SEAWIN Electricals MP6402 User manual

KNX/EIB BUS
POWER ACTUATORS
Product Manual
KNX Bus Power Supply
Manual-Ver2.1
MP6402

KNX/EIB BUS
POWER ACTUATORS
Product Manual
Catalog
1 Overview ..................................................................................................................................................................................................... 1
2 Detailed parameters .............................................................................................................................................................................. 1
3 Dimensional drawing and wiring diagrams..................................................................................................................................... 2
4 Handling ...................................................................................................................................................................................................... 2
5 Power running test ................................................................................................................................................................................... 3
6 Safe use and maintenance ...................................................................................................................................................................... 3
7 Contact ........................................................................................................................................................................................................ 3

KNX/EIB BUS
POWER ACTUATORS
Product Manual
1
1 Overview
The EIB / KNX bus power supply is used to provide and monitor the voltage of the EIB / KNX system. The output has
two terminals, including one KNX bus output for EIB bus power supply and signal transmission. One 30V DC auxiliary
output and provides a power supply voltage of 30V DC, 640mA which can be sent to the terminal; the reactor has been
integrated into the bus connection terminal; if a reactor is connected to the 30V DC auxiliary power supply terminal, it
can also be used as a bus power supply terminal and also has a signal transmission function.
In order to facilitate installation into the distribution box, the KNX bus power supply is designed as a modular
installation device that can be mounted on a 35 mm DIN rail. The equipment adopts screw terminals to realize 220V
voltage input and auxiliary power output connection. The EIB bus connection is directly connected through the EIB
terminal (red / black).
The power can be reset by pressing the reset button on the device for 24s.
Functions:
(1)Meet the power supply of KNX / EIB bus equipment;
(2)LED1(ON)Green indicates normal operation,LED2(Reset)Red indicates reset,LED3(I>Imax)Red indicates output
overcurrent, short circuit;
(3)With output short circuit, over current, over voltage protection function;
2 Detailed parameters
Main input 200-240V AC
Frequency 50-60Hz
KNX Bus output 1 way with reactor,21-30V DC
Auxiliary power output 1 way without reactor,30V DC
Nominal output current I1+I2≤640mA , Short circuit protection
Output voltage accuracy ±5%(Typ.)
Power-down hold time >150ms
Shell material PC
Dimension (Lx W x H) 52mm X 90mm X 58mm
Weight (approx.) 195g
Installation method 35mm DIN rail mounting
Operating temperature -30°C to +70°C
Storage temperature -40°C to +85°C
Relative humidity max 95%

KNX/EIB BUS
POWER ACTUATORS
Product Manual
2
3 Dimensional drawing and wiring diagrams
Dimensional drawing wiring diagram
4 Handling
①Description: 200~240VAC power supply wiring port, the aperture can be connected to φ4 wires;
②Instructions: (1) ON: Power supply working status indicator, green status LED, when the status LED is always on, it
means that the power supply is working normally;
(2) Reset: red reset indicator light; (3) I1+I2>Imax: when the bus output current is overcurrent or the bus is
short-circuited, the LED indicator light is on and the red light flashes;
③Description: Auxiliary power supply 30V DC output wiring port, the aperture can be connected to φ4 wire;
④Instructions: The reset button can reset the KNX bus product, and the reset of the KNX bus product must be pressed
for at least 20 seconds;
⑤Description: KNX bus power supply output port, KNX bus access, red line connected to "+", black line connected to
"-";

KNX/EIB BUS
POWER ACTUATORS
Product Manual
3
5 Power running test
After the bus power is properly installed, turn on the main power and supply power to the bus. At this time, the status
ON indicators on the device are on, and the other lights are off, indicating that the bus power can operate normally.
6 Safe use and maintenance
(1) Read all instructions carefully before use.
(2) Create a good ventilation environment.
(3) During use, pay attention to moisture, shock and dust.
(4) Strictly forbid to rain, contact with other liquids or corrosive gases.
(5) If it is wet or attacked by liquid, it should be dried in time.
(6) When the machine fails, please contact professional maintenance personnel or our company.
7 Contact
Address:9th Floor, Building 5, Aotelang Science and Technology Park, No. 68, Nanxiang 1st Road, Huangpu District, G
uangzhou City, Guangdong Province.China
Tel: +86-20-82189121
Fax: +86-20-82189121
Website: http://www.seawin-knx.com
Table of contents
Other SEAWIN Electricals Power Supply manuals
Popular Power Supply manuals by other brands

Matsusada Precision
Matsusada Precision AMP Series instruction manual

Velleman
Velleman LABPSHH01U user manual

TDK-Lambda
TDK-Lambda GH10-100 user manual

M-system
M-system JPS3 instruction manual

Ametek
Ametek Sorensen XFR 1200 Watt Series Operation manual

Linergy
Linergy SPY CENTER BASIC SCB050 Series user manual

HUA YI ELECTRONICS
HUA YI ELECTRONICS HY3000-2 Series user manual

Horizont
Horizont farmer AN1000 Solar instruction manual

Rosslare
Rosslare PS-C18 installation manual

Transition Networks
Transition Networks PCVT-48VDC-53VDC install guide

Solar Stik
Solar Stik PRO-Verter S 2000 AGS Setup and operation

GE
GE Digital Energy datasheet