Sectoriel TCR-05-11-T-KT User manual

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
1/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
FEATURES
TCR-T-KT electrical actuators are intended for motorising ¼ turn valves with a torque of 50 or 80 Nm.
Double proportional control function 4-20mA + closing manoeuvre provided by a super-capacitor. With a compact
construction and plastic housing, they are especially well suited for motorising small size ball valves. The actuator has
many advanced control functions which can be set from the screen. IP67 leak-tightness: to be used indoors and, possibly,
outdoors under a shelter. Manual control with a key.
AVAILABLE MODELS
Supply voltages: 230V AC, 24V AC/DC.
Control: 4-20 mA, 0-20 mA, 2-10V, 0-10V.
LIMITS OF USE
MECHANICAL FEATURES
Actuator
TCR 05T-KT32
TCR 11T-KT32
Torques (Nm)
50
80
Voltage
24V AC - DC
95-265V AC-DC
24V AC - DC
95-265V AC-DC
Adjustment signal
4-20 mA, 0-20 mA, 2-10V, 0-10V
Feedback signal
4-20 mA, 0-20 mA, 2-10V, 0-10V
Manoeuvring time (s)
12
12
10
10
ISO 5211:
F05/F07 - star 14
F05/F07 - star 17
ELECTRICAL FEATURES
Actuator
TCR 05T-KT32
TCR 11T-KT32
Motor protection
Thermal switch
Anti-condensation
integrated
Electrical connection
PE M20 + 1.5m cable
2 x PE M14
Actuator
TCR 05T-KT32
TCR 11T-KT32
Voltage
24V AC - DC
95-265V AC-DC
24V AC - DC
95-265V AC-DC
Power (W)
40
40
100
100
Current (A)
1,8
0,18
2,5
0,3 - 0,6
Fuse protection (A)
10
2
5
2
IP Code
IP 67
Ambient temperature
- 20°C / +60°C
Service factor
S4-50%
Gear box
treated steel pinions
Torques
50 - 110 Nm
Angle of rotation
90° +/- 2°
Declutching
without
Override control
By key
IP
67
ISO
9001

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
2/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
CONSTRUCTION (TCR-05T-KT32)
DIMENSIONS (mm)
TCR-05T-KT32
No.
Name
Material
No.
Name
Material
1
Casing + lid
Plastic (ABS)
7
1.3” LCD display
OLED
2
Position indicator
Polycarbonate plastic
8
Rating plate
PVC
3
Screw x 6
Ansi 304
9
Packing gland
Nylon
4
Backup control stem
Ansi 304
10
Hex key
Steel
5
Gasket
NBR
11
Key support
Plastic (ABS)
6
Adjustment button
Rubber
12
Cover gasket
NBR
Weight (kg): 1.800

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
3/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
CONSTRUCTION (TCR-11T-KT32)
DIMENSIONS (mm)
TCR-11T-KT32
No.
Name
Material
No.
Name
Material
1
Casing + lid
Plastic (ABS)
7
1.3” LCD display
OLED
2
Position indicator
Polycarbonate plastic
8
Rating plate
PVC
3
Screw x 6
Ansi 304
9
Key support
Plastic (ABS)
4
Backup control stem
Ansi 304
10
Hex key
Steel
5
Gasket
NBR
11
X 2Packing gland
Nylon
6
Adjustment button
Rubber
12
Cover gasket
NBR
Weight (kg): 2.200
13
Cable gland unit
Plastic (ABS)

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
4/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
WIRING DIAGRAM
DESCRIPTION OF THE 1.3’’ LCD SCREEN
1.3’’ LCD angle without any blind spot, strong luminosity, automatic switching to the economy saving mode at
the end of 5 minutes. The control screen displays the set value and the % of opening of the valve.
BU
Neutral (Blue)
RD
Closing control (Red)
Y/G
Earth (Yellow / Green)
BK
Alarm return information (Black)
GR
Alarm return information (Green)
PL
0-10V and 2-10V control signal (Purple)
GY
4-20mA and 0-20mA control signal (Grey)
BR
4-20mA and 0-20mA feedback (Brown)
WT
Common control/feedback signals (White)
OG
0-10V and 2-10V feedback (Orange)

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
5/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
CONTROL IN LOCAL MODE
1
Press the K3 button for 5 seconds, until “K3” flashes at the top right of the screen.
2
Enter the password “111”
3
Press the K2 button to manoeuvre clockwise. The screen displays the % of opening. Release when the desired
position is reached.
Press the K3 button to manoeuvre anti-clockwise. The screen displays the % of opening. Release when the desired
position is reached.
PARAMETER SETTING MENU OF THE ACTUATOR
The following functions can have their parameters set from the menu accessible on the screen:
STEP
TITLE
FUNCTION AND VALUES
1
Standby screen
If the actuator did not receive any signal in the last 5 minutes, the
screen switches to standby. Press any button for 5 s. Then reactivate
the screen.
2
Enter the password
Press the “M” button for more than 5 s.
Enter the code “333” (use the keys K2 and K3)
Press again the button “M”
3
Choice of language
English or Mandarin
4
Choosing the control signal
Press “K3” to chose the control signal
Possible signals: 4-20mA, 0-20mA, 2-10V, 0-10V
Press “M” again to continue

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
6/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
5
Choosing the direction of rotation
of the actuator
Direct 4mA = valve closed / 20 mA = valve open
Inverted 4 mA = valve closed / 20 mA = valve open
6
Position by absence of any
control signal
In the absence of a control signal, the valve can take 3 positions: ON,
OFF or KEEP
7
Dead band
This function is used to set the accuracy and the sensitivity of the
control: the larger the band, the lower the accuracy; the narrower the
band, the more oscillating the system can be.
Setting range: 0.1 to 9.9% - Setting by default: 0.8%
8
Hysteresis adjustment
This parameter setting is a prerequisite for the next.
YES = adjustment is possible
NO = no adjustment is possible (value by default)
9
Hysteresis value
If the previous parameter is “YES”, it is possible to set the hysteresis
value between 0.1 and 9.9%. The value by default is 0.2%. Do not use
the function if there is a play between the valve’s stem and the
actuator’s square.
10
Redefining the 4 mA position
Used to set another position than 0% for the 4 mA value. This function
is useful for valves with an opening angle different from 90°.
Range: -50% +80% - Value by default = 0.0%
11
Redefining the 20 mA position
Used to set another position than 100% for the 20 mA value. This
function is useful for valves with an opening angle different from 90°.
Range: +81% +220% - Value by default = 100.0%

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
7/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
12
Manual adjustment of the speed
of rotation
This function is used for slowing down the motor.
Range: 20-100% - Value by default = 100%
13
Setting the maximum speed
This setting affects the available torque. Without a special need, do not
change it.
Range: 20-100% - Value by default = 100%
14
Setting the minimum speed
This setting affects the available torque. Without a special need, do not
change it.
Range: 20-95% - Value by default = 75%
15
Setting the speed for the stroke
This setting is used for setting a % of the actuator stroke during which it
will slow down before reaching the setpoint value position.
Range: 1-20% - Value by default = 10%
16
Braking time
In order to increase the stability of the motor, the motor will slow down
after a short time before reaching its setpoint value position. During
current use, this function is not useful.
Range: 0-50 ms –Value by default = 1 ms
17
Modification of the input signal
4 mA
The function is used to modify the 4mA input signal. If the value of the
parameter is increased, the signal will be increased. If the value is
decreased, the signal will be decreased. It is not recommended to
change the factory settings.
18
Modification of the 20mA input
signal
The function is used to modify the 20mA input signal. If the value of the
parameter is increased, the signal will be increased. If the value is
decreased, the signal will be decreased. It is not recommended to
change the factory settings.

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
8/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
19
Modification of the output signal
4 mA
If a deviation is found on the 4mA output signal, this function is used to
adjust it. If the number is increased, the current is higher. If the number
is decreased, the current is lower.
Range: 000_481_A –Value by default 191_A
NB: always limit the lower value to 20 mA
20
Modification of the 20mA output
signal
If a deviation is found on the 20mA output signal, this function is used
to adjust it. If the number is increased, the current is higher. If the
number is decreased, the current is lower.
Range: 191_1000_A –Value by default 909_A
21
Power supply position by default
Setting the position of the valve in the event of a power cut. This
manoeuvre will be carried out if the capacitor is sufficiently charged.
Possible values:
KEEP: unchanged position of the valve
ON: opening of the valve
OFF: valve closing
Value by default: OFF
22
Response time
Used to set the response speed of the valve. The smaller the value, the
less sensitive the control. The bigger the value, the more sensitive it is.
Increase the value when the response speed is too low.
Setting range: 1x20x –Value by default 3x
23
Checking the feed signal
The actuator periodically tests its electrical power supply. A change of a
value will change the interval between two tests. In current use, there is
no need to change this parameter.

REGULATING ELECTRICAL ACTUATOR
+ RETURN BY SUPER-CAPACITOR TCR-05-11-T-KT
Information given as an indication only, and subject to possible modifications
SECTORIEL S.A.
45 rue du Ruisseau
38290 SAINT QUENTIN-FALLAVIER –FRANCE
Telephone: +33 4 74 94 90 70 - Fax: +33 4 74 94 13 95
www.sectoriel.fr / Email : sectoriel@sectoriel.fr
Pages
9/9
Ref.
FT2419B ENG
Rev.
01
Date
02/2020
24
Super-capacitor charge
This parameter is used to set the % of charge on the super-capacitor
from which on the actuator switches to the automatic mode.
Setting range: 60-99%
Value by default: 95%
Do not set below 80%, the charge will be insufficient and would set off
the motor alarm
25
Actuator locking after the
intervention of the super-
capacitor
Used to seal off the valve if an emergency manoeuvre occurred.
Value by default: UNLOCK
26
Alarm test
This function is used to control whether a defect alarm is broadcast or
not. It is especially used for factory testing
Value by default: ON
27
Exiting the menu
Press K3 to exit the menu
The system will switch back in the automatic checking mode.
TROUBLESHOOTING
Defect met
Cause of defect
Method of solving
Inactive actuator
Non-connected electrical grid.
Connect to the electrical grid.
Wrong voltage.
Check the actuator’s voltage.
Motor overheating.
Check the torque on the valve.
Faulty connection.
Check the connection to the terminal box.
Damaged start capacitor.
Contact the supplier for repair.
No switch signal
Faulty connection.
Check the connections.
Damaged microswitch
Change the microswitch
Valve that is not fully
closed
Use the return signal from the actuator
check.
Receiving a return signal does not mean
that the actuator is fully closed, hence do
not cut the power supply.
The hysteresis increases due to wear or
between the actuator and the valve’s stem.
Readjust the limit cams.
Contact the supplier for repair.
Presence of humidity or
water in the actuator
Unsuitable cable cross-section being used.
Contact the supplier for repair.
The cable connection is not leak-tight.
Worn sealing gaskets.
Loose cover screws.
Dry the internal parts and tighten the
cover screws.
This manual suits for next models
2