General operations
Normal operation
In an idle mode (standard indication), the display
shows product and customer information. The list
counters are set to 0. The Operation M LED in-
dicates the system’s current operating status.
Fault messages
The N LED flashes and the fault’s signal is sound-
ing, if there are faults (Chapter Reset alarm/fault sig-
nal). The list of faults Faults T displays the mal-
functioning component with element type, element
number and where applicable detector zone.
There may be an device or system fault or the
emergency mode has been activated.
Emergency mode
(fire alarm control panels Integral EvoxX C and In-
tegral EvoxX B)
If the error code xxx/29 is displayed for a fault in
the active system, emergency mode is activated.
Operating and indication functions are reduced; fire
alarm system functions. Call the service depart-
ment/customer service immediately (necessary in-
formation: equipment type and number, customer
number, messages, error codes).
Reset alarm/fault signal
Pressing the button Buzzer silenced D disables
the signal tone of an active alarm or fault message
in the fire alarm control panel; the LED remain lit
up. Any additional alarm or fault message will trig-
ger the alarm and fault signal tones again. Acknow-
ledgement and intervention signal tones cannot be
reset.
Delay
(Depends on programming)
Pressing the button Delay B activates or deactiv-
ates the delay function. During the delay period it is
for instance possible to activate the intervention
function. If delayed switching has been activated
(daytime program), then the button LED is lit, and
if the night program is activated, then the LED is
not lit (night program).
Disabling/actuating elements
(An authorisation code must be entered for this to
be permitted)
Pressing the button of the element type to which
the element belongs H. Enter the number of the
element to be selected using the numerical buttons
of the keypad I. Confirm with the enter button
D.
Pressing the button Off K turns the element off.
Pressing the button On J turns the element on.
Further element operation
Pressing the button of the element type to which
the element belongs H. Enter the number of the
element to be selected using the numerical buttons
of the keypad I. Confirm with the enter button
D.
Pressing the button Other Commands L dis-
plays the list of all available commands. Using the
scroll buttons E/F to scroll through all the
entries in the list. Confirm with the enter button
D.
WARNING
Triggering automatically controlled outputs by maintenance
If extinguishing systems or other critical fire alarm devices are automatically controlled via a
fire alarm control panel, then electrical, mechanical and optical measures must be taken when
carrying out servicing and maintenance work, to ensure that the outputs cannot be accident-
ally triggered. Once the servicing or maintenance activities have been finished, the security
precautions must once again be removed!