Thank you for purchasing this emergency unit. Please read the instructions carefully before use to ensure safe and
satisfactory operation of this product. Please retain these instructions for future reference.
Warning
This is a Class 1 product and must be earthed.
Please read these instructions carefully before
commencing any work.
This unit must be fitted by a competent and qualified
electrician.
Install in accordance with IEE Wiring regulations and
currentBuildingRegulations.
To prevent electrocution switch off at mains supply
before installing or maintaining this fitting. Ensure
other persons cannot restore the electrical supply
without your knowledge.
This emergency unit should be connected to a fused
circuit.
If replacing an existing fitting, make a careful note of
the connections.
This product is not suitable for dimming.
Waste electrical products should not be disposed of
with household waste. Please recycle where facilities
exist. Check with your local authority or retailer for
recycling advice.
TheseproductsshouldnotbefittedtoPIRcircuitsor
short duration timed switches.
This unit is only for use with SAX01-48012
Specification
Layout
• Planthedesiredlayoutofthisfittingcarefully,
ensuring the cables will reach the distance between
the outdoor rated junction box and the light fitting
• Avoidlocatinganycablesinpositionsthatwould
cause a hazard. Position cables and outdoor rated
junction boxes (not supplied) away from areas
where they may be at risk from being cut, trapped or
damaged
• Themainssupplycablemusthaveaminimumcross
sectional area of 1.0mm²
Existing fittings must be completely removed before
installation of a new product. Before removing the
existing fitting, carefully note the position of each set
of wires.
• Undothetwoscrewsattheendoftheunit,remove
the screws and cover and set aside.
• ThisproductusestheLEDdriverincludedwiththe
SAX01-48012.DonotuseanyotherLEDdriverwith
this product.
• Ensurethattheunitisfittedwherethereisadequate
ventilation. It should not be placed on top of the
SAX01-48012.
• Ensurethatthecablesarepulledthroughtheholes
in the cover prior to wiring.
Installation
Having correctly identified the wiring from your existing
light fitting, keep the connection block inside the product
in the following way:
• ConnectacablefromthemainsinputintheLED
drivertothemainsintheEmergencyUnit.
• ConnecttheoutputofthedrivertotheEmergency
Unit(plugA).
• ConnecttheoutputoftheEmergencyUnittotheLED
fitting (plug B).
• Connectthemainswiringtotheunitasshown.
• Thereisatestbuttonlocatedontheoppositesideof
theunittothecover.Usethisperiodicallytocheck
that the unit is working correctly.
Wiring
Check that...
• Youhavecorrectlyidentifiedthewires
• The connections are tight
• No loose strands have been left out of the connection
block.
Voltage : 240V ~ 50Hz
Lamp : 1x16LED
IP rating : 20
Lumens : 250lm in EM mode
Duration : 3hours(180minutes)
Operating Temperature : 10˚C to 50˚C
Maximum Operating Humidity : 90%
Change over Time : Approximately 1s
BatterySpecification : NiCD12.0V1200mAh
Battery Charge Time : ≥24 hours
N
L
L (P)
L (Sw)
E
N
48012
Fitting