SEAWIN Electricals MP6401 User manual

KNX/EIB BUS
POWER ACTUATORS
Product Manual
KNX Bus Power Supply
Manual-Ver2.1
MP6401

KNX/EIB BUS
POWER ACTUATORS
Product Manual
Catalog
1 Overview .............................................................................................................................................................................................................. 1
2 Detailed parameters .......................................................................................................................................................................................... 1
3 Dimensional drawings and wiring diagrams ............................................................................................................................................. 2
4 Product Operating Instructions ..................................................................................................................................................................... 2
5 Power running test ............................................................................................................................................................................................. 3
6 Safe use and maintenance ............................................................................................................................................................................... 3
7 Contact ................................................................................................................................................................................................................... 3

KNX/EIB BUS
POWER ACTUATORS
Product Manual
1
1 Overview
The EIB / KNX bus power supply is used to provide and monitor the voltage of the EIB / KNX system. The output
has two terminals, including one KNX bus output for EIB bus power supply and signal transmission. One 30V DC
auxiliary output and provides a power supply voltage of 30V DC, 500mA which can be sent to the terminal; the reactor
has been integrated into the bus connection terminal; if a reactor is connected to the 30V DC auxiliary power supply
terminal, it can also be used as a bus power supply terminal and also has a signal transmission function.
In order to facilitate installation into the distribution box, the KNX bus power supply is designed as a modular
installation device that can be mounted on a 35 mm DIN rail. The equipment adopts screw terminals to realize 220V
voltage input and auxiliary power output connection. The EIB bus connection is directly connected through the EIB
terminal (red / black).
The power can be reset by pressing the reset button on the device for 24s.
Functions:
(1)Meet the power supply of KNX / EIB bus equipment;
(2)The yellow-green status LED indicates the current auxiliary power supply status. When the auxiliary output status
LED is constantly on, it indicates that the auxiliary power supply is normal. When the status LED flashes, it indicates
that any of the auxiliary power supply is overloaded.
(3)The red LED is always on to indicate that the KNX bus output exceeds the rated current of 640mA. When the KNX
bus output current exceeds 900mA, the bus output is automatically cut off and the red LED flashes. Press the reset
button to restore.
2 Detailed parameters
Main input 200-240V AC
KNX Bus output 1 way with reactor,21-30V DC
Auxiliary power output 1 way without reactor,30V DC/500mA
Bus powered output current Max.640mA, Short circuit protection
Auxiliary power supply output current Max.500mA
Continuous short-circuit current ≤1.3A
Power-down hold time >200ms
Frequency 50-60Hz
Shell material PA66
Dimension (Lx W x H) 144mm X 90mm X 64mm
Weight (approx.) 0.4KG
Installation method 35mm DIN rail mounting
Operating temperature -5°C-45°C
Storage temperature -20°C-70°C
Relative humidity max 90%

KNX/EIB BUS
POWER ACTUATORS
Product Manual
2
3 Dimensional drawing and wiring diagrams
Dimensional drawing wiring diagram
4 Product Operating Instructions
①Description: 200~240VAC power supply wiring port, the aperture can be connected to φ4 wire;
②Description: Auxiliary power supply 30V DC output wiring port, the aperture can be connected to φ4 wire;
③Description: KNX bus power supply output port, KNX bus access, red line connected to "+", black line connected to
"-";
④Description: Reset indicator light, the indicator light is red when the reset operation is performed, when the KNX bus
is short-circuited, the indicator light flashes red, and the indicator light is off when the device is in normal state;
⑤Description: Reset button, press it shortly, the power supply is in a power-off state, and it will automatically resume
normal power supply after 24s;
⑥Description: Status (Auxiliary): Auxiliary power supply output status indicator, yellow-green status LED, when the
status LED is always on, it means that the auxiliary power supply is normal, and when the status LED flashes, it means
that the auxiliary power supply is overloaded;
⑦Description: Status (KNX BUS): KNX bus status indicator;
⑧Explanation: Overload: When the KNX bus output exceeds the rated current of 640mA, the LED indicator is always on
in red; when the KNX bus output current exceeds 900mA, the bus output is automatically cut off and the LED indicator
flashes red, and it can be restored by pressing the reset button.

KNX/EIB BUS
POWER ACTUATORS
Product Manual
3
5 Power running test
After the bus power is properly installed, turn on the main power and supply power to the bus. At this time, the
status (KNX BUS) and Status (Auxiliary) indicators on the device are on, and the other lights are off, indicating that the
bus power can operate normally.
6 Safe use and maintenance
(1) Read all instructions carefully before use.
(2) Create a good ventilation environment.
(3) During use, pay attention to moisture, shock and dust.
(4) Strictly forbid to rain, contact with other liquids or corrosive gases.
(5) If it is wet or attacked by liquid, it should be dried in time.
(6) When the machine fails, please contact professional maintenance personnel or our company.
7 Contact
Address:9th Floor, Building 5, Aotelang Science and Technology Park, No. 68, Nanxiang 1st Road, Huangpu District, G
uangzhou City, Guangdong Province.China
Tel: +86-20-82189121
Fax: +86-20-82189121
Website: http://www.seawin-knx.com