SBC PCD7.LR P5 Series User manual

Manual
Document 27-653; version ENG07 | 2019-03-21
PCD7.LRxx-P5
Saia PG5®programmable
room controller

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Manual PCD7.LRxx-PG5
Table of contents
0-1
0
0 Table of contents
0.1 Document history ....................................................................................... 0-5
0.2 Trademarks ................................................................................................ 0-5
1 Graphic overview
1.1 Go to .. ....................................................................................................... 1-1
1.2 PCD7.LRL2-P5 (230 V AC) ....................................................................... 1-2
1.3 PCD7.LRL4-P5 (230 V AC) ....................................................................... 1-3
1.4 PCD7.LRL5-P5 (24 V AC) ......................................................................... 1-4
1.5 PCD7.LRS4-P5 (230 V AC) ....................................................................... 1-5
1.6 PCD7.LRS5-P5 (24 V AC) ......................................................................... 1-6
2 General guidance
2.1 Information on how to use this manual ...................................................... 2-2
2.2 Documents ................................................................................................. 2-3
2.3 Package contents ...................................................................................... 2-4
2.3.1 Storage information ................................................................................... 2-4
2.3.2 Tips for unpacking ...................................................................................... 2-5
2.4 Recommended installation material ........................................................... 2-6
2.5 IP30 protective terminal covers (optional) ................................................. 2-7
2.6 Disposal ..................................................................................................... 2-8
2.7 Information for commissioning ................................................................... 2-9
2.7.1 Safety information ...................................................................................... 2-9
2.8 Introduction ................................................................................................ 2-10
2.8.1 Overview .................................................................................................... 2-10
2.8.2 Room HVAC sample application template ................................................. 2-11
2.8.3 Legacy PCD7.L60x-1 room controller emulation ....................................... 2-12
2.8.4 System compatibility .................................................................................. 2-13
2.8.5 Addressing the room controllers ................................................................ 2-13
2.8.6 Media Backup/Restore .............................................................................. 2-13
2.9 Wiring ......................................................................................................... 2-16
2.9.1 Overvoltage protection for large distances or external lines ...................... 2-17
2.9.2 Addressing inputs and outputs (I/O) .......................................................... 2-17
2.10 Programming ............................................................................................. 2-18
2.11 Installation information for room operating devices ................................... 2-19
3 Room controller / CPU
3.1 Dimensions/device installation ................................................................... 3-2
3.1.1 Dimensions without protective terminal covers .......................................... 3-2
3.1.2 Dimensions with protective terminal covers ............................................... 3-3
3.1.3 Installation position and ambient temperature ........................................... 3-4
3.1.4 Installation on mounting rails ..................................................................... 3-4

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Manual PCD7.LRxx-PG5
Table of contents
0-2
0
3.1.5 Removal from mounting rails ..................................................................... 3-5
3.1.6 Wall mounting ............................................................................................ 3-6
3.1.7 Removal from the wall ............................................................................... 3-6
3.2 Electrical data ............................................................................................ 3-7
3.2.1 PCD7.LRL2-P5, -.LRL4-P5 and -.LRS4-P5 (230 VAC models) ................. 3-7
3.2.2 PCD7.LRL5-P5 and PCD7.LRS5-P5 (24 VAC) ......................................... 3-7
3.3 Power supply and earthing concept ........................................................... 3-8
3.3.1 Devices with a 230 VAC supply ................................................................. 3-8
3.3.2 Devices with a 24 VAC supply ................................................................... 3-9
......... 3-10
3.3.4 Earthing concept ....................................................................................... 3-11
3.4 CPU properties .......................................................................................... 3-12
3.5 General technical details ........................................................................... 3-13
3.6 Firmware/Operating system ....................................................................... 3-14
3.7 System memory structure .......................................................................... 3-15
3.8 System resources ...................................................................................... 3-16
3.8.1 User program in block structure ................................................................. 3-16
3.8.2 Data types/value ranges ............................................................................ 3-17
3.8.3 Resource elements .................................................................................... 3-17
3.8.4 RTC/internal hardware clock...................................................................... 3-17
3.9 LED/operating states ................................................................................. 3-18
3.10 RUN/HALT key ........................................................................................... 3-19
3.10.1 Multiple uses for the RUN/HALT key ......................................................... 3-19
3.10.2 Restart the controller with RUN/HALT button ............................................ 3-20
3.11 Watchdog (software) .................................................................................. 3-21
4 Inputs and outputs
4.1 Connection overview and functions ........................................................... 4-2
4.2.1 Use as digital inputs ................................................................................... 4-8
4.2.1.1 Digital input 24 VDC with source operation ............................................... 4-8
4.2.1.2 Digital input 24 VDC with sink operation .................................................... 4-8
4.2.1.3 Digital input as dry contact ......................................................................... 4-8
.......................................... 4-9
4.2.1.5 Programming digital inputs ........................................................................ 4-10
4.2.2 Use as analogue inputs ............................................................................. 4-11
4.2.2.1 Analogue input with 0…10V ...................................................................... 4-11
4.2.2.2 Analogue input as resistance measurement .............................................. 4-11
4.2.2.3 Analogue input as temp. measurement ..................................................... 4-11
........................................................ 4-12
4.2.2.5 Programming analogue inputs ................................................................... 4-14
.............................. 4-14
4.2.2.7 Status registers .......................................................................................... 4-15
4.3 ROx/TOx - Digital outputs .......................................................................... 4-16

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Manual PCD7.LRxx-PG5
Table of contents
0-3
0
4.3.1 ROx - Relay outputs .................................................................................. 4-16
4.3.2 TOx - Triac outputs .................................................................................... 4-18
4.3.3 Current limitations for the terminal «24 VAC Out» ..................................... 4-18
4.3.4 Connection examples for Triac Outputs ..................................................... 4-19
4.3.4.1 Triac outputs 24VAC external power supply .............................................. 4-19
4.3.4.2 Triac outputs 24VAC internal powered ...................................................... 4-20
4.3.4.3 Triac outputs 230VAC external power supply ............................................ 4-21
4.4 AOx - Analogue outputs ............................................................................. 4-22
4.5 Connection examples ............................................................................... 4-23
5 Communication interfaces
5.1 PGU (Micro-USB port) programming interface .......................................... 5-2
5.2 Using the SBC S-Bus protocol ................................................................... 5-3
5.3 RS-485 interfaces (ports 0 + 1) in general ................................................. 5-4
5.3.1 Schematic diagram of a PCD7.LRxx-P5 room controller in
an RS-485 bus with terminating resistors .................................................. 5-5
5.3.2 Bus cable for serial S-Net (S-Bus/RS-485) ................................................ 5-6
5.3.3 Requirements for the S-Bus (RS-485) shielding ........................................ 5-7
5.3.4 RS-485 interface port0 ............................................................................... 5-7
5.3.5 RS-485 interface port 1 .............................................................................. 5-8
5.3.5.1 Sample system architecture for I/O extension ........................................... 5-8
5.3.5.2 Limitations for I/O extension with E-Line modules ..................................... 5-8
5.3.5.3 Recommendations for use with lighting or blind control ............................ 5-11
5.3.5.4 DALI with E-Line (PCD1.F2611-C15 module) ............................................ 5-13
5.4 Modbus on PCD7.LRxx-P5 RS-485 interfaces .......................................... 5-14
5.4.1 Limitations .................................................................................................. 5-14
5.4.2 Addressing ................................................................................................. 5-15
5.4.3 Media Mapping .......................................................................................... 5-17
5.5 Sylk bus ..................................................................................................... 5-23
5.5.1 Key information about the bus ................................................................... 5-23
5.5.2 Recommendations regarding the PCD7.LR-TR40x/TR42x wall modules . 5-24
5.5.3 Devices and Programming/FBoxes ........................................................... 5-24
6 Conguration
................................................... 6-2
6.1.1 Requirement for operation ......................................................................... 6-2
6.1.2 General ...................................................................................................... 6-2
................................................................... 6-4
................................................................ 6-4
............................................................... 6-4
6.2.3 Media mapping view .................................................................................. 6-5
6.2.4 Digital/analogue universal inputs ............................................................... 6-6
6.2.5 Relay outputs ............................................................................................. 6-8
6.2.6 Triac outputs .............................................................................................. 6-9
6.2.7 Analogue outputs ....................................................................................... 6-10

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Manual PCD7.LRxx-PG5
Table of contents
0-4
0
7 Room operating devices
7.1 Overview of room operating devices ......................................................... 7-2
7.2 Sylk bus FBoxes ........................................................................................ 7-4
7.2.1 Initialising the Sylk bus interface ................................................................ 7-4
7.2.2 PCD7.LR-TR40-xxx wall device without LC display .................................. 7-5
7.2.3 PCD7.LR-TR42-xxx wall device with LC display ....................................... 7-6
...................... 7-9
.................................. 7-12
7.3 PCD7.D1000 S-Bus/Modbus room operating device
on RS-485 interface ................................................................................... 7-13
8 Maintenance
8.1 Maintenance-free ....................................................................................... 8-1
A Appendix
A.1 Symbols .....................................................................................................A-2
A.2 RS-485 signal level ....................................................................................A-3
A.3 Installation regulations and relay contacts .................................................A-4
A.3.1 Installation regulations for switching low voltages .....................................A-4
A.3.2 Switching inductive loads ...........................................................................A-4
A.3.3 Information from the relay manufacturers on dimensioning
the RC element ..........................................................................................A-5
A.4 Sensor properties ......................................................................................A-7
A.4.1 Sensor input accuracy ...............................................................................A-7
A.4.2 Sensor property tables ...............................................................................A-7
..............................................................................A-10
...............................................................A-11
..................................................................A-11
A.6 Glossary .....................................................................................................A-12
A.7 Contact ......................................................................................................A-13

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Manual PCD7.LRxx-PG5
Table of contents
0-5
0
0.1 Document history
Version Changed Published Chapter Remarks
ENG02 2018-06-07 2018-06-07 Manual - New document
ENG03 2018-07-17 2018-07-17 5.3.5.6 -
ENG04 2018-09-21 2018-09-21 3.2.2
4.2
4.2.3
5.4
7
Manual
- MaxPower consumption in W
-
- Programming
-
- Operating devices more detail
- Various pictures changed and and details corrected
throughout the book
ENG05 2018-11-12 2019-01-14 3.9
5.4.3
A.4.2
4
Manual
- Corex table operating status
- Media mapping table corex
-
- Chapter optimization
- Spelling correction
ENG06 2019-02-07 2019-02-07 3.3.3 - Correction: max. Current and connection examples
change
ENG07 2019-03-21 2019-03-22 4.5
5.5
-
corrected or supplemented.
-
0.2 Trademarks
Saia PCD®is a registered trademark of Saia-Burgess Controls AG.
Subject to technical changes in line with the latest technological developments.
Saia-Burgess Controls AG, 2019. © All rights reserved.
Published in Switzerland

1 Graphic overview
1.1 Go to ..
1.2 PCD7.LRL2-P5 (230 V AC)
1.3 PCD7.LRL4-P5 (230 V AC)
1.4 PCD7.LRL5-P5 (24 V AC)
1.5 PCD7.LRS4-P5 (230 V AC)
1.6 PCD7.LRS5-P5 (24 V AC)
1.1 Go to ..
The graphic overviews show some of the most important points in the operating
instructions.
Clicking the descriptive text for the connections allows you to jump directly to the
corresponding section of the document.
The numbers below the descriptive text correspond to the section numbers, with
full stops separating individual chapters and sections.
Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Go to ..
Graphic overview
1-1
1

RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
RUN/HALT
Sylk Bus
RS485 / Port 1
UI0…
0-10 V
GND
Dig. NTC V
TN T~ TO0TNTO1 TO2 TNTO3
RS485 / Port 0
C1+/D A +
DB-
GND
C1-
AO0…
GND
0-10V
V
Power Supply
24 VAC
Out
---
230 V
24 VAC
---
USB
T2 R2 T1 R1 !
1
L
2
N
3
24V~
4
24V0
5
24V~
6
24V0
7
TN
8
T~
9
TO0
10
TN
11
TO1
12
TO2
13
TN
14
TO3
15
RC3
16
RO3
17
IN3
18
RN
19
RN
20
IN0
21
RO0
22
IN1
23
RO1
24
IN2
25
RO2
/DA+
26
DB-
27
GND
28
24V~
29
/DA+
62
DB-
63
GND
64
WM1
30
WM2
31
AO0
32
AO1
34
AO2
36
AO3
38
AO4
40
AO5
42
GND
33
24V~
35
GND
37
24V~
39
GND
41
24V~
43
24V~
44
GND
46
UI1
48
UI2
50
GND
52
UI5
54
LED
45
UI0
47
GND
49
UI3
51
UI4
53
GND
55
UI6
56
GND
58
UI9
60
UI7
57
UI8
59
GND
61
16 17 18 19 20 21 22 23 24 25
16 17 18 19 20 21 22 23 24 25
8 9 10 11 12 13 14
7 8 9 10 11 12 13 14
5 6
5 6
1 2
1 2
62 63 64
44 46 48 52 5450
45 47 49 53 5551
32 34
33 35
30 3126 27 28 29
1.2 PCD7.LRL2-P5 (230 V AC)
2analogue outputs
4.4
Port 1 (RS-485)
5.3
6universal inputs
4.2
Sylk bus
5.5
Port 0 (RS-485)
5.3
4relay outputs
4.3.1
USB port
5.1
RUN/HALT key
3.10
4triac outputs
4.3.2
24 V AC
supply
voltage output
3.3.3
LEDs for
• Communication
• Error
• Power
3.9
Supply
230 V AC
3.3.1
Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Go to ..
Graphic overview
1-2
1

RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
RUN/HALT
Sylk Bus
RS485 / Port 1
UI0…
0-10 V
GND
Dig. NTC V
TN T~ TO0TNTO1 TO2 TNTO3
RS485 / Port 0
C1+/D A +
DB-
GND
C1-
AO0…
GND
0-10V
V
Power Supply
24 VAC
Out
---
230 V
24 VAC
---
USB
T2 R2 T1 R1 !
1
L
2
N
3
24V~
4
24V0
5
24V~
6
24V0
7
TN
8
T~
9
TO0
10
TN
11
TO1
12
TO2
13
TN
14
TO3
15
RC3
16
RO3
17
IN3
18
RN
19
RN
20
IN0
21
RO0
22
IN1
23
RO1
24
IN2
25
RO2
/DA+
26
DB-
27
GND
28
24V~
29
/DA+
62
DB-
63
GND
64
WM1
30
WM2
31
AO0
32
AO1
34
AO2
36
AO3
38
AO4
40
AO5
42
GND
33
24V~
35
GND
37
24V~
39
GND
41
24V~
43
24V~
44
GND
46
UI1
48
UI2
50
GND
52
UI5
54
LED
45
UI0
47
GND
49
UI3
51
UI4
53
GND
55
UI6
56
GND
58
UI9
60
UI7
57
UI8
59
GND
61
1 2 5 6 7 8 9 10 11 12 13 14 16 17 18 19 20 21 22 23 24 25
33 35 37 39 41 43
47 49 53 55 57 59 6151
26 27 28 29 30 31 32 34 36 38 40 42 46 48 52 54 56 58 6050 62 63 64
1.3 PCD7.LRL4-P5 (230 V AC)
6analogue outputs
4.4
Port 1 (RS-485)
5.3
10universal inputs
4.2
Sylk bus
5.5
Port 0 (RS-485)
5.3
4relay outputs
4.3.1
USB port
5.1
RUN/HALT key
3.10
4triac outputs
4.3.2
24 V AC
supply
voltage output
3.3.3
Supply
230 V AC
3.3.1
LEDs for
• Communication
• Error
• Power
3.9
Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Go to ..
Graphic overview
1-3
1

RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
RUN/HALT
Sylk Bus
RS485 / Port 1
UI0…
0-10 V
GND
Dig. NTC V
TN T~ TO0TNTO1 TO2 TNTO3
RS485 / Port 0
C1+/D A +
DB-
GND
C1-
AO0…
GND
0-10V
V
Power Supply
24 VAC
Out
---
230 V
24 VAC
---
USB
T2 R2 T1 R1 !
1
L
2
N
3
24V~
4
24V0
5
24V~
6
24V0
7
TN
8
T~
9
TO0
10
TN
11
TO1
12
TO2
13
TN
14
TO3
15
RC3
16
RO3
17
IN3
18
RN
19
RN
20
IN0
21
RO0
22
IN1
23
RO1
24
IN2
25
RO2
/DA+
26
DB-
27
GND
28
24V~
29
/DA+
62
DB-
63
GND
64
WM1
30
WM2
31
AO0
32
AO1
34
AO2
36
AO3
38
AO4
40
AO5
42
GND
33
24V~
35
GND
37
24V~
39
GND
41
24V~
43
24V~
44
GND
46
UI1
48
UI2
50
GND
52
UI5
54
LED
45
UI0
47
GND
49
UI3
51
UI4
53
GND
55
UI6
56
GND
58
UI9
60
UI7
57
UI8
59
GND
61
3 4 5 6 7 8 9 10 11 12 13 14 16 17 18 19 20 21 22 23 24 25
33 35 37 39 41 43
47 49 53 55 57 59 6151
26 27 28 29 30 31 32 34 36 38 40 42 46 48 52 54 56 58 6050 62 63 64
1.4 PCD7.LRL5-P5 (24 V AC)
4relay outputs
4.3.1
USB port
5.1
RUN/HALT key
3.10
4triac outputs
4.3.2
24 V AC
supply
voltage output
3.3.3
24 V AC
supply
voltage input
3.3.2
6analogue outputs
4.4
Port 1 (RS-485)
5.3
10universal inputs
4.2
Sylk bus
5.5
Port 0 (RS-485)
5.3
LEDs for
• Communication
• Error
• Power
3.9
Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Go to ..
Graphic overview
1-4
1

AO0…
GND
0-10V
V
UI0…
0-10 V
GND
Dig. NTC V
RS485 / Port 0
/D A +
DB-
RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
TN T~ TO0 TN TO1
RUN/HALT
Power Supply
---
230 V In
24 VAC In
24 VAC Out
Sylk Bus
RS485 / Port 1
USB
T1 R1 T0 R0 !
1
L
2
N
3
24V~
4
24V0
5
TN
6
T~
7
TO0
8
TN
9
TO1
10
RO3
11
IN3
12
RN
13
RN
14
IN0
15
RO0
16
IN1
17
RO1
18
IN2
19
RO2
AO0
26
24V~
27
GND
28
AO1
29
AO2
30
24V~
31
UI0
34
GND
35
UI1
36
/DA+
40
DB-
41
GND
42
UI2
37
GND
38
UI3
39
GND
32
AO3
33
WM1
20 WM2
21 24V~
22
/DA+
23 DB-
24 GND
25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
40
41
4226 27 28 29 30 31 32
33
34
35
36
37
38
39
20 21 22
23 24 25
1.5 PCD7.LRS4-P5 (230 V AC)
4analogue outputs
4.4
Port 1 (RS-485)
5.3
4universal inputs
4.2
Sylk bus
5.5
Port 0 (RS-485)
5.3
Supply
230 V AC
3.3.1
4relay outputs
4.3.1
USB port
5.1
RUN/HALT key
3.10
2
triac outputs
4.3.2
Supply
voltage
output
24 V AC
3.3.3
LEDs for
• Communication
• Error
• Power
3.9
Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Go to ..
Graphic overview
1-5
1

AO0…
GND
0-10V
V
UI0…
0-10 V
GND
Dig. NTC V
RS485 / Port 0
/D A +
DB-
RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
TN T~ TO0 TN TO1
RUN/HALT
Power Supply
---
230 V In
24 VAC In
24 VAC Out
USB
Sylk Bus
RS485 / Port 1
T1 R1 T0 R0 !
1
L
2
N
3
24V~
4
24V0
5
TN
6
T~
7
TO0
8
TN
9
TO1
10
RO3
11
IN3
12
RN
13
RN
14
IN0
15
RO0
16
IN1
17
RO1
18
IN2
19
RO2
AO0
26
24V~
27
GND
28
AO1
29
AO2
30
24V~
31
UI0
34
GND
35
UI1
36
/DA+
40
DB-
41
GND
42
UI2
37
GND
38
UI3
39
GND
32
AO3
33
WM1
20 WM2
21 24V~
22
/DA+
23 DB-
24 GND
25
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
40
41
4226 27 28 29 30 31 32
33
34
35
36
37
38
39
20 21 22
23 24 25
1.6 PCD7.LRS5-P5 (24 V AC)
Supply
24 V AC
3.3.2
4relay outputs
4.3.1
USB port
5.1
RUN/HALT key
3.10
2
triac outputs
4.3.2
4analogue outputs
4.4
Port 1 (RS-485)
5.3
4universal inputs
4.2
Sylk bus
5.5
Port 0 (RS-485)
5.3
LEDs for
• Communication
• Error
• Power
3.9
Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Go to ..
Graphic overview
1-6
1

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
General guidance
2-1
2
2 General guidance
2.1 Information on how to use this manual
2.2 Documents
2.3 Scope of supply
2.4 Recommended installation material
2.5 IP30 protective terminal covers (optional)
2.6 Disposal
2.7 Information for commissioning
2.8 Introduction
2.9 Wiring
2.10 Programming
2.11 Installation information for room operating devices

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Information on how to use this manual
General guidance
2-2
2
2.1 Information on how to use this manual
This manual describes the technical details of the components. The meaning of
the symbols and abbreviations used in this manual and general technical informa-
tion can be found in the Appendix.
This section aims to help you identify and implement the basic principles of plan-
ning and installing control systems.
-
shooting are covered in the relevant sections.
Example:
PCD7.LRSx-P5 refers to devices PCD7.LRS4-P5 and PCD7.LRS5-P5.

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Documents
General guidance
2-3
2
2.2 Documents
on the following websites.
Support: www.sbc-support.com
PCD homepage: www.saia-pcd.com
The following documents are recommended as supplements to this manual:
Subject Document number
Data sheets
PCD7LRxx-P5 PG5 Room Controller PP31-405
PCD7.LR-TR42x Wall Modules PP31-409
Q.RCU-A-xxxx Analogue Room Control Unit PP31-049
Manuals
Saia PG5®user manual 26-732
Saia PG5®instruction list 26-733
System cables and power supply adapters 26-792
RS-485 network 26-740
PCD7.L63x Room Controller Units 26-859
Others
System catalogue 26-215
Accompanying slip/mounting instructions PCD7.LRx-P5 MU1B-0643GE51 R1217A_MI

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Package contents
General guidance
2-4
2
2.3 Package contents
Package contents
1 PCD7.LRxx-P5 device
1 Plastic bag with connectors
1 Installation instructions
Not included, but required for commissioning etc.
- Connecting cable between PCD7.LRxx-P5 device and PC
USB A male to Micro-USB B male
- Power supply for the PCD7.LRxx-P5 device
- Saia PG5® programming and commissioning software V2.3.x
Included PDF documents:
- «26-732 Saia PG5®User manual»
- «Installation instructions PG5®» (with minimum PC requirements)
- «What´s new»
- Personal Computer
(Minimum requirements, see «Installation instructions PG5®»)
2.3.1 Storage information
95% RH
0% RH
-20 ... +70 °C 0 ... +50 °C
AO0…
GND
0-10V
V
UI0…
0-10V
GND
Dig. NTC V
RS485/ Port 0
/DA +
DB-
RO3 IN3 RNRN IN0 RO0 IN1 RO1 IN2 RO2
TN T~ TO0 TNTO1
RUN/HALT
PowerSupply
---
230V In
24VAC In
24VAC Out
SylkBus
RS485/ Port 1
USB
T1 R1 T0 R0 !
1
L
2
N
3
24V~
4
24V0
5
TN
6
T~
7
TO0
8
TN
9
TO1
10
RO3
11
IN3
12
RN
13
RN
14
IN0
15
RO0
16
IN1
17
RO1
18
IN2
19
RO2
AO0
26
24V~
27
GND
28
AO1
29
AO2
30
24V~
31
UI0
34
GND
35
UI1
36
/DA+
40
DB-
41
GND
42
UI2
37
GND
38
UI3
39
GND
32
AO3
33
WM1
20 WM2
21 24V~
22
/DA+
23 DB-
24 GND
25
1 2 3 4 5 6 7 8 9 1011 12 13 14 15 16 17 18 19
4041 4226 27 28 29 30 31 32 33 343536 37 38 392021 22
2324 25

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Recommended installation material
General guidance
2-5
2
2.3.2 Tips for unpacking
AO0…
GND
0-10V
V
UI0…
0-10V
GND
Dig. NTC V
RS485 / Port 0
/DA +
DB-
RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
TN T~ TO0 TN TO1
RUN/HALT
Power Supply
---
230 V In
24 VAC In
24 VAC Out
Sylk Bus
RS485 / Port 1
USB
T1 R1 T0 R0 !
1
L
2
N
3
24V~
4
24V0
5
TN
6
T~
7
TO0
8
TN
9
TO1
10
RO3
11
IN3
12
RN
13
RN
14
IN0
15
RO0
16
IN1
17
RO1
18
IN2
19
RO2
AO0
26
24V~
27
GND
28
AO1
29
AO2
30
24V~
31
UI0
34
GND
35
UI1
36
/DA+
40
DB-
41
GND
42
UI2
37
GND
38
UI3
39
GND
32
AO3
33
WM1
20 WM2
21 24V~
22
/DA+
23 DB-
24 GND
25
3 4 5 6 7 8 9 1011 12 13 14 15 16 17 18 19
40
41
422627 28 29 30 31 32
33
34
35
36
37
38
3920 21 22
23 24 25
RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
RUN/HALT
Sylk Bus
RS485 / Port 1
UI0…
0-10V
GND
Dig. NTC V
TN T~ TO0 TNTO1 TO2 TN TO3
RS485 / Port 0
C1+/DA +
DB-
GND
C1-
AO0…
GND
0-10V
V
Power Supply
24 VAC
Out
---
230 V
24 VAC
---
USB
T2 R2 T1 R1 !
1
L
2
N
3
24V~
4
24V0
5
24V~
6
24V0
7
TN
8
T~
9
TO0
10
TN
11
TO1
12
TO2
13
TN
14
TO3
15
RC3
16
RO3
17
IN3
18
RN
19
RN
20
IN0
21
RO0
22
IN1
23
RO1
24
IN2
25
RO2
/DA+
26
DB-
27
GND
28
24V~
29
/DA+
62
DB-
63
GND
64
WM1
30
WM2
31
AO0
32 AO1
34 AO2
36 AO3
38 AO4
40 AO5
42
GND
33 24V~
35 GND
37 24V~
39 GND
41 24V~
43
24V~
44 GND
46 UI1
48 UI2
50 GND
52 UI5
54
LED
45 UI0
47 GND
49 UI3
51 UI4
53 GND
55
UI6
56 GND
58 UI9
60
UI7
57 UI8
59 GND
61
1 2 5 6 7 8 9 1011 12 13 14 16 17 18 19 20 21 22 23 24 25
33 35 37 39 41 43
47 49 53 55 57 59 6151
26 27 28 29 30 31 32 34 36 38 40 42 46 48 52 54 56 58 6050 62 63 64
PCD7.LRLx-P5 PCD7.LRSx-P5
Packing the
box
Installation instructions
Electrical
cabinet
Device
connectors
If the following instructions are observed, the packaging and device repair tools
can be reused multiple times.
Procedure:
- Open the box.
- Remove everything from the box. The device is secured to an internal box with
read on!
- Hold this internal box with the device lengthwise using both hands, so that the
long side of the box is facing away from your body.
- Align the two upright ends at the front and back with the bottom of the box, so
that the box is held level in your hands.
- Then unfold the two side parts on the back of the box (to the left and right). The
- Remove the device. (Take care to protect the labels with the barcode.)
- All the packaging parts can be easily stored in the box for reuse.
- It is obligatory to pay attention to the numbers indicated on the connectors. The
connectors must be placed according to the numbers indicated on the device.

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Recommended installation material
General guidance
2-6
2
2.4 Recommended installation material
Pieces Description
2Screws for wall mounting
(screws as per DIN EN ISO 7049 – ST4.2x22 - C - H)
4Screws for mounting the protective terminal covers
(screws as per DIN EN ISO 7049 – ST2.9x9.5 - C (F) - H)
1Mounting rail as per DIN EN 60715 TH35
Cables

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
IP30 protective terminal covers (optional)
General guidance
2-7
2
2.5 IP30 protective terminal covers (optional)
If the controllers are installed outside a control cabinet, the protective terminal
covers must be mounted before being connected to the device’s power supply in
order to achieve IP30 conformity.
IRM-RxC Set of 10 covers
(two covers are needed each PCD7.LRxx-P5,
not included in the PCD7.LRxx-P5 package contents)
The covers can be secured using optional screws for plastic as
per DIN EN ISO 7049 – ST2.9x9.5 - C (F) - H
(not included in package contents).
AO0…
GND
0-10V
V
UI0…
0-10 V
GND
Dig. NTC V
RS485 / Port 0
/D A +
DB-
RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
TN T~ TO0 TN TO1
RUN/HALT
Power Supply
---
230 V In
24 VAC In
24 VAC Out
Sylk Bus
RS485 / Port 1
USB
T1 R1 T0 R0 !
PCD7.LRSx
54
162
54
59
58.4
58.4
162
Order no.:
For small housing
IRM-RSC
without screws
(two needed for each
device)
Small housing with IRM-RSC protective terminal covers, dimensions (in mm)
RO3 IN3 RN RN IN0 RO0 IN1 RO1 IN2 RO2
RUN/HALT
Sylk Bus
RS485 / Port 1
UI0…
0-10 V
GND
Dig. NTC V
TN T~ TO0 TNTO1 TO2 TN TO3
RS485 / Port 0
C1+/D A +
DB-
GND
C1-
AO0…
GND
0-10V
V
Power Supply
24 VAC
Out
---
230 V
24 VAC
---
USB
T2 R2 T1 R1 !
PCD7.LRLx
54
59
58.4
58.4
162
198
54
Order no.:
For large housing
IRM-RLC
without screws
(two needed for each
device)
Large housing with IRM-RLC protective terminal covers, dimensions (in mm)

Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Disposal
General guidance
2-8
2
2.6 Disposal
WEEE Directive 2012/19/EC Waste Electrical and Electronic
Equipment directive
At the end of the product life dispose of the packaging and
product in a corresponding recycling centre. Do not dispose of
the unit with the usual domestic refuse. Do not burn the product !
This manual suits for next models
5
Table of contents
Other SBC Controllers manuals
Popular Controllers manuals by other brands

Komfovent
Komfovent VAV installation manual

IMI
IMI SC Series instruction manual

Curtis Instruments
Curtis Instruments MultiMode 1230 manual

Neousys Technology
Neousys Technology Nuvo-5026E user manual

Linea Research
Linea Research ASC-48 user guide

Rain Bird
Rain Bird CRC-8A Programming and operating instructions