MODBUS
Address Description Code Unit Step Min. Max. Default*
40001 Superheat set-point SH °F0.1 0.5 99.9 10.8 (108)
40003 Start open ratio bIr % 1 0 100 0
40004 Start open ratio duration time Sdt Sec 1 0 600 0
40005 P:Proportional gain dFr %0.1 0.1 99.9 3.0 (30)
40006 I: Integral time Irt Sec 1 0 999 20
40007 D: Derivative time drt Sec 1 0 999 4
40008 Low SH alarm mode LS 0=No use , 1= automatic return, 2=manual return 1
40009 Low SH alarm value LSH °F0.1 0.5 30 0.9 (9)
40010 Low SH alarm delay time LSd Sec 1 1 300 15
40011 Clear low SH alarm LSF °F0.1 1 30.5 5.4 (54)
40012 MOP alarm mode mP 0=No use , 1= automatic return, 2=manual return 1
40013 MOP alarm pressure moP PSIG 0.1 -15 999 130
40014 MOP alarm delay time mPd Min 1 1 15 1
40015 Clear MOP alarm mPF PSIG 1 -15 129 116
40016 High SH alarm mode HS 0=No use , 1= automatic return, 2=manual return 0
40017 High SH alarm value HSH °F 1 10 40 54
40018 High SH alarm delay time HSd Sec 1 1 15 3
40019 Clear high SH alarm HSF °F 1 7 37 49
40021 Freeze prevention alarm mode Fr 0=No use , 1= automatic return, 2=manual return 0
40022 Freeze prevention alarm value FrE °F 1 -40 40 32
40023 Freeze prevention alarm delay time Frd Sec 1 5 200 30
40024 Clear freeze prevention alarm FrF °F 1 35 109 37
40025 Select pumpdown function and delay time Pd Sec 1 0 180 OFF (-1)
40026 Pressure set-point for stopping pumpdown PdP PSIG 1 -7 261 7
40027 Pressure low limit alarm mode LP 0=No use , 1= automatic return, 2=manual return 0
40028 Pressure low limit alarm value LoP PSIG 1 -12 256 0
40029 Low limit pressure alarm delay time LPd Sec 1 5 200 5
40030 Clear low limit pressure alarm LPF PSIG 1 3 261 4
SEC61X SERIES | Electronic Expansion Valve Controller
PARAMETERS
Menu 1 = 1.Pr
*Default as displayed on controller menu. Modbus address value in parenthesis.