Sectoriel TCR-02T-KT User manual

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-02T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
1/7
Ref.
FT2419 ENG
Rev.
01
Date
02/2020
FEATURES
The TCR-02T-KT electric actuator is intended for motorising ¼ turn valves with a torque of 15 Nm.
Double proportional control function 4-20mA + closing manoeuvre provided by a super-capacitor. With a compact
construction and plastic housing, it is especially well suited for motorising small dimensions ball valves. The actuator has
many advanced control functions which can be set from the screen. IP67 leak-tightness: to be used indoors and, possibly,
outdoors under a shelter. Manual control with a key.
AVAILABLE MODELS
Supply voltages: 230V AC, 24V AC/DC.
Control: 4-20 mA
LIMITS OF USE
MECHANICAL FEATURES
Torque (Nm)
15
Voltage
24V AC - DC
95-265V AC-DC
Adjustment signal
4-20 mA
Feedback signal
4-20 mA
Manoeuvring time (s)
15
15
ISO 5211:
F03/F04/F05 - star 11
ELECTRICAL FEATURES
Motor protection
Thermal switch
Limit switches
2 adjustable switches
Anti-condensation
integrated
Electrical connection
PE M10 + 1.5m cable
Voltage
24V AC - DC
95-265V AC-DC
Power (W)
36
40
Current (A)
1,5
0,035 - 0,09
Fuse protection (A)
5
1
IP Code
IP 67
Ambient temperature
- 20°C / +60°C
Service factor
S4-50%
Gear box
treated steel pinions
Torque
15 Nm
Angle of rotation
90° +/- 2°
Declutching
without
Override control
By key
IP
67
ISO
9001

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-02T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
2/7
Ref.
FT2419 ENG
Rev.
01
Date
02/2020
CONSTRUCTION
DIMENSIONS (mm)
TCR-02T-KT32
No.
Name
Material
No.
Name
Material
1
Casing + lid
Plastic (ABS)
7
1.3” LCD display
OLED
2
Position indicator
Polycarbonate plastic
8
Rating plate
PVC
3
Screw x 4
Ansi 304
9
Packing gland
Nylon
4
Backup control stem
Ansi 304
10
Hex key
Steel
5
Gasket
NBR
11
Key support
Plastic (ABS)
6
Adjustment button
Rubber
12
Cover gasket
NBR
Weight (kg): 0.620

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-02T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
3/7
Ref.
FT2419 ENG
Rev.
01
Date
02/2020
WIRING DIAGRAM
DESCRIPTION OF THE 1.3’’ LCD SCREEN
The control screen displays the % of opening and the actuator parameter setting.
1.3’’ LCD angle without any blind spot, strong luminosity, automatic switching to the economy saving mode at
the end of 5 minutes.
BU
Power supply neutral (Blue)
RD
Power supply phase (Red)
BR
4-20 mA signal output + (Brown)
WT
4-20 mA signal output - (White)
GY
4-20 mA signal input (Grey)
BK
Input alarm signal (Black)
PL
Output alarm signal (Purple)
Y/G
Earth (Yellow / Green)

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-02T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
4/7
Ref.
FT2419 ENG
Rev.
01
Date
02/2020
LOCAL OPERATION
1
Press the K3 button for 5 seconds, until “K3” flashes at the top right of the screen.
2
Enter the password “111”
3
Press the K2 button to manoeuvre clockwise. The screen displays the % of opening. Release when the desired
position is reached.
Press the K3 button to manoeuvre anti-clockwise. The screen displays the % of opening. Release when the
desired position is reached.
ACTUATOR SETTINGS
The following functions can have their parameters set from the menu accessible on the screen:
STEP
TITLE
FUNCTION AND VALUES
1
Entering the menu
Press the “M” button for more than 5 s.
2
Enter the password
Press the “M” button for more than 5 s.
Enter the code “333” (use the keys K2 and K3)
Press again the button “M”
3
Choice of language
English or Mandarin
4
Choosing the direction of
rotation of the actuator
Direct: 4mA = valve closed / 20 mA = valve open
Inverted: 4 mA = valve closed / 20 mA = valve open
5
Position by absence of any
control signal
In the absence of a control signal, the valve can take 3 positions: ON, OFF or
KEEP

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-02T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
5/7
Ref.
FT2419 ENG
Rev.
01
Date
02/2020
6
Dead band
This function is used to set the accuracy and the sensitivity of the control:
the larger the band, the lower the accuracy; the narrower the band, the
more oscillating the system can be.
Setting range: 0.1 to 9.9% - Setting by default: 0.8%
7
Hysteresis adjustment
This parameter setting is a prerequisite for the next.
YES = adjustment is possible
NO = no adjustment is possible (value by default)
8
Hysteresis value
If the previous parameter is “YES”, it is possible to set the hysteresis value
between 0.1 and 9.9%. The value by default is 0.2%. Do not use the
function if there is a play between the valve’s stem and the actuator’s
square.
9
Manual adjustment of the
speed of rotation
This function is used for slowing down the motor.
Range: 20-100% - Value by default = 100%
10
Braking time
In order to increase the stability of the motor, the motor will slow down
after a short time before reaching its setpoint value position. During
current use, this function is not useful.
Range: 0-95 ms –Value by default = 1 ms
11
Setting the maximum speed
This setting affects the available torque. Without a special need, do not
change it.
Range: 20-100% - Value by default = 100%
12
Setting the minimum speed
This setting affects the available torque. Without a special need, do not
change it.
Range: 20-95% - Value by default = 75%

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-02T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
6/7
Ref.
FT2419 ENG
Rev.
01
Date
02/2020
13
Setting the speed for the
stroke
This setting is used for setting a % of the actuator stroke during which it will
slow down before reaching the setpoint value position.
Range: 0.1-20% - Value by default = 10%
14
Redefining the 4 mA
position
Used to set another position than 0% for the 4 mA value. This function is
useful for valves with an opening angle different from 90°.
Range: -50% +80% - Value by default = 0.0%
15
Redefining the 20 mA
position
Used to set another position than 100% for the 20 mA value. This function
is useful for valves with an opening angle different from 90°.
Range: 20% +220% - Value by default = 100.0%
16
Modification of the 4 mA
output signal
If a deviation is found on the 4mA output signal, this function is used to
adjust it. If the number is increased, the current is higher. If the number is
decreased, the current is lower.
Range: 000_481_A –Value by default 191_A
NB: always limit the lower value to 20 mA
17
Modification of the 20mA
output signal
If a deviation is found on the 20mA output signal, this function is used to
adjust it. If the number is increased, the current is higher. If the number is
decreased, the current is lower.
Range: 191_1000_A –Value by default 909_A
18
Response time
Used to set the response speed of the valve. The smaller the value, the less
sensitive the control. The bigger the value, the more sensitive it is. Increase
the value when the response speed is too low.
Setting range: 1x20x –Value by default 3x

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-02T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
7/7
Ref.
FT2419 ENG
Rev.
01
Date
02/2020
19
Power supply position by
default
Setting the position of the valve in the event of a power cut. This
manoeuvre will be carried out if the capacitor is sufficiently charged.
Possible values:
KEEP: unchanged position of the valve
ON: valve opening
OFF: valve closing
Value by default: OFF
20
Capacitor charge
Setting the % of charge when the feed current is higher than the set value.
Setting range: 60-99%
Value by default: 95%
Do not set below 80%, the charge will be insufficient and would set off the
motor alarm
21
Exiting the menu
Press K3 to exit the menu
The system will switch back in the automatic checking mode.
TROUBLESHOOTING
Defect met
Cause of defect
Method of solving
Inactive actuator
Non-connected electrical grid.
Connect to the electrical grid.
Wrong voltage.
Check the actuator’s voltage.
Motor overheating.
Check the torque on the valve.
Faulty connection.
Check the connection to the terminal box.
Damaged start capacitor.
Contact the supplier for repair.
No switch signal
Faulty connection.
Check the connections.
Damaged microswitch
Change the microswitch
Valve that is not fully
closed
Use the return signal from the actuator
check.
Receiving a return signal does not mean
that the actuator is fully closed, hence do
not cut the power supply.
The hysteresis increases due to wear or
between the actuator and the valve’s stem.
Readjust the limit cams.
Contact the supplier for repair.
Presence of humidity or
water in the actuator
Unsuitable cable cross-section being used.
Contact the supplier for repair.
The cable connection is not leak-tight.
Worn sealing gaskets.
Loose cover screws.
Dry the internal parts and tighten the
cover screws.
Table of contents
Other Sectoriel Controllers manuals
Popular Controllers manuals by other brands

Chemitech IT Perdana
Chemitech IT Perdana pH/ORP-3500 Series Operation manual

Robur
Robur Direct Digital Controller Installation, use and programming manual

EMKO
EMKO EPC-1 instruction manual

Offshore
Offshore 3350-HTPO Installation and operating instructions

Kitz
Kitz ESR Series Operation manual

Matelec
Matelec RPC-30030 Owner's operation manual