SE Controls SECO Ni 24 40 Manual

SECO Ni 24 40
Technical information and operating instructions
10566
v3 02.21
+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modications. Diagram is not binding.
Application
• 24V DC Chain Motor.
• Natural and Smoke Ventilation
applications
• Congurable:
• Speed
• Stroke
• Seal Relief
• Volt Free Contact (optional)
• Range of Fixing Systems.
• Options for customisation to meet
application requirements.
• Marked
• Tested to principles of EN1210-2: 2003
Annex G

+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modications. Diagram is not binding.
Specication
Actuator SECO Ni 24 40
Actuator Type 24V dc Chain Opener
Voltage (all +/-5%) 24V dc
Amp Draw Current (with load) 0-600mm = 1.0A, 601-900mm = 1.2A
Stroke 0-600mm congurable, 601-900mm congurable
Operating Speed 600mm = 12mm/sec, 900mm = 15mm/sec
Ambient Operating Temp -5°C +60°C
Thrust Force 400N
Close Force 400N
Soft Close Yes
Switching Electronic
Standard Finish Powder coated Grey (RAL 9006)
Seal Relief Programmable up to 20mm
Clamping Force 4000N
Colour Option Other RAL colours available on request
Flex Length 2m
Flex Type 2 core / 0.75mm silicon for smoke
Flex Colour Grey (RAL 9006)
Product Warranty 15,000 cycles
Duty Cycle 22% 2 mins on, 7 mins o
Protection Degree IP20 / IP42
Bracket Sill xing / open inward / face x bracket
Synchronisation Optional
Application Environmental Ventilation

+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modications. Diagram is not binding.
1.1 General Safety Information
SE Controls reserves the right to introduce any
modications and improvements to the contents of this
publication without the obligation of giving prior notice.
Read and observe the information contained in these
safety instructions and respect the order of procedure
stated therein.
Please keep these safety instructions for future reference
and maintenance. Reliable operation and the prevention
of damage and risks are only granted if the equipment
is assembled carefully and the settings are carried out
according to these instructions and to the operating
instructions of the drives.
Please observe the exact terminal assignment, the
minimum and maximum power ratings (see technical data)
and the installation instructions.
Please observe the following warning symbols:
1.2 Health and Safety
Warning!
Carefully ready these warnings
Warning!
Danger of electric shock.
Warning!
Draws attention to instructions that must
be followed in order to prevent damage to
the actuator.
Notice
Indicates important notices to which
attention must be paid.
All actuator products contain metallic, plastic
and electronic parts. Redundant electronic
products are classied as hazardous waste
under the WEEE regulations (Waste Electrical
and Electronic Equipment). Electronic parts
must be disposed by an authorised and
licensed recycler.
Handling and storage; Care must be taken in transportation
to the installation location and during tting. Actuator
products must not be dropped, impacted, allowed to get
wet or abused in any other way. Mishandling can result in
serious damage.
Competence; Installation and connection must only be
carried out by authorised, competent and safety conscious
persons.
1.3 Environmental
They must not be disposed of in ‘general waste’ skips.
Consult SE Controls for assistance.
Danger!
General danger or precautionary warning
with numerous implications.
Danger!
Danger that could cause personal injury.
Danger of hands been crushed!
Electrical Safety; Warning 230 V AC Dangerous
voltage. Can cause death, serious injury or
considerable material damage. Disconnect the
equipment from the power supply at all poles
before opening, assembling or carrying out any
structural alterations.
Warning! Never connect the drives to 230V!
They are built for 24V! Risk of death!
Personal Protective Equipment; It is
recommended that suitable PPE is worn at all
times during the installation and connection
of actuator products in accordance with a
recommended safe system of work.

+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modications. Diagram is not binding.
For further application, please contact SE Controls.
The actuator compiles with current safety directives.
Operating safety can be guaranteed only if installers comply
with the safety regulations in force in the country where the
actuator is used.
The actuator is not a structural member of the window.
Always mount the safety arms in bottom-hung applications.
The position of the three-way switch button must be
outside the eld of action of the moving part of the window.
Do not allow children to play with the xed or remote
controls.
When using the actuator, follow these safety
instructions described herein. This equipment
is designed for the automatic opening and
closing of the stated types of windows.
Do not install two or more actuators on the
same window without using a synchronisation
accessory.
Any other application of the actuator must
be approved after technical testing of the
application. Use only original accessories or
accessories approved by SE Controls to install
the actuator.
When opening or closing the window, make
sure other people are far away from the moving
part, even when a re detection system is
closing an open window.
1.4 Application and Use
It would be beyond the scope of these safety instructions
to list all the valid regulations and guidelines.
Always make sure that your system
corresponds to the valid regulations. Pay
particular attention to: the aperture cross-
section of the window, the opening time and
opening speed, the temperature resistance of
the cables and equipment, cross-sections of
the cables in relation to the cable lengths and
power consumption.
Care must be taken to ensure that actuator
products are controlled with compatible
products; refer to SE Controls. No liability will
be accepted and no guarantee nor service is
granted if actuator controls are used without
such compatibility being conrmed.
Installation of this equipment must only be carried out by
authorised, competent and safety conscious persons.
Routing of cables and electrical connections only to be
done by a qualied electrician.
The cables must be installed in such a way that they cannot
be severed o, twisted or bent o during operation.
Junction boxes must be accessible for maintenance work.
1.5 Installation
The actuator must be assembled and
connected only by specialised sta who have
been properly trained and who are familiar
with the problems associated with automatic
window opening and closing systems, technical
reference standards and safety standards.
The window closes automatically. When
opening and closing, the drive unit is stopped
by the power cut- o. The corresponding
pressure force is listed in the technical data.
Take care - the pressure force is high enough to
cause injury!
During assembly and operation do not obstruct
the window opening!
Danger of crushing/trapping!
Warning! Incorrect installation may render the
actuator dangerous! Follow all the instructions
set out below and the instructions applied to
the motor.
Power supply leads 230 V AC to be fused
separately by the customer. Keep power supply
leads sheathed until the mains terminal.
All low voltage cables (24 V DC) to be installed
separately from high voltage cables. Flexible
cables should not be plastered in. Provide
strain relief for freely suspended cables.
Adhere to the type of cables, cable lengths
and cross- sections as stated in the technical
information.
After installation and any changes to the system check all
functions by a trial run.

+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modications. Diagram is not binding.
• Building regulations 2002
• Health and Safety at Work Act 1974
• I.E.E Regulations
• Regulatory Reform (Fire Safety) Order 2005
• At least once a year, check that the power
cable and connection has not been damaged
and that it shows no sign of wear
• Check that no object obstructs the window
movement.
• If faults arise, never work on the actuator
and never open or dismantle parts of the
actuator that deny access to the inside of the
mechanism.
• If the actuator fails to function or is damaged,
contact SE Controls.
• Do not use the actuator until it has been
repaired.
The system must be protected against
unintentional re-starting.
All smoke ventilation systems must be
periodically (annually) checked, serviced,
maintained and, if necessary, repaired and re
tested by a authorised, trained and competent,
safety conscious persons.
Maintenance shall be carried out in accordance with the
requirements of;
In order to keep the equipment in optimum operating
condition it is recommended that ventilation systems are
similarly maintained.
There are no user repairable parts in this equipment.
Basic checks that can be carried out include;
A suitable service contract with SE Controls is
recommended for this purpose.
The gear system is greased for life and is maintenance free.
After maintenance, repair or any changes to the system
check all functions by a trial run.
Defective equipment must only be repaired by
SE Controls. Only original spare parts are to be
used.
1.6 Maintenance
Always disconnect the motor’s supply voltage and batteries
during cleaning or maintenance operations, especially if the
actuator is equipped with an automatic control device.

+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modications. Diagram is not binding.
A. Top hung
open out window
B. Bottom hung
open in window
C. Top hung open
out window on sill
3. Still xing option 4. Face xing option 5. Open inward option
2. Trunnion set (installed on the
moving part of the window)
1. Body of
chain actuator
Installation Guide
Product Components

+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modications. Diagram is not binding.
Installation Guide
A. Top hung open out window installation
B. Bottom hung open in window installation
i. Fix the trunnion set in the mid position on the moving part of the window.
ii. Close the window, then x the chain actuator body with the pivot bracket set (3) provided. It should be aligned with the
trunnion set (2) on the moving part of the window. Caution: misalignment will cause improper opening and closing of
the window.
iii. Fix all screws in the trunnion set and pivot bracket rmly. (make sure sucient space is allowed for the actuator body
to rotate).
iv. Fix the pin to connect the trunnion set to the top part of the chain.
v. Switch on the power supply to test run the actuator for a few cycles, make sure the opening and closing of the window is
smooth and free from obstruction.
The installation process is similar to the above (Top hung window installation)
Caution: Safety arms chains are recommended to connect to the frame for moving part of the window if bottom hung widows
are installed.

+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modications. Diagram is not binding.
Installation Guide
C. Top hung open out window on sill installation
i. Fix the trunnion set in the mid position on the moving part of the window using the holding bracket provided.
ii. Close the window, then x the chain actuator body with the pivot bracket set provided. It should be aligned with the
trunnion set on the moving part of the window. Caution: misalignment will cause improper opening and closing of the
window.
iii. Fix all screws in the trunnion set and pivot bracket rmly. (make sure sucient space is allowed for the actuator body
to rotate).
iv. Fix the pin to connect the trunnion set to the top part of the chain.
v. Switch on the power supply to test run the actuator for a few cycles, make sure the opening and closing of the window is
smooth and free from obstruction.
vi. Repeat the above if adjustment is required.
Setting the zero position of the actuator (For optimum performance and to maintain soft close feature, ensure
zero point is correctly set)
i. Fit actuator to vent as required, run motor fully open and then commence close of motor.
ii. Position Zero Set Tool (ZST) as shown whilst actuator is closing. (See below)
iii. Still holding ZST in place, allow vent to continue close stroke until it stops on current limit. ENSURE YOU DO NOT TRAP
YOUR FINGERS.
iv. New zero point is now set. Power and ZST can be removed.
Locate on corner of escutheon
Zero position setting tool (FXS00500020)
Magnet

Installation Guide
Connection
DC 24 V version (2 wires)
Cross section of ex is 0.75mm
Name & registered office: Loanguard Limited, Lancaster House, Wellington Crescent, Fradley Park, Lichfield, Staffordshire WS13 8RZ Company No.01468061 Vat No.377 5600 30 - SE Controls is a Registered Trademark
Lancaster House
Wellington Crescent
Fradley Park, Licheld
Staordshire WS13 8RZ
Creating a healthier & safer environment
+44 (0)1543 443060
sales@secontrols.com
www.secontrols.com
Table of contents
Other SE Controls Controllers manuals

SE Controls
SE Controls SECO Ni Manual

SE Controls
SE Controls SECO Ni AKS20000001 User manual

SE Controls
SE Controls SECO AKS20000003 Manual

SE Controls
SE Controls Seco Ni 40 Manual

SE Controls
SE Controls SELA U 24 75 Manual

SE Controls
SE Controls OS2 User manual

SE Controls
SE Controls OS2 Manual

SE Controls
SE Controls TWIN SECO N 24 25 Manual
Popular Controllers manuals by other brands

RSS
RSS Digital Snake S-4000R Instalation manual

Pentair
Pentair GOYEN IS Series Products Installation Instructions

Danfoss
Danfoss EKC 368 instructions

Hubbell
Hubbell Electric Fire Pump Controllers LXi 1400 Specifications

Danfoss
Danfoss DEVIreg Multi Installation and user guide

Deif
Deif SGC 420 user manual