SE Controls SECO AKS20000003 Manual

SECO Ni Folding Arm Actuator
Fixed Version - Technical information and operating
instructions
+44 (0)1543 443060
www.secontrols.com
Please keep these operating instructions for future reference and maintenance.
Subject to technical modifications. Diagram is not binding.
SECO Ni Folding Arm
Fixed Version
•
24
V dc Fixed Folding Arm
•
Smoke & Environmental Ventilation
applications
•
Configurable:
•
Speed
•
Stroke
•
Seal Relief
•
Volt Free Contact
•
Range of Fixing Systems.
•
Options for customisation to meet
application requirements.
•
CE Marked
Bracket Part Numbers
AKS20000003 - Pivot/Slider Kit
AKS20000002 - Mounting Bracket Kit

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com
Technical Data
Actuator
SECO Ni Folding Arm Actuator
Actuator Type
24V dc Folding Arm Actuator
Voltage (all +/-5%)
24V dc
Current Draw (Amp)
1.0A
Stroke/Opening Angle
0-600mm / 0-90° programmable
Operating Speed
15mm/sec
Ambient Operating Temp
-5°C to +60°C
Thrust Force
400N
Close Force
400N
Soft Close
Yes
Switching
Electronic
Standard Finish
Grey (RAL 9006)
Seal Relief
Programmable up to 20mm
Colour Option
Other RAL colours available on request
Flex Length
2m
Flex Type
5 Core - 2x 0.75mm ² (Power)/ 3x 0.25mm ² (Comms)
Flex Colour
Black
Product Warranty
15,000 cycles
Duty Cycle
22% (2 mins on, 7 mins off)
IP Rating
IP20
Bracket
Frame Mounted Roller / Door Mounted Fixed

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com
Synchronisation
Optional in pairs

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com
1.1 General Safety Information
SE Controls reserves the right to introduce any
modifications and improvements to the contents of this
publication without the obligation of giving prior notice.
Read and observe the information contained in these
safety instructions and respect the order of procedure
stated therein.
Please keep these safety instructions for future
reference and maintenance. Reliable operation and
the prevention of damage and risks are only granted
if the equipment is assembled carefully and the
settings are carried out according to these
instructions and to the operating instructions of the
drives.
Please observe the exact terminal assignment, the
minimum and maximum power ratings (see technical
data) and the installation instructions.
Please observe the following warning symbols:
Warning!
Carefully ready these warnings
Warning!
Draws attention to instructions that must
be followed in order to prevent damage to
the actuator.
Notice
Indicates important notices to which
attention must be paid.
Danger!
General danger or precautionary warning
with numerous implications.
Danger!
Danger that could cause personal injury.
Danger of hands been crushed!
Warning!
Danger of electric shock.
1.2 Health and Safety
Electrical Safety; Warning 230 V AC Dangerous
voltage. Can cause death, serious injury or
considerable material damage. Disconnect the
equipment from the power supply at all poles
before opening, assembling or carrying out any
structural alterations.
Warning! Never connect the drives to 230V!
They are built for 24V! Risk of death!
Personal Protective Equipment; It is
recommended that suitable PPE is worn at
all times during the installation and connection of
actuator products in accordance with a recommended
safe system of work.
Handling and storage; Care must be taken in
transportation to the installation location and during
fitting. Actuator products must not be dropped,
impacted, allowed to get wet or abused in any other way.
Mishandling can result in serious damage.
Competence; Installation and connection must only be
carried out by authorised, competent and safety
conscious persons.
1.3 Environmental
All actuator products contain metallic, plastic
and electronic parts. Redundant electronic
products are classified as hazardous waste
under the WEEE regulations (Waste Electrical
and Electronic Equipment). Electronic parts must be
disposed by an authorised and licensed recycler.
They must not be disposed of in ‘general waste’ skips.
Consult SE Controls for assistance.

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com
1.4 Application and Use
When using the actuator, follow these safety
instructions described herein. This equipment
is designed for the automatic opening and closing of the
stated types of windows.
For further application, please contact SE Controls.
The actuator compiles with current safety directives.
Operating safety can be guaranteed only if installers comply
with the safety regulations in force in the country where the
actuator is used.
Do not install two or more actuators on the
same window without using a synchronisation
accessory.
Any other application of the actuator must
be approved after technical testing of the
application. Use only original accessories or
accessories approved by SE Controls to install the
actuator.
The actuator is not a structural member of the window.
Always mount the safety arms in bottom-hung
applications. The position of the three-way switch button
must be outside the field of action of the moving part of
the window.
Do not allow children to play with the fixed or remote
controls.
When opening or closing the window, make
sure other people are far away from the
moving part, even when a fire detection
system is closing an open window.
It would be beyond the scope of these safety
instructions to list all the valid regulations and
guidelines.
Always make sure that your system
corresponds to the valid regulations. Pay
particular attention to: the aperture
crosssection of the window, the opening time and
opening speed, the temperature resistance of the
cables and equipment, cross-sections of the cables in
relation to the cable lengths and power consumption.
Care must be taken to ensure that actuator
products are controlled with compatible
products; refer to SE Controls. No liability will
be accepted and no guarantee nor service is granted if
actuator controls are used without such compatibility
being confirmed.
1.5 Installation
Warning! Incorrect installation may render
the actuator dangerous! Follow all the
instructions set out below and the
instructions applied to the motor.
Installation of this equipment must only be carried out by
authorised, competent and safety conscious persons.
The actuator must be assembled and
connected only by specialised staff who have
been properly trained and who are familiar with the
problems associated with automatic window opening
and closing systems, technical reference standards and
safety standards.
The window closes automatically. When
opening and closing, the drive unit is stopped
by the power cut- off. The corresponding
pressure force is listed in the technical data.
Take care - the pressure force is high enough to
cause injury!
During assembly and operation do not obstruct
the window opening!
Danger of crushing/trapping!
Routing of cables and electrical connections only to be
done by a qualified electrician.
Power supply leads 230 V AC to be fused
separately by the customer. Keep power supply
leads sheathed until the mains terminal.
All low voltage cables (24 V DC) to be
installed separately from high voltage cables.
Flexible cables should not be plastered in.
Provide strain relief for freely suspended
cables.
The cables must be installed in such a way that they
cannot be severed off, twisted or bent off during
operation.
Junction boxes must be accessible for maintenance work.
Adhere to the type of cables, cable lengths
and cross- sections as stated in the
technical information.
After installation and any changes to the system check all
functions by a trial run.

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com
1.6 Maintenance
Always disconnect the motor’s supply voltage and batteries
during cleaning or maintenance operations, especially if the
actuator is equipped with an automatic control device.
The system must be protected against
unintentional re-starting.
All smoke ventilation systems must be
periodically (annually) checked, serviced,
maintained and, if necessary, repaired and re
tested by a authorised, trained and competent,
safety conscious persons.
Maintenance shall be carried out in accordance with the
requirements of;
•Building regulations 2002
•Health and Safety at Work Act 1974
•I.E.E Regulations
•Regulatory Reform (Fire Safety) Order 2005
In order to keep the equipment in optimum operating
condition it is recommended that ventilation systems are
similarly maintained.
There are no user repairable parts in this equipment.
Basic checks that can be carried out include;
•At least once a year, check that the
power cable and connection has not been
damaged and that it shows no sign of wear
•Check that no object obstructs the window
movement.
•If faults arise, never work on the actuator and
never open or dismantle parts of the actuator that
deny access to the inside of the mechanism.
•If the actuator fails to function or is damaged,
contact SE Controls.
•Do not use the actuator until it has been repaired.
A suitable service contract with SE Controls is
recommended for this purpose.
The gear system is greased for life and is maintenance free.
Defective equipment must only be
repaired by SE Controls. Only original
spare parts are to be used.
After maintenance, repair or any changes to the system
check all functions by a trial run.

Please keep these operating instructions for future reference and maintenance. +44 (0)1543 443060
www.secontrols.com

+44 (0)1543
443060
sales@secontrols.com
Please keep these operating instructions for future
reference and maintenance. Subject to technical
modifications. Diagram is not binding.
1
.
Ensure door is free and clear of
all obstructions and debris.
.
4
Power the actuator to the fully
open position.
7.
Mark up the bracket holes in all
four positions.
.
10
Attach the slider bracket and
bracket retention cable to the door.
Cycle test the door open and closed
multiple times to ensure correct
operation.
2
.
Install the Supplied pivot
bracket set to the actuator.
.
5
Mark up the distance from the
hinge to the actuator to allow
the door to be opened to the
required position.
8
.
Drive the actuator fully closed
and allow the door to close, ensure
the opening doesn’t clash with the
actuator.
11
.
Installation is complete, if
required add finger entrapment
stickers to the door.
.
3
Offer actuator up to door with the
door and actuator fully closed. Take
measurement of the fixing height
required for the actuator not to touch
the opening door when door opens/
closes.
6
.
Ensure the installation location
allows for the actuator to open to
the maximum opening angle.
.
9
Fix actuator using screws
suitable for the door
construction.
Installation Guide - Door Applications

+44 (0)1543
443060
sales@secontrols.com
Technical Drawing
Wiring
Please keep these operating instructions for future reference and maintenance. Subject to technical
modification.

Creating a healthier & safer environment
Wiring - Electric Strike
Wiring - Magnet

+44 (0)1543
443060
Lancaster House +44 (0)1543 443060
Wellington Crescent
Fradley Park, Lichfield sales@secontrols.com
Staffordshire WS13 8RZ www.secontrols.com
Name & registered office: Loanguard Limited, Lancaster House, Wellington Crescent, Fradley Park, Lichfield, Staffordshire WS13 8RZ Company No.01468061 Vat
No.377 5600 30 - SE Controls is a Registered Trademark
This manual suits for next models
1
Table of contents
Other SE Controls Controllers manuals

SE Controls
SE Controls SECO Ni 24 40 Manual

SE Controls
SE Controls TWIN SECO N 24 25 Manual

SE Controls
SE Controls SECO Ni Manual

SE Controls
SE Controls Seco Ni 40 Manual

SE Controls
SE Controls OS2 Manual

SE Controls
SE Controls OS2 User manual

SE Controls
SE Controls SECO Ni AKS20000001 User manual

SE Controls
SE Controls SELA U 24 75 Manual