- 8 -
6. INSTALLATION & WIRING
6-1 Installation environment
: Install at good conditioned place as follows
(1) Airy place ( ambient temperature : -5
℃
~40
℃
)
(2) Adequate protection should be provided to keep the controller from
being exposed to direct sunlight or rain
(3) Moistureless place that ambient humidity is less than 85%
(4) A place without the mechanical vibration
(5) A place with sufficient space for easy maintenance and wiring
(6) A place without dust, corrosive gas and any influences of electronic
power
6-2 Installation method
(1) Panel mounting type
※
Refer to out-drawing for panel cutting
(2) Insert 2 eas of mount bracket in the upper and lower holes and
fasten the bolts with +
○
driver.
6-3 Connection of sensor cable
:
Cable connector should be kept in dry and clean to get a stable value.
(1) Standard cable length is 10m.
In case of extension over than 10m, use the connector box and
exclusive cable for DO supplied by SAMSAN CROWN.
(2) Install at the place without any influences due to motors of machinery.
(3)
Lead cable of sensor should be fully left for calibration of standard
solution
and
checking of sensor.
(4) Contact to our technical sales dept. in case of using Temperature
Compensation electrode.
6.8 k
Ω
at 25
℃
or 500
Ω
at 25
℃
A : Anode
K : Cathode
T. T : Temp. compensation electrode terminal
E : Shield cable
※
Refer to following drawing for wiring to terminal.
6-4 Connection of output cable
(1) Output signal of DC 4~ 20mA against measuring range come out.
※
Max. load resistance : 500
Ω
0.00 ppm
→
4 mA
3.75 ppm
→
8 mA
7.50 ppm
→
12 mA
11.25 ppm
→
16 mA
15.00 ppm
→
20 mA