Sectoriel TCR-02T User manual

TCR-02T CONTROL ELECTRICAL ACTUATOR
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.com / Email : sectorie[email protected]
Pages
1/8
Ref.
FT2415 ENG
Rev.
05
Date
05/2023
FEATURES
The TCR-02T electric actuator is intended for motorising ¼ turn valves with a torque of 20 Nm. Control function:
this motor is used to control the position of the valve depending upon an a 4-20mA or 0-10V input signal. With a
compact construction and plastic housing, they are especially well suited for motorising small size ball valves. IP67
leak-tightness: to be used indoors and, possibly, outdoors under a shelter. Possible installation in parallel. Manual
control with a key. This actuator has many functions. Parameter setting is done directly on the screen.
AVAILABLE MODELS
Supply voltages: 230V AC, 24V AC/DC.
Control: 4-20mA, 0-10V
LIMITS OF USE
MECHANICAL FEATURES
Actuator
TCR 02T
Torques (Nm)
20
Voltage
24V AC - DC
95-265V AC-DC
Adjustment signal
4-20mA / 0-10V
Manoeuvring time (s)
10
10
ISO 5211:
F03/F05 - star 11
ELECTRICAL FEATURES
Actuator
TCR 02T
Motor protection
Thermal switch
Limit switches
Without
Auxiliary switches
Without
Anti-condensation
integrated
Electrical connection
PE M10 + 1.5m cable
Actuator
TCR 02T
Voltage
24V AC - DC
95-265V AC-DC
Power (W)
10
10
Current (A)
0,35
0,035 - 0,075
Fuse protection (A)
2
1
IP Code
IP 67
Ambient temperature
- 20°C / +60°C
Service factor
S4 - 50%
Gear box
treated steel pinions
Torques
20 Nm
Angle of rotation
90° +/- 2°
Declutching
without
Override control
By key
IP
67

TCR-02T CONTROL ELECTRICAL ACTUATOR
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.com / Email : sectorie[email protected]
Pages
2/8
Ref.
FT2415 ENG
Rev.
05
Date
05/2023
CONSTRUCTION (TCR-02T)
DIMENSIONS (mm)
TCR-02T
No.
Name
Material
No.
Name
Material
1
Casing + lid
Plastic (ABS)
7
1.3” LCD display
OLED
2
Position indicator
Polycarbonate plastic
8
Rating plate
PVC
3
Screw x 4
Ansi 304
9
Packing gland
Nylon
4
Backup control stem
Ansi 304
10
Hex key
Steel
5
Gasket
NBR
11
Key support
Plastic (ABS)
6
Adjustment button
Rubber
12
Cover gasket
NBR
Weight (kg): 0.620

TCR-02T CONTROL ELECTRICAL ACTUATOR
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.com / Email : sectorie[email protected]
Pages
3/8
Ref.
FT2415 ENG
Rev.
05
Date
05/2023
WIRING DIAGRAM (TCR 02T)
BU
Neutral (Blue)
RD
Phase (Red)
BR
Current control signal output (Brown)
WT
Common (White)
GY
Current control signal input (Grey)
BK
Alarm signal (Black)
PL
Alarm signal (Purple)
Y/G
Terre (Jaune/Vert)
SCHEMA 4-20mA
Version 4-20mA / 0-10V :
BU
Neutral (Blue)
RD
Phase (Red)
BR
Voltage control signal output (Brown)
WT
Common (White)
GY
Voltage control signal input (Grey)
Y/G
Earth (Yellow / Green)
BK
Not used
PL
Not used
SCHEMA 0-10V

TCR-02T CONTROL ELECTRICAL ACTUATOR
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.com / Email : sectorie[email protected]
Pages
4/8
Ref.
FT2415 ENG
Rev.
05
Date
05/2023
DESCRIPTION OF THE 1.3’’ LCD SCREEN
ACTUATOR SETTINGS
The following functions can have their parameters set from the menu accessible on the screen:
STEP
TITLE
FUNCTION AND VALUES
1
Entering the menu
Press the “M” button for more than 5 s.
2
Enter the password
Press the “M” button for more than 5 s.
Enter the code “333” (use the keys K2 and K3)
Press again the button “M”
3
Choice of language
English or Mandarin
4
Choosing the direction of
rotation of the actuator
Direct: 4mA = valve closed / 20 mA = valve open
: 0V = valve closed / 10V = valve open
Inverted: 4 mA = valve closed / 20 mA = valve open
: 0V = valve closed / 10V = valve open
5
Position by absence of any
control signal
In the absence of a control signal, the valve can take 3 positions: ON, OFF or
KEEP

TCR-02T CONTROL ELECTRICAL ACTUATOR
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.com / Email : sectorie[email protected]
Pages
5/8
Ref.
FT2415 ENG
Rev.
05
Date
05/2023
6
Dead band
This function is used to set the accuracy and the sensitivity of the control: the
larger the band, the lower the accuracy; the narrower the band, the more
oscillating the system can be.
Setting range: 0.1 to 9.9% - Setting by default: 0.8%
7
Hysteresis adjustment
This parameter setting is a prerequisite for the next.
YES = adjustment is possible
NO = no adjustment is possible (value by default)
8
Hysteresis value
If the previous parameter is “YES”, it is possible to set the hysteresis value
between 0.1 and 9.9%. The value by default is 0.2%. Do not use the function
if there is a play between the valve’s stem and the actuator’s square.
9
Manual adjustment of the
speed of rotation
This function is used for slowing down the motor.
Range: 20-100% - Value by default = 100%
10
Braking time
In order to increase the stability of the motor, the motor will slow down after
a short time before reaching its setpoint value position. During current use,
this function is not useful.
Range: 0-95 ms –Value by default = 1 ms
11
Setting the maximum speed
This setting affects the available torque. Without a special need, do not
change it.
Range: 20-100% - Value by default = 100%
12
Setting the minimum speed
This setting affects the available torque. Without a special need, do not
change it.
Range: 20-95% - Value by default = 75%

TCR-02T CONTROL ELECTRICAL ACTUATOR
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.com / Email : sectorie[email protected]
Pages
6/8
Ref.
FT2415 ENG
Rev.
05
Date
05/2023
13
Setting the speed for the
stroke
This setting is used for setting a % of the actuator stroke during which it will
slow down before reaching the setpoint value position.
Range: 0.1-20% - Value by default = 10%
14
Redefining the 4 mA or 10V
position
Used to set another position than 0% for the 4 mA value. This function is
useful for valves with an opening angle different from 90°.
Range: -50% +80% - Value by default = 0.0%
15
Redefining the 20 mA
position
Used to set another position than 100% for the 20 mA or 10V value. This
function is useful for valves with an opening angle different from 90°.
Range: 20% +220% - Value by default = 100.0%
16
Modification of the 4 mA
output signal
If a deviation is found on the 4mA output signal, this function is used to
adjust it. If the number is increased, the current is higher. If the number is
decreased, the current is lower.
Range: 000_481_A –Value by default 191_A
NB: always limit the lower value to 20 mA
17
Modification of the 20mA
output signal
If a deviation is found on the 20mA output signal, this function is used to
adjust it. If the number is increased, the current is higher. If the number is
decreased, the current is lower.
Range: 191_1000_A –Value by default 909_A
18
Response time
Used to set the response speed of the valve. The smaller the value, the less
sensitive the control. The bigger the value, the more sensitive it is. Increase
the value when the response speed is too low.
Setting range: 1x20x –Value by default 3x

TCR-02T CONTROL ELECTRICAL ACTUATOR
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.com / Email : sectorie[email protected]
Pages
7/8
Ref.
FT2415 ENG
Rev.
05
Date
05/2023
19
Checking the feed signal
The actuator periodically tests its electrical power supply. A change of a value
will change the interval between two tests. In current use, there is no need
to change this parameter.
20
Power supply position by
default
This setting is not available on this version (see version T-KT)
Value by default: KEEP
21
Capacitor charge
This setting is not available on this version (see version T-KT)
Value by default: 95%
22
Alarm test
(version 4-20 mA)
This function is used to control whether a defect alarm is broadcast or not. It
is especially used for factory testing
Value by default: ON
23
Exiting the menu
Press K3 to exit the menu
The system will switch back in the automatic checking mode.

TCR-02T CONTROL ELECTRICAL ACTUATOR
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.com / Email : sectorie[email protected]
Pages
8/8
Ref.
FT2415 ENG
Rev.
05
Date
05/2023
TROUBLESHOOTING
Defect met
Cause of defect
Method of solving
Inactive actuator
Non-connected electrical grid.
Connect to the electrical grid.
Wrong voltage.
Check the actuator’s voltage.
Motor overheating.
Check the torque on the valve.
Faulty connection.
Check the connection to the terminal box.
Damaged start capacitor.
Contact the supplier for repair.
No switch signal
Faulty connection.
Check the connections.
Damaged microswitch
Change the microswitch
Valve that is not fully
closed
Use the return signal from the actuator
check.
Receiving a return signal does not mean
that the actuator is fully closed, hence do
not cut the power supply.
The hysteresis increases due to wear or
between the actuator and the valve’s stem.
Readjust the limit cams.
Contact the supplier for repair.
Presence of humidity or
water in the actuator
Unsuitable cable cross-section being used.
Contact the supplier for repair.
The cable connection is not leak-tight.
Worn sealing gaskets.
Loose cover screws.
Dry the internal parts and tighten the
cover screws.
Table of contents
Other Sectoriel Controllers manuals
Popular Controllers manuals by other brands

Omron
Omron CS1W-FLN22 Operation manual

Spirax Sarco
Spirax Sarco PLC Installation, operation and maintenance manual

National Instruments
National Instruments PXIe-8881 Getting started guide

Mitsubishi Electric
Mitsubishi Electric QX10 user manual

V2
V2 AYROS-24V series manual

JUMO
JUMO IMAGO F3000 operating instructions