Samsan Korea CRN-96DO User manual

INSTRUCTION MANUAL
FOR
Dissolved Oxygen Controller
Model : CRN-96DO
S A M S A N K O R E A , L T D .
TEL: +81-(0)31-334-7723 FAX: +81-(0)31-334-7746
h t t p : / / w w w . s a m s a n k o e a . c o m

- 1 -
DIGITAL T PE DO Controller
Thank you very much for your purchasing of
Advanced SAMSAN CROWN CONTROLLER with microprocessor.
This controller has been checked and tested thoroughly to meet prescribed
specifications and certain safety standards by our inspector before ex-factory,
however, surely check the state of controller outside and accessaries when delivered.
Also Read all instruction manuals and understand basic functions & full operating
methods for complete use.
1. FEATURES
Advanced SAMSAN CROWN CONTROLLER with microprocessor
Condensed in a compact DIN size (96×96m/m), versatile functions provide more
simplicity in operation and more efficiency in performance, in addition to accurate
monitoring results.
With the appropriate sensors and accessaries, SAMSAN CROWN CONTROLLER can
serve as the most suitable and effective cost monitoring system to meet process,
waste water and control applications.

- 2 -
1-1
With microprocessored controller's various functions and design of one touch
button, you can
get more effective, reliable data and very simple setting.
1-2 Designed for using out-put of signal and alarm
(DC 4~20㎃ or 1~5V and others)
1-3 With 3 Digit Digital Display, Reading & setting are very simple by appearance of
each message.
1-4 Isolator is equipped for transmission of stable data with isolated DC 4~20㎃ or
1~5V output and you can connect with personal computer and data logger
directly.
1-5 Designed to set high and low alarm for controlling of water quality in process,
waste water and your applications.
1-6 Equipped with Automatic Temperature Compensation for more accurate
monitoring results and appearance.
1-7 DIN (96×96m/m) size for simple installation and maintenance.
1-8 Equipped with power switch for protection of controller by ON/OFF of power
supply while setting or A/S.
1-9 Equipped with EEPROM, SAMSAN CROWN CONTROLLER can hold all set
values of preset parameters while power is OFF and when power become ON,
they can continue to measure and monitor with all values set before.
2. SPECIFICATIONS
2-1 DO CONTROLLER
Model
CRN-96DO
Range
0.0 ~ 2..0 ppm
( OPTION: 0.0 ~ 20.0 ppm )
SA(Sensitivity Adjustment)
0.1 ~ 1.0 ppm ( ± 0.5 ppm )
Shift
± 2.0 ppm
Accuracy
± 2% Full Scale
Ambient Temperature
-5
℃
~ 45
℃
Output
DC 4~20mA ( Option: Isolation )
Alarm
High, Low Relay ( 1a1b )
Panel Cut
92 (W) × 92 (H) mm
Power Source
AC 100/220V ±10%, 50/60㎐

- 3 -
2-2 Cable : This cable is special for DO controller and used to connect between
the controller and connector box.
(1) Model : SC-20
(2) Size : 6
ψ
(3) Length : 10m ( standard ), Max. extension : 20m ( option )
2-3 Connector box
(1) Model : SCB-20
(2) In case of over than 10m between controller and electrode holder, install
with connector box near electrode holder and connect with SAMSAN
special cable surely in connection between connector box and controller.
2-4 DO Electrode ( DO Chip )
(1) Model : 5401
(2) Liquid Temp. : -5 ~ 45
℃
(3) Type : Galvanic electrode
(4) KCL non-filling type
2-5 DO Probe
(1) Model : SP-10 ( Submersible type )
(2) Mat'l : PP
(3) Temp. of sampling liquid : -5 ~ 45
℃
(4) Holder length : 1 M ( Standard ), 1.5M, 2M, 2.5M, 3M ( Option )
※
Flow-throw type available
2-6 Bracket
(1) Model : SB-10
2-7 Standard solution (option) : DO standard powder 0.0ppm ( Na2SO3)
( Use Na2SO3diluted with 1g in distilled
water 50cc )

- 4 -
3. NAME OF PARTS
3-1 Display : d
isplay of measured value, set-value, parameter's set contents
3-2 State lamps
(1) MEAS : when measuring, LED lamp on
(2) CAL : when calibration, CAL switch-on and lamp on,
HIGH/LOW Relay off
(3) DISPLA
LOW : when set-value(related with LOW) is appeared, lamp on
LOW set / SA / SHIFT
HIGH : when set-value(related with HIGH) is appeared, lamp on
HIGH set / SA / SHIFT
(4) ALARM
LOW : when LOW ALARM, lamp on
HIGH : when HIGH ALARM, lamp on
3-3 Function buttons
(1) MEAS : set MODE
→
measuring MODE
CAL on
→
CAL off
(2) MODE : using when reading and changing of set-value
(3) UP : using when changing of set-value in set-MODE
(4) SHIFT : using when changing of figure's place
(5) ENTER: using when finishing of setting
1. DISPLAY
2. STATE LAMPS
3. FUNCTIONS
4. CAL VOLUME

- 5 -
3-4 CAL volume
: used when calibration with buffer solution
(1) CAL : when CAL button on, LOW /HIGH Relay off and stop of
alarm & all kinds of controlling
(2) ZERO(VR) : using when calibration of 0.0ppm (ZERO)
(3) SPAN(VR) : using when calibration of 12.0ppm (SPAN)
4. OPERATION
4-1 Setting flow chart
4-2 Changing method
(1) used when increasing of twinkling figure
UP
(2) used when moving of twinkling figure to right side
SHIFT
(3) used when saving of setting value
ENTER
After changing of set-value, if ENTER button is not pushed,
it will be returned to former set-value.
MEAS
(enter to state of measurement)
push MODE button
LOW set (LOW display lamp-on)
HIGH set (HIGH display lamp-on)
LOW SA (LOW display lamp-on)
LOW SHIFT (LOW display lamp-on)
HIGH SA (HIGH display lamp-on)
HIGH SHIFT (HIGH display lamp-on)
MODE
MODE
MODE
MODE
MODE
MODE
push MODE button over than 5 seconds
․output relay off in setting routine
․If any button is not operated for
30 seconds in setting routine,
it will be automatically changed to
measuring mode

- 6 -
5. S.A.(Sensitivity Adjustment) & SHIFT
5-1 S.A.(sensitivity adjustment)
: When ON and OFF with 1 point, out-put is chattered and easy to
receive influences of any noises, however, if you set the width of
S.A. as following diagram, stable control is possible.
Setting is possible from 0.1ppm to 4.0ppm (±2.0ppm) and it was set as
0.1ppm when ex-factory.
Set example) LOW set : occasion of lower limit 5.0ppm
S.A : 0.2ppm
SHIFT : 0.0ppm
Set example) HIGH set : occasion of upper limit 8.0ppm
S.A : 0.4ppm
SHIFT : 0.0ppm
S.A 0.2 ppm
▲
4.9ppm
5.1ppm
ON
OFF
O
U
T
P
U
T
5.0ppm
setting value
8.0ppm
setting value
▲
8.2ppm
ON
OFF
O
U
T
P
U
T
▲
7.8ppm
ON
S.A 0.4 ppm

- 7 -
5-2 SHIFT
: A constant error is occured against target value when ON and OFF.
This error is called as off-set and this off-set can be controlled to
target value without any errors, if you use this SHIFT function in
SAMSAN CROWN controllers.
Setting is possible from 0.0ppm to 2.0ppm and it was set as 0.0ppm
when ex-factory.
Set example) LOW set : 5.0ppm
S.A : 0.2ppm
SHIFT : -0.1ppm
Set example) HIGH set : 8.0ppm
S.A : 0.4ppm
SHIFT : +0.2ppm
▲
8.4ppm
ON
OFF
S.A 0.4 ppm
8.0ppm
sett ng value
O
U
T
P
U
T
S.A 0.2 ppm
▲
4.8ppm
ON
OFF
5.0ppm
sett ng value
O
U
T
P
U
T

- 8 -
6. INSTALLATION & WIRING
6-1 Installation environment
: Install at good conditioned place as follows
(1) Airy place ( ambient temperature : -5
℃
~40
℃
)
(2) Adequate protection should be provided to keep the controller from
being exposed to direct sunlight or rain
(3) Moistureless place that ambient humidity is less than 85%
(4) A place without the mechanical vibration
(5) A place with sufficient space for easy maintenance and wiring
(6) A place without dust, corrosive gas and any influences of electronic
power
6-2 Installation method
(1) Panel mounting type
※
Refer to out-drawing for panel cutting
(2) Insert 2 eas of mount bracket in the upper and lower holes and
fasten the bolts with +
○
driver.
6-3 Connection of sensor cable
:
Cable connector should be kept in dry and clean to get a stable value.
(1) Standard cable length is 10m.
In case of extension over than 10m, use the connector box and
exclusive cable for DO supplied by SAMSAN CROWN.
(2) Install at the place without any influences due to motors of machinery.
(3)
Lead cable of sensor should be fully left for calibration of standard
solution
and
checking of sensor.
(4) Contact to our technical sales dept. in case of using Temperature
Compensation electrode.
6.8 k
Ω
at 25
℃
or 500
Ω
at 25
℃
A : Anode
K : Cathode
T. T : Temp. compensation electrode terminal
E : Shield cable
※
Refer to following drawing for wiring to terminal.
6-4 Connection of output cable
(1) Output signal of DC 4~ 20mA against measuring range come out.
※
Max. load resistance : 500
Ω
0.00 ppm
→
4 mA
3.75 ppm
→
8 mA
7.50 ppm
→
12 mA
11.25 ppm
→
16 mA
15.00 ppm
→
20 mA

- 9 -
(2) Output
6-5 Connection of power cable
: Connect with correct voltage
(1)
Power switch is attached to terminal board in the back of the controller
(2) Surely ground for your safety
7. CALIBRATION & OPERATION
Prior to operating, adjust controller & using sensor with standard solution .
Regular calibration is surely needed because character of sensor changes
when used for long time.
7-1 ZERO Calibration
(1) Remove DO chip from probe.
(2) Set indicating value on window as 0 ppm.
(3) Set DO chip in probe again.
7-2 SPAN Calibration ( atmosphere calibration )
: If indicating value is stabilized after openning the probe to the
atmosphere, set the indicating value as 12.0 ppm with span volume.
8. REPAIR
8-1 Controller should be calibrated once in a month.
8-2 Electrode should be cleaned once in a week ( once in a day in case
of using in vilulent waste water ).
8-3 If sensitivity & response of electrode is bad, clean DO chip with
gause wetted by alcohol as soft as possible.
Rec rder r P r
PID C ntr ller
C ntr ller
+
○
+
○
+
○
-
○
C ntr ller
+
○
-
○
-
○
-
○
Rec rder r P r
PID C ntr ller
Rec rder r P r
PID C ntr ller
※
Whole load resistance of all
output receiver is max. 500
Ω
.

- 10 -
8-4 If span calibration isn't operated, charge to new DO chip because
it means electrode's life is ended.
9. TROUBLESHOOTING
trouble
cause
remedy
Indicating value is
unstable
Flow speed-down of liquid.
Flow-speed up.
Breakage of diaphragm
the end of DO chip.
Replace.
Induced current by any
influences outside.
- Use the exclusive cable
surely
- Check the ground
Late response.
Stained diaphragm of
DO chip.
Rinse with alcohol.
Faulty connection of
terminal board.
Correct connection.
Indicating Value is
down slowly
Electrode's life was ended.
Replace.
Breakage of diaphragm in
the end of DO chip.
Replace.
Faulty indicating value
(over or low)
Faulty calibration of SPAN.
Calibrate correctly.

- 11 -
10. DIMENSIONS
MIN.
150
MIN. 130
92.0
±
0.5
92.0
±
0.5
91
145
10
PANEL-CUT SIZE (UNIT: mm)
96mm
96mm

- 12 -
11. TERMINAL BOARD
12. INNER STRUCTURE
LOW
HIGH
RELAY
POWER
TRANS
OUTPUT 4-20mA
DO RANGE CARD
ZERO
SPAN
BIAS
ANODE
FUSE 250V/0.5A
1
2
3
4
5
6
7
8
9
LOW
a.(NO)
b.(NC)
COM
HIGH
a.(NO)
b.(NC)
COM
POWER
200/220V
100/110V
ON
OV OFF
220
110
0
LOW ALARM
CONTROL
AC250V 4A
(R-LOAD)
HIGH ALRAM
CONTROL
AC250V 4A
(R-LOAD)
POWER
SOURCE
GROUND
12
13
14
15
16
17
SENSOR
A
K
EARTH
T
T
OUTPUT
+
4-20mA
-
GND
X
T
T
+
-
F
18
G
DO SENSOR
ATC(OPTION)
Max.500
Ω
Output
10
11
A
Other Samsan Korea Controllers manuals
Popular Controllers manuals by other brands

DINUY
DINUY RE KNT 004 manual

RKC INSTRUMENT
RKC INSTRUMENT THW-3 Series quick start guide

EUTECH INSTRUMENTS
EUTECH INSTRUMENTS WD-19505-40 instruction manual

Belden
Belden Grass Valley Densite 3 Frame Guide to installation and operation

DeZurik
DeZurik POWERRAC R1 Installation and operation manual

Drok
Drok 091029 manual