
13
USER MANUAL SLC CUBE4 7.5 kVA to 20 kVA - UNINTERRUPTIBLE POWER SUPPLY-
In terms of charging the batteries, this will occur when the UPS
is working in normal mode (AC voltage network present, AC/DC
rectifier operating). The UPS has a reducer converter ("buck"),
which is supplied by the DC bus voltage, adjusting it to the re-
quired levels for charging the batteries. This battery charging
includes 2 basic stages, or even 3 (depending on the type of
battery):
•Constant current: the set charge current must not be ex-
ceeded, and the output voltage of the charger will be dy-
namically adjusted to achieve this allocation.
•Constant voltage: once the battery floating voltage is
reached, the charge current will decrease. This floating
voltage must be maintained in normal mode, a voltage that
will be readjusted depending on the temperature.
•Quick charge or "boost" voltage: depending on the type of
battery (chemistry), an intermediate stage can be config-
ured, after charging at constant current and before allo-
cating continuous float voltage, which consists of supplying
the batteries with a voltage that is higher than the floating
voltage for a limited time, in order to obtain a quicker and
more efficient recharge.
The architecture of the charger is based on a double reducer
converter: from positive and negative semi-buses, positive and
negative battery charge voltages and currents are obtained.
The switching of the charger's IGBTs also consists of a PWM
controlled digitally by DSP.
The charger incorporated as standard in the units allows the
batteries to be recharged for both standard autonomy and for
extended autonomy (greater capacity in Ah installed).
4.4.5. Static bypass
The static bypass switch allows the load or loads to be switched
between the inverter and the emergency (or bypass) network,
and vice versa, without interruption. This bypass line may or
may not be common to the rectifier AC input.
However, and unless otherwise requested - separate networks
-, the phase terminals of both blocks are connected internally at
the factory in order to have a single common input.
When separate power supplies are required, it will be neces-
sary to remove the bridges between phases from both blocks
before connecting the power cables.
The switching of the output load to the bypass line can be or-
dered manually, or it can be activated by the UPS automatic
control in certain emergency situations, such as overload or over-
temperature.
As power switching elements, it uses thyristors (SCR) and re-
lays. Thyristors for connecting/disconnecting the voltage of the
bypass line to the loads, relays for connecting/disconnecting
the inverter voltage.
4.4.6. Manual or maintenance bypass
The manual bypass is used to isolate the UPS from the input
voltage and loads, supplying the load directly from the input net-
work in the event of maintenance or serious faults.
It consists of a switch, supplied as standard and integrated in
the unit, which allows the bypass or emergency line voltage
(common or not to the rectifier AC input) to be connected
directly to the output by simply activating this switch, and
without the intervention of a converter or controlled electronic
device. An auxiliary signal will notify the UPS control that this
switch is activated.
The manual bypass switch supplied in the unit has a mechan-
ical lock that makes it impossible for it to be activated acciden-
tally by unqualified staff.
Before operating this switch, it is necessary to transfer the
power supply of the load on the static bypass via the respec-
tive command from the touchscreen. The transfer of the power
supply to the loads from the static bypass to the manual bypass
is without interruption.
External manual bypass
In addition to the standard internal manual bypass, it is also
possible to optionally install an external manual bypass.
4.4.7. Input-output configurations
The types available are:
•Three-phase/three-phase (with or without separate by-
pass).
•Three-phase/single-phase.
•Single-phase/single-phase (with or without separate by-
pass).
The user is not permitted or authorised to change the
configuration, as this implies the modification of the
plates between the power terminals by adding or removing
them in order to obtain the required configuration, as well as
changes to variables from menus accessed by "Password" via
the control panel.
4.5. OPERATING MODES
The UPS can operate in various operating modes, which can
be reached automatically or forced by a manual action of the
operator. These basic operating modes are:
•Normal mode.
•Battery mode (autonomy mode).
•Bypass mode.
•Maintenance bypass mode.
•ECO mode.
•Frequency converter mode.
•Standby mode.
4.5.1. Normal mode.
For the UPS to work in normal mode, there must be an input
network (input switch activated), output switch activated
(supply for the loads), and there must be batteries in the unit or
connected in an external cabinet.
In this double conversion mode, the rectifier works powered by the
AC network and supplying direct voltage to the inverter (DC bus). The
inverter converts the DC voltage into a stabilised sine wave, con-
necting to the loads via its static switch. The rectifier also supplies
voltage to the battery charger, which keeps the batteries in an op-
timal state of charge.