SDC S6000DE User manual

S6000DE / S6000KDE
DELAYED EGRESS DEVICE
Verbal Exit Instructions or
Alarm Tone Only and
Digital Countdown Display
Features:
Egress Delay
15 or 30 second exit delay
1 or 2 second nuisance delay
Built-In 3 Function keypad
Alarm and lock reset
1 to 30 second bypass
Sustained bypass
Additional key switch optional
Control Inputs
1 to 30 second request-to-exit and
bypass input with anti-tailgate and
jumper selectable door prop alarm.
Reset
Built-In Annunciation
Armed mode
Nuisance mode
Irreversible egress mode
Release mode
Digital countdown mode
Field selectable voice notification or tone
Field selectable male voice with security
message or female voice with safety
message
Trigger Modes
Egress alarm triggered by Push Bar
Trigger input from external device
field selectable (N/O or N/C)
Code Compliance
IFC International Fire Code
IBC International Building Code
NFPA 101 Life Safety Code
NFPA 1 Uniform Fire Code
California Building Code
Field selectable automatic or manual
power up after emergency release or
power loss. Use of manual power up
complies with California Building Code
(OSHPD) requirements.
P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 1
Any suggestions or comments to this instruction or
product are welcome. Please contact us through
our website or email eng[email protected]m
Choice of Mounting
Recessed mounted
(3 gang metal plaster ring included)
Surface mounted with optional 3 gang
box (DEC-J)
Optional shroud (SHD-J) to be used with
DEC-J surface box.
Rim Mount, Surface Vertical Rod, or Mortise Exit Device
NOTE: SDC 600 Series Power Supply required
Application:
When unauthorized egress is initiated SDC Exit Check® delays egress through the door for 15 seconds (or 30 seconds). Meanwhile,
the person exiting must wait while personnel or security responds. The exit device unlocks after 15 seconds have elapsed, permitting
egress. When powered by a fire control supervised power supply, the exit device will allow egress immediately in an emergency.
The integral verbal message, digital countdown display and sign provide comprehensive and clear instructions of the door operation for
persons without prior knowledge of the exit delay, including the sight and hearing impaired.
The digital keypad eliminates the need to carry and locate keys for reset and bypass functions.
Monitoring Outputs
Egress initiation status
Secure/unsecure status
S6000DE
MODELS
S6000KDE
Exit Check® Applications include:
Restricting the egress of wandering patients
for their own safety.
HUGS® Infant Protection System
compatibility
Restricting the egress of commercial center
patrons for security application needs.
Controlling pedestrian traffic in
transportation facilities, including airport
jetways and tarmacs
Reducing Shoplifting and Employee Theft
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011
INSTALLATION INSTRUCTIONS

P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 2
101-DE/101-KDE Operational Description
The door is closed and secured by latching hardware. The model 101-DE/101-KDE Exit Check controller sends power
to the Delayed Egress Panic Device to lock the door in the secured position. The integral digital display shows the
unlock delay time.
Activation / Alarmed Release :
Activation of the Exit Check’s trigger input initiates the 15 or 30 second unlock cycle . A pre-activation warning tone is
sounded during the short nuisance delay period and the integral display starts counting down. To prevent false alarms,
removing the trigger input activation during the nuisance delay period will silence the pre-activation warning tone, reset
the countdown display and keep the door locked.
Once the nuisance delay period has been exceeded, the Exit Check continues to count down during an irreversible
door release cycle. The integral digital countdown display and voice commands continue to inform the person intending
to exit of the seconds remaining until unlock. An alarm output is activated to alert personnel of an unauthorized exit.
After the 15 or 30 second delay cycle has expired, the Exit Check will remove power to the locking device, allowing free
egress.
Reset / Relock:
The Exit Check can be manually reset by authorized personnel by closing the door and entering a code on the integral
digital keypad, momentarily turning the optional reset key switch to the reset position, or by momentarily activating a
N/O switch connected to the remote reset terminals.
Request to Exit / Authorized Bypass:
A Request-to-Exit (REX) cycle is initiated by entering an authorized REX code on the integral digital keypad,
momentarily turning the optional key switch to the bypass position, or momentarily activating a N/O switch connected to
the REX terminals. The power will be removed from the locking device allowing free egress. After the request to exit
cycle has expired, the Exit Check will automatically reapply power to the locking device to re-secure the door.
Unlocking the door for extended periods of time (Authorized Bypass mode) is accomplished by entering an Authorized
Bypass code on the integral keypad, turning the optional key switch to the Bypass position or placing a maintained
closure across REX terminals. Releasing the closure across the REX terminals will initiate the Request to Exit cycle.
Entering the Reset code on the integral digital keypad, or momentarily turning optional key switch to the Reset position
will immediately reapply power to the locking device to re-secure the door.
(BOCA/Chicago)
The 101-DE/101-KDE operation
complies with BOCA National
Building Code and the Chicago
Building Code: UL Listed, Special
Locking Arrangements and Auxiliary
Locks.
Option
Code
Delay Release
Time
Nusiance
Time
Reset after
Alarm
Lock Status on
Power-Up
Auto/Manual
BD 15 sec
Fixed
0 sec or 1 sec
Selectable
Locked or Unlocked
Selectable
Auto/Manual
BH 30 sec
Fixed
0 sec or 1 sec
Selectable
Locked or Unlocked
Selectable
Auto/Manual
BC 15 sec
Fixed
0 sec
Fixed
Locked or Unlocked
Selectable
Per BOCA compliance, the Exit Check is manually reset by authorized personnel after an alarm by closing the door and
actuating the integral reset key switch or by momentarily closing a contact connected to the remote reset terminals. In
addition, reset will be automatically initiated once the door has been opened, then closed and remains closed for 30
consecutive seconds.
(NFPA-101)
The 101-DE/101KDE operation
complies with the following building
and fire codes: NFPA 101; NFPA 1-
UFC; UBC; IBC; IFC; SBC; California
Building Code. Listings: UL Listed:
Special Locking Arrangements and
Auxiliary Locks; California State Fire
Marshal (CSFM) Listed.
Option
Code
Delay Release
Time
Nusiance
Time
Reset after
Alarm
Lock Status on
Power-Up
Manual
NA 15 sec or 30 sec
Selectable
1 sec or 2 sec
Selectable
Locked or Unlocked
Selectable
Manual
ND 15 sec
Fixed
0 sec or 1 sec
Selectable
Locked or Unlocked
Selectable
Manual
NH 30 sec
Fixed
0 sec or 1 sec
Selectable
Locked or Unlocked
Selectable
Manual 15 sec
Fixed
0 sec or 1 sec
Selectable
Unlocked
Fixed
NC
(CBC Compliant)
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 3
SURFACE MOUNT 3 GANG BOX OVER
EXISTING RECESSED 2 GANG BOX
2) Carefully insert unit and
secure with screws
supplied.
1) Attach optional 3 Gang Surface
Mount Box to existing recessed 2 gang
box using screws supplied.
RECESSED MOUNTING
DRY WALL
KEY CYLINDER INSTALLATION
WITH KEY CYLINDER IN PROPER
POSITION INSIDE SWITCH BLOCK,
TIGHTEN THE SET SCREW TO
LOCK CYLINDER IN PLACE.
1-1/8” KEY CYLINDER
7185SC1-26D-KD
1-1/4” KEY CYLINDER
REQUIRES COLLAR
3-3/4"
1) Cut hole in dry wall to
dimensions shown.
2) Mount wall bracket
over hole.
3) Carefully insert unit and
secure with screws
supplied.
5-3/4”
*PTH-4
Power Supply
SDC 600
Series
PTH-4 = Power Transfer Hinge
PTH-4DPS = Power Transfer Hinge w/DPS
MC-4 = Recessed DPS
*SDC P/N:
Power Supply
SDC 600
Series
*PTH-4
8 Wires
min.
4 Wires (PTH-4) or
6 Wires (PTH-4-DPS)
2 Wires
*MC-4
*MC-4
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 4
RECOMMENDED MOUNTING PROCEDURE
A
A
SLIDE PACKING FOAM BETWEEN WALL
AND UNIT TO PREVENT DAMAGE TO FACEPLATE
USE 1-1/4” SCREWS SUPPLIED WITH
WALL MOUNT FRAME TO HANG UNIT
TEMPORARILY FOR WIRING PURPOSES
VIEW A-A
WIRE UNIT AS SHOWN
(SHOWN WITH NO OPTIONS).
REXTRIG RESET IBO
J4
J6
J1
KEYPAD
RESET
C NO C NO C NO C NO
C NCNOC NCNO
PWR LOCK RED RLY GRN RLY
SP1
TO
PANIC DEVICE FROM
POWER SUPPLY
TO
DPS
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 5
WARNING!
CONTACT THE AUTHORITY HAVING JURISDICTION FOR APPROVAL
PRIOR TO SELECTING DELAY TIME OR PWR-UP SETTINGS
TANDEM UNIT
(PAIR OF DOORS)
WHT
WHT
BLK
RED
WHT
WHT
BLK
RED
PTH-4-DPS
Door 1
SDC 600 Series Power Supply requiredNote:
To
Power
Supply
WHT
WHT
BLK
RED
POWER
TRANSFER
HINGE x DPS
SINGLE
DOOR
}
}
Alarm Secure
}
}
Remote
Access Remote
Reset
Monitor Relays
C – GREEN
N/O - RED
N/C - WHITE
MC-4**
NOTE: All door switches are shown in an
active state (i.e., Door is closed)
101-DE / 101-KDE
PWR LOCK RED RLY TRIG REX RESET
C NOC NOC NO- +- +
GRN RLY
NO C NCNO C NC
IBO
C NO
JUMPER J1 (DOOR PROP)
J1 INSTALLED: The S6000DE/KDE will enter the alarm mode
if the door is held open past the request to exit period.
J1 REMOVED: The S6000DE/KDE will remain unlocked if the
door is held open past the request to exit period. No alarm will
sound.
**
J6
24VDC @ 430mA (Single)
@ 680mA (Tandem)
Monitor Relays
Contact Rating
Operating Temp
Range
Power
Requirements
SPDT (Dry)
1 Amp @12/24VDC (Resistive)
0 C to 70 C
Door Contact OR Power Transfer Hinge by DPS required
for Anti-Tailgate, BOCA, Door Prop, or Forced Door
operation.
C
N/C
N/O
GRY
YEL
101-DE/
101-KDE
PWR LOCK RED R
NO C
TRIG REX RESET
C NOC NOC NO
- +
To
Power
Supply
C NO
IBO
J6
- +
C – GREEN
N/O - RED
N/C - WHT
MC-4**
C – GREEN
N/O - RED
N/C - WHT Door 2
Door 1
C
N/C
N/O
GRY
YEL
C
N/C
N/O
GRY
YEL
PTH-4-DPS
Door 2
Jumper
Installed = IBO input used for DPS
Jumper
Installed = IBO input used for DPS
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011
DIP SWITCH
SETTINGS
15 30
12
15 20 30 1
N/CN/O
UNLOCKED LOCKED
VOICE/TONE
TONE
ONLY
FEMALE
MSG
MALE
MSG
ON
DELAY
TIME
[ON]
[OFF]
1 2 3 4 5 6 7 8
NUISANCE
DELAY
REX/BYPASS
PERIOD
TRIGGER
TYPE
PWR UP
STATE
ALARM
TYPE
MESSAGE
JUMPER J1**

P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 6
Keypad Programming
KEYPAD STATUS LEDS FACTORY PROGRAMMED CODES
1234 Master Code (default)
11 Reset
22 Authorized Exit (Rex)
Function
Pin
Code
33 Bypass
User
No.
01
02
03
04
Output
Code
NA
2
3
4
*
*
*
*
If the factory programmed codes are acceptable for your
installation, no additional programming is required.
System Operation
- -
POWER-UP LOCKED
The door is
locked and
secure
15 30
or
POWER-UP UNLOCKED
The door is unlocked. To enter the
Armed Mode, turn the keyswitch to
Reset or enter the Reset Code
“11 ” on the keypad
*
GREEN Power on, No errors,
No outputs are active
Fast :
Flash
Steady :
No errors,
At least one output is active
RED General error, invalid code
entered
Steady :
YELLOW For ADA requirements, it will light
each time a key is pressed
Flash :
Slow :
Flash
Keypad is in Programming Mode
The door is still locked and secure. The display is counting
down with audible alarm/voice instructions. Once the display
reaches “00”, the door will unlock.
15 14 01
DELAYED EGRESS MODE
...
00 00 The door is unlocked and
has been opened
ALARMED UNLOCKED [Alternating Display]
- -
- -
- -
The door is unlocked and the alarm
is sounding. To return to Armed
Mode, close the door and turn the keyswitch
to Reset or enter the Reset Code “11 “
on the keypad *
RESET [Armed] Keypad Code 11 (Green LED solid)
*
The door is locked and secure
15 30
or
The door is unlocked until the REX timer has expired or
until the door has been opened and then closed.
AUTHORIZED EGRESS [REX] Keypad Code 22 (Green LED Solid)
Door Closed
- -
- -
- -
- - Door has
been opened
*
BYPASS [Maintained Unlock] Keypad Code 33 (Green LED Flashing)
Door Closed
- -
- -
- -
- - Door has
been opened
The door is unlocked indefinitely. To return to Armed Mode, enter the
Reset Code “11 “on the keypad.
*
*
KEY SWITCH BYPASS [Maintained Unlock] (Green LED Solid)
KDE Model Only:
The door is unlocked indefinitely. To return to Armed Mode, close the door and
turn the keyswitch to RESET or enter the Reset Code “11 “ on the keypad.
*
Door Closed
- -
- -
- -
- - Door has
been opened
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

*
Returning the Keypad to Factory Default Settings
Short the Keypad Reset [J4] jumper terminal located on the main controller board.
Press 99# 1234 8# .
Press 3#1#2# . Sets the Output #1 (Reset) for 2 seconds.
Press 3#2#2# . Sets the Output #2 (Auth Exit) for 2 seconds.
Press 3#3#0# . Sets the Output #3 (Bypass) for latching.
Press 1#02#11#2# . Adds user # 2 with a code of 11. [Reset]
Press 1#03#22#3# . Adds user # 3 with a code of 22. [Auth Exit]
Press 1#04#33#4# . Adds user # 4 with a code of 33. [Bypass]
Press to exit programming mode.
Remove the shorting jumper from the Keypad Reset terminal.
*
*
*
*
*
*
*
**
REXTRIG RESET IBO
J4
J6
J1
KEYPAD
RESET
C NO C NO C NO C NO
*
Deleting a User (Option 2)
To delete a user:
Press 2# User Number (2 digits)# .
For example: 2# 05# deletes user 5.
*
*
Erase All Users (Option 8)
To ERASE ALL USERS!!
Press 8# .
All users are erased and the Default Master Code is reset to 1234.
**
Exit Programming Mode
Press .
*
Adding a User / Changing User Pin Codes (Option 1)
To add a user:
Press 1# User Number (2 digits)# New Pin Code# Output Relay # .
For example: 1# 05# 55# 2# adds user 5's pin code as one that will activate authorized exit.
*
Output Relay Codes
2= Reset
3= Authorized Exit
4= Bypass
P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 7
*
Entering Programming Mode
Press 99# Master Code .
For example: 99# 1234 Enters programming mode using the Default Master Code.
*
*
*
** *
*
Changing the Master Code
User 1 is always used as the Master Code and is required to access keypad programming. The Factory
Default Master Code is “1234 ”. It is strongly recommended that a new Master Code is assigned after
installation. WRITE DOWN THE NEW CODE. If the master code is lost, you must use the keypad reset jumper
on the main circuit board to enter programming mode by using the Default Master Code.
To Change the Master Code (User 1)
1) Enter Programming Mode: Press 99# Master Code .
2) Assign new Master Code : Press 1# 01# New Pin Code# Output Relay # .
For example: 99# 1234 1# 01# 3871# 0# changes the Master code from 1234 to 3871.
3) Press to exit programming mode.
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 8
PATIENT
MONITORING
SYSTEM
Connecting to a Infant/Patient Monitoring System
1. Locate jumper [J6] (above the IBO input). Verify that it is NOT installed across both pins.
2. Close AND hold the REX input. The 101-DE will be in Bypass Mode and will be unlocked.
3. Whenever the IBO input is closed AND held, the 101-DE will immediately relock and rearm.
Egress is possible by activating the Exit Check’s trigger input and initiating the irreversible
15 or 30 second unlock cycle.
4. Releasing the IBO input will return the 101-DE to the Bypass Mode.
5. Releasing the REX input will rearm the system.
6. Upon power-up, you must manually reset the lock to activate the IBO input.
Connection to a Infant/Patient Monitoring
System has not been investigated by UL.
To
600 Series
Power
Supply
101-DE / 101-KDE
PWR LOCK RED RLY TRIG REX RESET
C NOC NOC NO
- +- +
GRN RLY
NO C NCNO C NC
IBO
C NO
Close to
Override
Bypass
Close &
Hold to
Unlock
REXTRIG RESET IBO
J4
J6
J1
KEYPAD
RESET
C NO C NO C NO C NO
Jumper Removed =
IBO input used for
Patient Monitoring
WHT
WHT
BLK
RED
POWER
TRANSFER
HINGE x DPS
SINGLE
DOOR
}
}
Alarm Secure
Monitor Relays
C – GREEN
N/O - RED
N/C - WHT
MC-4** NOTE: All door switches are shown in an
active state (i.e., Door is closed)
C
N/C
N/O
GRY
YEL
J6
** Door Contact OR Power Transfer Hinge by DPS required
for Anti-Tailgate, BOCA, Door Prop, or Forced Door
operation. When connecting a Patient Monitoring System,
the DPS must be wired in series with the device trigger, as
shown.
Connecting Optional Accessories
To
Power
Supply
REMOTE
BYPASS
Lock
Power
RED LED (+)
GRN LED (+)
LED COM (-)
101-1A or
101-1AK
REMOTE
ANNUCIATION
REXTRIG RESET IBO
J4
J6
J1
KEYPAD
RESET
C NO C NO C NO C NO
C NCNOC NCNO
PWR LOCK RED RLY GRN RLY
SP1
101-1AK
REMOTE
RESET
Remote Speaker
w/ plug-in
connector
101-SP
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

S6100 SERIES
RIM
PANIC/FIRE EXIT DEVICES
These instructions are presented a in step by
step sequence. Please read it through before
installation.
Note:
The dimensions of the Template are shown in
inches. See attached page for the Metric
Conversion Table for millimeters.
P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 9
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011
INSTALLATION INSTRUCTIONS

A. DESIGNATION OF PARTS
B. TYPE OF INSTALLATION
A. Single Door B. Double Door with Mullion C. Double Door without Mullion
2-7/16”
C
L
TRIM TRIM
DOOR DOOR
MULLION
2-7/16”
C
L
TRIM
DOOR
C. MARK POSITION FOR INSTALLING
1. Mark the center line of device by drawing a line
across the door and stop 40" above the finished floor
as shown at right.
2. Prepare door for you specific device per supplied template.
3. Drill holes as marked on door and jamb or mullion.
INSIDE
FACE
OF DOOR
JAMB
C
LOF
STRIKE
40" to
Finished
Floor
C
LOF
DEVICE
2-7/16”
C
L
TRIM TRIM
DOOR DOOR
DOUBLE DOOR
STRIKE
Strike
Chassis Cover
Chassis
Chassis
Latch Assembly
Push Bar
End Cap
End Cap Bracket
Dogging Device
(Fire Exit Hardware is not
Equipped with this device)
P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 10
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 11
STOP LINE
Jamb
of Device
Strike
L
C
Strike
Site
Door
D. INSTALL STRIKE TO FRAME
1. Place strike over the drilled holes, and attach it to
the jamb or mullion with the supplied screws.
2. If installing with a vertical rod device for double
doors, and additional Double Door Strike must be
used in place of the regular strike provided.
E. IF CYLINDER IS INCLUDED WITH THE DEVICE
1. Drill one 1-3/16" diameter thru hole for the cylinder/bracket plate.
2. Insert cylinder and cylinder collar from outside of door.
3. Place bracket plate on inside of face of the door.
4. Put two cylinder mounting screws through the bracket plate and
into the cylinder.
5. Cut the cylinder mounting screws and tailpiece to the required door
thickness at break-off points, then fasten screws.
F. INSTALL OUTSIDE TRIM
Mark and drill holes for the outside trim (see trim instructions).
E. INSTALL DEVICE BODY
1. Remove chassis cover from latch assembly
and end cap from end cap bracket.
2. Place the device horizontally over the drilled holes and
attach with the supplied mounting screws. Bolt
device chassis to trim with sexbolts (if required).
3. Make sure cylinder or trim actuator shaft (tailpiece) can
insert into device cam concentrically (see device cam
at right).
4. Install end cap bracket on device, then screw to door.
5. Tighten all screws or bolts.
Device Cam
Insert Trim Actuator Shaft
Into device cam “+”.
Latch Assembly
Outside face of door
Cylinder Collar
Rim Cylinder
Cylinder
Actuator shaft
(Tailpiece)
Inside face of door
Cylinder
bracket plate
Cylinder mounting screws
Tailpiece projection
1/4”
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011

P:\INST INSTRUCTIONS\Delayed Egress\INST-6000\INST-S6000DE_KDE Rev D 11-20 Page 12
H. INSTALL COVERS
NOTE: The Device bar has 3 different lengths;
Standard 3' Door Device = Approx 33"
Standard 3.5' Door Device = Approx 40"
Standard 4' Door Device = Approx 44"
The bar lengths of devices are pre-cut for 36", 42" and
48" wide door, no additional cutting is necessary.
If narrower door installation is needed, cut device at the
“A” location, to door width minus 4" to fit properly.
1. Test push bar operation before installing covers:
a. No Trim: Latch bolt is retracted by push bar
inside.
b. With Trim: Latch bolt is retracted by push bar
inside, key or lever/knob outside.
c. Dogging: See dogging description and chart
below.
2. Make sure and secure latch bolt engagement. Adjust
strike if required.
3. Install chassis cover on chassis.
4. Install end cap.
Note: For increasing the life of this device,
dogging device during high traffic
period of the day (Panic device only).
Dogging Wrench
(Allen Key) Dogging:
Depress push bar,
Insert dogging wrench
and turn clockwise 35 degrees.
Depress
push bar
The push bar will remain depressed and
the latch will remain retracted
Release Dogging:
Depress push bar,
Insert dogging wrench and
turn counter-clockwise 35 degrees.
Depress
push bar
The push bar will return to up position
and the latch will project to lock the
door.
Latch
Assembly
Mark mounting holes
through End Cap Bracket
after device is level
A
SECURITY DOOR CONTROLS ■ WWW.SDCSECURITY.COM
[t] 800.413.8783 ■ 805.494.0622 ■ E-mail: [email protected] ■ 801 Avenida Acaso, Camarillo, CA 93012 ■ PO Box 3670, Camarillo, CA 93011