:FF 00:00
F.3 Alarm 10 address 00:00 - FF:FF 00:00
F.38 Restore controller factory settings 0: No
1: Yes 0
F.39 Modbus (Holding register) type param-
eter reading and changing tool 0 - 999 0
F.40 Modbus (Coil register) type parameter
reading and changing tool 0 - 999 0
F.41 Control panel version - -
F.42 Fan’s controlled by 0..10 VDC signal
start delay time in seconds 0 - 120 0
F.43 0..10 VDC Disable / Enable 0: OFF
1: ON 0
F.44
Restore factory settings of PRV control
board.
Note: accessible only by connecting to
PRV controller
0: No 1: Yes 0
F.45 Tool for air ow adjustment. 0 - 100 0
To restore factory settings, service password “022” should be reentered.
Due to limited number of symbols in segment display, modbus addresses of “CUSTOM” device are
entered as HIGH and LOW bytes in hexadecimal (HEX) system. Using buttons B2 and B3, select
HIGH or LOW bytes, “H.00” and “L.00” are displayed respectively.
14. MODBUS REGISTER READ AND RECORD TOOL
Modbus register read and record tool indicated in F.39 and F.40 items is useful when you want to
set the unit‘s parameters, which by default are not controlled by remote controller, but these param-
eters are accessible via Modbus. F.39 is used for Holding type registers and F.40 used Coil registers.
Using the Tool:
1. Modbus register address is indicated and conrmed by “MAX” button.
2. The tool reads the address value and shows on a segmental display (the value ashes).
3. Change the value with “+” and “-” button and conrm with the MAX button.
4. The tool records the value to indicated register and return to the service menu.

16 | EN STOUCH v2019.1
15. AIR FLOW HANDLING TOOL
Service menu F.45 is used to adjust air ow for dierent modes. Air ow handling tool operates with
MCB and PRV controllers.
Tool operation instruction:
1. Select desired air ow, what you want to control: SF.1, SF.2, SF.3, SF.4, EF.1, EF.2, EF.3or EF.4.
(SF and EF determine, for which fan airow will be modied; SF – air supply fan, EF – air exhaust fan.
Number determines speed/mode, for which air ow will be modied).
2. Equipment switches to the mode/speed, what was selected. Value from the controller is shown
on the split screen.
3. By pressing B4 and B6 you may change values (from 0 up to 100%). Fans speed/airow changes
automatically.
4. By pressing B5 you may exit airow handling tool. Adjusted settings are saved on controller.
5. In order to change other airow setting, please repeat steps 1-4.
16. STOUCH CONTROL PANEL AND OTHER MODBUS DEVICES MAY
NOT WORK PROPERLY WHEN PRV AUTOMATION IS ON THE COMPAT-
IBILITY MODE.“COMPATIBILITY MODE” CAN BE TURNED OFF WITH
STOUCH CONTROL PANEL:
1. Go to Service menu item F.40 (Modbus Coil read / write tool). How to enter service interface is
described in Stouch technical manual.
2. Specify address 21 and press “MAX” (indicate “Compatibility mode” Modbus register)
3. Set “0” and press “MAX” (“1” - on, “0” - o)
17. MODBUS SLAVE ADDRESS TABLE
NAME POSSIBLE VALUES TYPE ADDRESS
(HEX)
ADDRESS
(DEC)
Fan control
0: 0..100 %
1: Fixed speeds
2: Based on xed pressures
Holding
register 0x01 1
Switch of locking
0: Not locked
1: Fan always operates at
minimum speed 1
Holding
register 0x02 2
Speed 1 (%) 0 – 100 Holding
register 0x03 3
Speed 2 (%) 0 – 100 Holding
register 0x04 4
Speed 3 (%) 0 – 100 Holding
register 0x05 5
Speed 4 (boost) (%) 0 – 100 Holding
register 0x06 6
Speed 1 (Pa) 0 – 999 Holding
register 0x07 7

EN | 17STOUCH v2019.1
Speed 2 (Pa) 0 – 999 Holding
register 0x08 8
Speed 3 (Pa) 0 – 999 Holding
register 0x09 9
Speed 4 (boost) (Pa 0 – 999 Holding
register 0x0A 10
Pressure PID – P 0 – 999 Holding
register 0x0B 11
Pressure PID – I 0 – 999 Holding
register 0x0C 12
Pressure PID – D 0 – 999 Holding
register 0x0D 13
Converter
0: No
1: Pressure
2: CO2
Holding
register 0x0E 14
Converter MIN 0 - 250 x 10 Holding
register 0x0F 15
Converter MAX 1 - 250 x 10 Holding
register 0x10 16
Controller Modbus master/
slave address
0: Master
1 - 247: Slave
Holding
register 0x11 17
Modbus data transfer rate
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
Holding
register 0x12 18
Setting of data package
0: N,8,1;
1: E,8,1;
2: O,8,1;
3: N,8,2;
4: E,8,2;
5: O,8,2;
Holding
register 0x13 19
Controlled device
0: None
1: Custom
2: ECO
3: PRV
4: MCB
5: EKR
Holding
register 0x14 20
Modbus address of con-
trolled device 1 - 247 Holding
register 0x15 21
SET Temperature address 00:00 - FF:FF Holding
register 0x16 22
SET Fan speed (%) ad-
dress 00:00 - FF:FF Holding
register 0x17 23

18 | EN STOUCH v2019.1
SET Fan speed xed
address 00:00 - FF:FF Holding
register 0x18 24
SET Pressure address 00:00 - FF:FF Holding
register 0x19 25
SET CO2address 00:00 - FF:FF Holding
register 0x1A 26
Temperature address 00:00 - FF:FF Holding
register 0x1B 27
Alarm 1 address 00:00 - FF:FF Holding
register 0x1E 28
Alarm 2 address 00:00 - FF:FF Holding
register 0x1F 29
Alarm 3 address 00:00 - FF:FF Holding
register 0x20 30
Alarm 4 address 00:00 - FF:FF Holding
register 0x21 31
Alarm 5 address 00:00 - FF:FF Holding
register 0x22 32
Alarm 6 address 00:00 - FF:FF Holding
register 0x23 33
Alarm 7 address 00:00 - FF:FF Holding
register 0x24 34
Alarm 8 address 00:00 - FF:FF Holding
register 0x25 35
Alarm 9 address 00:00 - FF:FF Holding
register 0x26 36
Alarm 10 address 00:00 - FF:FF Holding
register 0x27 37
Restore controller factory
parameters
0: No
1: Yes
Holding
register 0x28 38
Sleep mode
0 - O
1 - 99 sleeping time in
seconds
Holding
register 0x29 39
Sound 0: O
1: 1 – 9 sound tone
Holding
register 0x2A 40
Supply temperature display
0: Not shown
1: Shown interchangeably
with the set temperature
Holding
register 0x2B 41
CO2required (ppm) 0 – 99 x 10 ppm Holding
register 0x2C 42
CO2 allowed dierence 0 – 99 x 10 ppm Holding
register 0x2D 43
SET Temperature 150 – 350 (/10) Holding
register 0x2F 44

EN | 19STOUCH v2019.1
SET Fan speed (%) 0,20 - 100 Holding
register 0x30 45
SET Fan speed xed 0 - 4 Holding
register 0x31 46
SET Pressure 0 – 999 Pa Holding
register 0x32 47
Display supply temperature - 500 – 1000 (/10) Holding
register 0x34 48
Save parameters 0: No
22: Yes
Holding
register 0x36 49
0..10 VDC holdback 0 – 120 Holding
register 0x37 50
0..10 VDC Disable / Enable 0: OFF
1: ON
Holding
register 0x38 51
Current fan speed (%) 0 – 100 % Input
register 0x01 1
Current xed fan speed 0 – 4 Input
register 0x02 2
Temperature Setpoint 150 – 350 °C (/10) Input
register 0x03 3
Current Temperature - 500 – 1000 (/10) Input
register 0x04 4
Pressure Setpoint 0 – 999 Pa Input
register 0x05 5
Current pressure 0 – 999 Pa Input
register 0x06 6
CO2Setpoint 0 – 999 ppm Input
register 0x07 7
Current CO20 – 999 ppm Input
register 0x08 8
Alarm 1 address 0/1 Coil 0x01 1
Alarm 2 address 0/1 Coil 0x02 2
Alarm 3 address 0/1 Coil 0x03 3
Alarm 4 address 0/1 Coil 0x04 4
Alarm 5 address 0/1 Coil 0x05 5
Alarm 6 address 0/1 Coil 0x06 6
Alarm 7 address 0/1 Coil 0x07 7
Alarm 8 address 0/1 Coil 0x08 8
Alarm 9 address 0/1 Coil 0x09 9
Alarm 10 address 0/1 Coil 0x0A 10
To save conguration parameters, write 22 to the register 49, then settings are saved to
EEPROM memory, controller reloads.

20 | EN STOUCH v2019.1
18. ALARMS
A– Alarm.
– Warning.
18.1. ECO AUTOMATION ALARMS
INDICATION VALUE (FOR ALARM DESCRIPTION PLEASE REFER TO THE UNIT
TECHNICAL MANUAL)
.01 Activated heat exchanger antifreeze protection
A.02 External protection activated for example, re emergency exit, lter contamination
(pressure rely activated), fans
A.03 Return water critical temperature
A.04 “P-mA” of water heater
.05 Low unit’s power voltage
A.06 Extracted air temperature sensor fault
A.0 Supply air temperature sensor fault
A.08 Return water temperature sensor fault of water heater
A.09 Ambient air temperature sensor fault
18.2. PRV AUTOMATION ALARMS
INDICATION VALUE (FOR ALARM DESCRIPTION PLEASE REFER TO THE UNIT
TECHNICAL MANUAL)
.01 Heat exchanger antifreeze protection activated
A.02 Fire protection activated
A.03 Clogged lters
A.04 Fan fault
.05 Low voltage
A.06 DTJ (100) temperature sensor alarm fault
A.0 Exhaust air temperature sensor fault
A.08 Supply air temperature sensor fault
.09 DTJ (100) humidity sensor fault
A.10 Return water temperature sensor fault
A.11 Ambient air temperature sensor fault of water heater
A.12 Overheat
A.13 Rotor failure
A.14 Low air humidity
Other manuals for Stouch
4
Table of contents
Languages:
Other Salda Control Unit manuals