3
interrupter (GFCI) is recommended for use on any
electrical appliance submerged in water.
3.Use this pump only for backup sump pump duty in a
residential application. It is not designed as a primary
sump pump.
4. Hazardous Voltage. Can cause severe or
fatal electrical shock. Do not plug in or unplug battery
charger while standing on a wet floor or in water. Be
sure one hand is free when plugging in or unplugging
charger. If basement floor is wet, disconnect power to
basement before walking on floor.
5.Do not lift pump by electrical cord.
6.Pump water only with this pump.
7.Do not run pump dry. To do so will damage seals and
can cause leaking and property damage.
8.Pump is permanently lubricated at the factory. Do not
try to lubricate it!
9.Keep battery charger and battery box in a dry, cool,
well ventilated area.
10.To avoid danger of fire or explosion, keep sparks and
flame away from battery.
11. Battery acid is corrosive. Do not spill on
skin, clothing, or battery charger. Wear eye protec-
tion when working on battery.
12.Maximum vertical pumping distance is 15 feet.
13.Make sure sump is clear of debris.
BASIC TOOLS AND MATERIALS NEEDED
Pipe Wrenches Screwdriver
Hacksaw 1-1/4" Check Valve
Adjustable Wrench Teflon Tape
Knife 12-volt Battery
GENERAL INFORMATION
The Battery-Powered Back-up Sump Pump is not a sub-
stitute for your primary sump pump. It is designed as a
backup pump to pinch-hit for your primary sump pump
during a power outage or other problem which prevents
normal operation. Do not use it to pump flammable
liquids or chemicals. If pumping salt water, flush the
pump with clear water after use.
Keep battery charger dry and protected from damage.
In an emergency (such as an extended power outage)
which depletes the system battery, your automobile
battery may be temporarily substituted. Be sure to replace
the system battery as soon as possible.
CHARGER OPERATION
Backup pump will start automatically when sump water
level rises far enough to trip float switch. After a delay of
about 4 seconds, alarm will sound. Silence alarm by
pushing ALARM TEST/RESET button. In normal (switch ac-
tuated) operation, alarm is locked out until about 4
seconds after float switch has dropped to OFF position;
cycle can then begin again.
Test alarm by pushing ALARM TEST/RESET button when
alarm is not sounding. Alarm will then sound as long as
button is held down. Pushing ALARM TEST/RESET button
to test alarm overrides lockout, so alarm can be tested at
any time.
If alarm sounds, check operation of primary pump, which
may need service. If battery backup operation is due to a
power outage, alarm will sound, but no service is likely to
be required to primary pump.
Battery charger has capacity to run pump and charge
battery at the same time as long as power to the charger is
not interrupted. If power to charger circuit is interrupted,
the length of time that the backup pump will run depends
on the Ampere-hour capacity of the battery used.
Extended periods of operation (for example, during an ex-
tended power outage) may exhaust the battery. However,
once the load is removed, usually it will self-regenerate far
enough to allow the charger to start. The battery charger
will begin charging the battery as long as the battery has a
charge of at least 1/2 volt.
After power is restored, charger will automatically re-
charge battery fully in about six hours.
NOTICE: Some trouble conditions will cause the alarm to
sound. See chart below for causes and action:
PROBLEM ACTION
Back-up pump has run Push ’Reset’. Check main pump.
Power out more than Disconnect charger from battery.
24 hours Call power company.
Continuous charging Disconnect charger from battery.
more than 24 hours Check for defective battery.
Loose connection or Disconnect charger from battery.
no power to charger Check plug, receptacle, and
power at main breaker.
After restoring power or replacing battery, alarm can be reset.